Installation instructions auroMATIC 620 0020094404_00 controller 140
Loadpump overrun
The cylinder charging pump overrun starts after swit-
ching off of the boiler at the end of the cylinder
charging. During this time, no temperature requirement
is required from the heater(s) which have carried out
the cylinder charging. All other functions (controlling of
the charging pump/switching valve) remain on during
this period of time. This
function is used to supply the high inlet temperatures
required for charging the cylinder to a great extent
before the heating circuits, in particular the burner cir-
cuit, are enabled again.
Maximum limit outside temperature
The maximum limit outside temperature is the outside
temperature at which the demand-dependent heating
shutdown (automatic shutdown in summer) takes effect.
The maximum outside temperature limit can be set
separately for each heating circuit within a range of 5
to 50 °C. The default setting is 21 °C. The required room
temperature is set to 20 °C for each heating circuit
(default setting). If the required room temperature is
changed in the basic menu, the maximum limit for the
outside temperature must also be changed (at least 1 °C
higher than the required room temperature).
Maximum preheating
With this function the activation of the heating circuit
before the heating window is made possible, with the
aim of accessing the set day value at the beginning of
the heating window.
The function is only performed for the first heating win-
dow of the day. The beginning of heating is established,
depending on the outside temperature.
Influence of outside temperature:
OT –20 °C : set preheating period
OT +20 °C : no preheating period
The period of time is calculated linearly between the
two reference values.
Once preheating has been started, it is only ended once
the time window has been reached (not ended if the
outside temperature rises in the meantime).
Maximum preset switch off
This function is used to avoid unnecessary heating of
the heating system directly before a preprogrammed
set-back time. The calculation of the actual time
depends on the outside temperature of the controller.
The set value merely represents the maximum period of
time desired by the customer. Tf the outside tempera-
ture is at -20°C, there is no preset switch-off; at an out-
side temperature of +20°C, the maximum preset switch-
off comes into effect. At outside temperature between
these two reference values, the controller calculates a
value that corresponds to a linear curve between these
two reference values.
Maximum temperature of heating circuit
The maximum forward flow temperature can be set for
each heating circuit. The calculated flow set target tem-
peratures are limited to the set value.
Maximum temperature of solar cylinder
In order to ensure the highest possible gain from the
solar heating of the cylinder, while at the same time
ensuring that limescale protection is active, you can set
a maximum value for the solar temperature cylinder.
For this purpose, the "Upper cylinder temp." sensor,
SP1, is used for Cylinder 1 if it is connected to the cylin-
der in question. Otherwise, the "Lower cylinder temp."
sensor, SP2, is automatically used. For the second cylin-
der (swimming pool), SP3 is used.
If the set maximum temperature is exceeded, the solar
circuit pump is switched off. Solar charging is only
enabled again once the temperature at the active sen-
sor drops 1.5 K below the maximum temperature.
Minimum temperature for solar circuit and solid fuel
boiler
The minimum temperature for each solar circuit or for
the solid fuel boiler (for hydraulic plans with solid fuel
boilers) can be set in the range 0 ... 99 °C.
Note: The delta-T control will only be enabled when the
temperature at the collector sensor > minimum tempe-
rature.
Note: Does not apply in combination with a VPM S or
VMS solar pump unit.
Minimum temperature of heater
The minimum boiler temperature is used to protect the
boiler, e. g. against corrosion, if, for example, the boiler
has to be operated permanently in the condensate
range due to high water capacities. The setting range is
between 15 and 65 °C (default 15 °C).
Mixing circuit/Mixer control
A mixed heating circuit is a heating circuit which is
decoupled from the boiler circuit (temperature) by an
actuator (mixer).
Night set back temperature
The night set back temperature is the temperature to
which your heating system reduces the room tempera-
ture outside of the programmed time window.
Number of heating appliances
They are usually already configured with the system –
parameter setting is only necessary in exceptional cases
(e.g. removing heating appliances (HA) from the sys-
tem).
Number of steps
The stages are usually already configured with the sys-
tem – parameterisation is only necessary in cases where
a two-stage burner is to be actuated in a single stage.
Glossary
198

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Vaillant VRS 620-3 bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Vaillant VRS 620-3 in de taal/talen: Engels als bijlage per email.

De handleiding is 6,37 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Andere handleiding(en) van Vaillant VRS 620-3

Vaillant VRS 620-3 Gebruiksaanwijzing - Nederlands - 204 pagina's

Vaillant VRS 620-3 Gebruiksaanwijzing - Deutsch - 52 pagina's

Vaillant VRS 620-3 Gebruiksaanwijzing - Français - 204 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info