Installation instructions auroMATIC 620 0020094404_00 controller 138
Glossary
Activation duration controlling
Activation duration controlling serves to keep the solar
circuit at the activation value, and thus in operation, for
as long as possible. For this purpose the pump is swit-
ched on and off in periodical thrusts depending on the
collector temperature and lower storage tank tempera-
ture. On reaching the switch-on difference, the function
is started (if activated) with an activation duration of 30
% - i.e. the pump is switched on for 18 s and then swit-
ched off for 42 s. In the temperature difference incre-
ases, the activation duration is increased (e.g. 45 s on,
15 s off). In the temperature difference decreases, the
activation duration is decreased (e.g. 20 s on, 40 s off).
The period length is always a minute.
Note: Does not apply in combination with a VPM S or
VMS solar pump unit.
Actual flow temperature
The flow temperature actually present in a heating cir-
cuit.
Anti-legionella function
The anti-Legionella function can only be activated glo-
bally for all cylinder charging circuits. When active, the
function is carried out at the predetermined time: 1x
weekly or daily at the selected time, the respective
cylinder and the corresponding hot water pipes are rai-
sed to a temperature of 70 °C. To achieve this, the tar-
get value for the cylinder in question is increased to
68/70 °C (2 K hysteresis) and the corresponding circu-
lation pump is switched on. The function is terminated
when the cylinder sensor measures a temperature
68 °C for longer than 30 mins, or after a period of 90
mins has elapsed (to avoid getting “stuck“ in this func-
tion if water is drawn simultaneously).
Anti-legionnaire’s disease protection is naturally not
carried out for the swimming pool (storage tank 3).
Peculiarities: If the 230 V contact is configured as an
"Anti-legionella contact", a solar pump is started up via
this contact, which mixes the contents of the solar cylin-
der thoroughly, so that the lower region of the cylinder
can attain the necessary temperature.
If a temperature of > 68 °C has already been reached at
the lower solar sensor through a solar filling, the heater
doesn’t have to be switched on. Then only the anti-
legionnaire’s disease contact and circulation pump are
switched on.
AT continuous heating
Outside temperature below which heating using the tar-
get room temperature/heating curve assigned to the
heating circuit is continuous outside the programmed
time window.
A night time reduction or total switch-off no longer
takes place if the temperature reaches or falls below
the set value.
Bleeding function solar circuit
The solar circuit pump is activated for an adjustable
period of up to 600 minutes from the A7 menu to carry
out bleeding independent of the controller.
Note: This function is not supported in combination with
the VPM S and the VMS, as both solar pump units carry
out bleeding permanently.
Control behaviour of the mixing circuit:
If the current temperature of the mixing circuit deviates
by more than +/- 0.5 K from the target inlet tempera-
ture required by the controller, the mixer valve is actua-
ted via the mixer motor with impulses of variable activa-
tion duration (AD). The duty cycle (voltage signal for
"open" or "closed") depends on the control deviation,
i.e. on the difference between the actual and target flow
temperatures and the conversion factor.
In the default setting, we have pre-set a proportional
band of 12 K, i. e. controlling is performed at a switch-on
ratio of 100 % in the “open” or “closed” direction in the
event of a control deviation of 12 K or more. If control
deviation is, for example, 6 K, the mixer is controlled at
a switch-on ratio of 50 %. Since the period time has a
fixed cycle time of 20 seconds, this means that the
mixer is operated 10 seconds in “open” or “closed”
direction and is at a standstill for 10 seconds.
Cylinder charging circuit/cylinder recharging delay
With the controller, the cylinder charging circuit is used
for the timed enabling of the reheating function. The
reheating takes place within the programmed timer pro-
gramme, provided the target cylinder temperature has
not been reached yet. The cylinder recharging is activa-
ted when the target cylinder temperature is exceeded
by more than 5 K.
In order to avoid unnecessary recharging, a recharging
delay function has been integrated. In this case, if the
solar pump is running, the actual required reheating is
delayed by the preset value. If the solar pump switches
off during the delay period, reheating takes place imme-
diately.
The controller has a factory-set timer program, which
you can customise:
Mon - Fri 5:30 - 22:00
Sat 7:00 - 23:30
Sun 7:00 - 22:00
The preset times do not apply to the VPM W.
Cylinder frost protection
The temperature in the cylinder is always maintained at
a minimum level of 12 °C. The cylinder frost protection
is ineffective if a contact at the cylinder sensor input is
activated (R 0 Ohm – R infinite).
Glossary
196

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Vaillant VRS 620-3 bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Vaillant VRS 620-3 in de taal/talen: Engels als bijlage per email.

De handleiding is 6,37 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Andere handleiding(en) van Vaillant VRS 620-3

Vaillant VRS 620-3 Gebruiksaanwijzing - Nederlands - 204 pagina's

Vaillant VRS 620-3 Gebruiksaanwijzing - Deutsch - 52 pagina's

Vaillant VRS 620-3 Gebruiksaanwijzing - Français - 204 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info