1) Measuring Touch Current Without Tripping the RCD
Measuring Method
The instrument uses a measuring current of only ⅓ nominal resid-
ual current for the determination of touch voltage UIΔN which
occurs at nominal residual current. This prevents tripping of the
RCCB.
This measuring method is especially advantageous, because
touch voltage can be measured quickly and easily at any electrical
outlet without tripping the RCCB.
The usual, complex measuring method involving testing for the
proper functioning of the RCD at a given point, and subsequent
substantiation that all other systems components requiring pro-
tection are reliably connected at low resistance values to the
selected measuring point via the PE conductor, is made unneces-
sary.
N-PE Reversal Test
Additional testing is conducted in order to
determine whether or not N and PE are
reversed. The pop-up window shown at
the right appears in the event of reversal.
Attention!
!
In order to prevent the loss of data in data processing
systems, perform a data backup before starting the
measurement and switch off all consumers.
Start Measurement
Amongst other values, touch voltage UIΔN and calculated earthing
resistance RE appear at the display panel.
Note
The measured earthing resistance value RE is acquired
with very little current. More accurate results can be
obtained with the selector switch in the RE position.
The DC + function can be selected here for sys-
tems with RCCBs.
Unintentional Tripping of the RCD due to Bias Current within the
System
If bias currents should occur, they can be measured with the help
of a clamp type current transformer. The RCCB may be tripped
during the testing of touch voltage if extremely large bias currents
are present within the system, or if a test current was selected
which is too great for the RCCB.
After touch voltage has been measured, testing can be performed
to determine whether or not the RCCB is tripped within the
selected time limit values at nominal residual current.
Unintentional Tripping of the RCD due to Leakage Current in the
Measuring Circuit
Measurement of touch voltage with 30% nominal residual current
does not normally trip an RCCB. However, the trip limit may be
exceeded as a result of leakage current in the measuring circuit,
e.g. due to interconnected consumers with EMC circuit, e.g. fre-
quency converters or PCs.
2) Tripping Test after the Measurement of Touch Voltage
Press the I
Δ
N
key
The tripping test need
only be performed at
one measuring point for
each RCCB.
If the RCCB is not tripped at nominal residual current, the MAINS/NETZ
LED blinks red (line voltage disconnected) and, amongst other val-
ues, time to trip ta and earthing resistance RE appear at the dis-
play panel.
If the RCCB is not tripped at nominal residual current, the LIMIT LED
lights up red.
Touch Voltage Too High
If touch voltage UIΔN, which has been measured with ⅓ nominal
residual current IΔN and extrapolated to IΔN, is > 50 V (> 25 V), the
LIMIT LED lights up red.
If touch voltage UIΔN exceeds 50 V (25 V) during the measuring
sequence, safety shut-down occurs.
Note
Safety Shut-down: At up to 70 V, a safety shut-down is
tripped within 3 seconds in accordance with IEC 61010.
Touch voltages of up to 70 V are displayed. If the value is greater
than 70 V, UIΔN > 70 V is displayed.
Limit Values for Allowable, Continuous Touch Voltage
The limit for allowable, continuous touch voltage is equal to
UL= 50 V for alternating voltages (international agreement).
Lower values have been established for special applications
(e.g. medical applications: UL=25V).
Attention!
!
If touch voltage is too high, or if the RCCB is not tripped,
the system must be repaired (e.g. earthing resistance is
too high, defective RCCB etc.)!
3-Phase Connections
For proper RCD testing at three-phase connections, the tripping
test must be conducted for one of the three phase conductors
(L1, L2 or L3).
Inductive Power Consumers
Voltage peaks may occur within the measuring circuit if inductive
consumers are shut down during an RCCB trip test. If this is the
case, the test instrument might not display any measured value
(– – –). If this message appears, switch all consumers off before
performing the trip test. In extreme cases, one of the fuses in the
test instrument may blow, and/or the test instrument may be
damaged.
19

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Gossen Metrawatt Profitest Intro bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Gossen Metrawatt Profitest Intro in de taal/talen: Engels als bijlage per email.

De handleiding is 1.69 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info