139Installation instructions auroMATIC 620 0020094404_00 controller
Fast temperature increase
This function is used for mixer heating circuits
a) to allow the mixer to reach its target value at target
boiler temperature shortly before the boiler is swit-
ched on again despite being fully open,
b) to allow, in the event of mixing circuits with a fixed
admixture, the target mixer value (also at target hea-
ter temperature) to be reached during the morning
heating-up operation even though the fixed admix-
ture reduces the mixing circuit temperature too far,
c) in order to facilitate an optimum control range for
the operation of the mixer. (Reliable operation is only
possible if the mixer only rarely needs to move to the
"open" stop, thus ensuring a better quality of cont-
rol).
For this reason you can set a common boiler tempera-
ture excess for all mixing circuits. This will increase the
current heating circuit target value by the value set.
Fixed value circuit/Fixed value control
This function is required for special applications such as
vent curtains, fans etc. This type of control is performed
at a fixed inlet temperature regardless of the required
room temperature and outside temperature.
All operating modes can be set for this type of control.
Demand-dependent switching off of heating works in
the same way.
Floor drying
The floor-drying function is used to “heat dry” a freshly-
laid heating layer according to instructions. All opera-
ting modes, including those selected by telephone, are
interrupted if this function is activated. The flow tempe-
rature of the controlled heating circuit is controlled
according to a pre-set program regardless of the out-
side temperature.
Starting temperature: 25°C
The operating mode is displayed together with the cur-
rent day and the target inlet temperature. The current
day can be set manually.
When the function is started, the current time of the
start is saved. The change of day takes place in each
case
exactly at this time.
After a mains off/on, the floor-drying begins with
the last active day.
Frost protection delay/ Heating frost protection
The heating frost protection function ensures protec-
tion from frost in the Off and Eco modes (outside the
time windows) in the heating installationand applies to
all connected heating circuits. To prevent the system
from freezing, the required room temperature is set to
the set set-back value and the heating circuit pump is
switched on if the outside temperature falls below 3 °C.
The frost protection function can be suppressed for a
certain period of time by setting a delay time (setting
range of 0 - 23 h).
Furthermore frost protection is activated regardless of
the measured outside temperature if it is established
that the measured room temperature is lower than the
set night set back temperature with a connected remote
control device.
Heating curve
The flow temperature in heating installations, calculated
as a function of the outside temperature, is known as
the heating curve. The flow temperature in the heating
circuit gets warmer the lower the outside temperature
becomes.
Hot water priority
The hot water priority switch is only active if the DHW
cylinder in hydraulic plans 5-8 is connected directly to
the priority switching valve or the charging pump for
the boiler. Cylinder sensor TD2 remains connected to
the VRS 620. With this hydraulic connection the boiler
can charge either the buffer cylinder or the DHW cylin-
der.
Hot water reheating for drinking water cylinder
Reheating of the drinking water cylinder (SP1 with
hydraulic plan 1–4 or SP4 with hydraulic plan 5–8)
always occurs if:
the cylinder circuit is within the programmed time
window,
the cylinder temperature is 5K below the preset tar-
get value.
The activated recharging delay prevents charging of the
cylinder for the preset length of time if there is a solar
gain present. In hydraulic plan 9, the reheating is initia-
ted by the VPM W fresh water unit. See the VPM W
manual.
Legionella
Legionella are water-borne bacteria which can quickly
propagate and cause serious lung diseases. They occur
wherever heated water provides the optimum condi-
tions for multiplication. Temporarily heating the water
to above 65 °C kills off the legionella.
Glossary
197

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Vaillant VRS 620-3 bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Vaillant VRS 620-3 in de taal/talen: Engels als bijlage per email.

De handleiding is 6,37 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Andere handleiding(en) van Vaillant VRS 620-3

Vaillant VRS 620-3 Gebruiksaanwijzing - Nederlands - 204 pagina's

Vaillant VRS 620-3 Gebruiksaanwijzing - Deutsch - 52 pagina's

Vaillant VRS 620-3 Gebruiksaanwijzing - Français - 204 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info