MODE 8 LATCH OUTPUT AT PRESET 1 AND ZERO, MANUAL RESET TO
PRESET 2, TIME STOPS AT ZERO (INSTANTANEOUS & TIME
DELAY CONTACT, TIME DOWN)
In this mode, as the unit times down from preset 2, output 1 will
latch on when preset 1 is reached and output 2 will latch on when
zero is reached. The unit will stop timing when zero is reached.
This mode also has an input tracking feature (INSTANTANEOUS
CONTACT) where if preset 1 is set to zero, output 1 will turn on when the
input is activated, and it will turn off when the input is deactivated. (Output 2
is the TIME DELAY CONTACT.) When a manual resetoccurs, the unit will
Reset to Preset and the outputs, if latched on, will unlatch.
To use as an INSTANTANEOUS AND TIME DELAY CONTACT timer,
set preset 1 value to zero and set preset 2 value to the desired delay value.
When “RUN” is at a low level, time will decrement and output 1 will be
activated. Output 2 (TIME DELAY CONTACT) will activate when zero is
reached. To recycle use 1) reset, or 2) set the power-up reset switch to enable,
then remove and reapply input power.
MODE 9 LATCH OUTPUT AT PRESET 1 AND ZERO, MANUAL RESET TO
PRESET 2, TIME CONTINUES AT ZERO (INSTANTANEOUS & TIME
DELAY CONTACT, TIME DOWN)
In this mode, as the unit times down from preset 2, output 1 will
latch on when preset 1 is reached, and output 2 will latch on when
zero is reached. Time will continue to accumulate after zero is
reached. This mode also has an input tracking feature (INSTANTANEOUS
CONTACT) which if preset 1 is set to zero, output 1 will turn on when the
input is activated, and it will turn off when the input is deactivated. (Output 2
is the TIME DELAY CONTACT.) When manual resetoccurs, the unit will
Reset to Preset 2 and the outputs, if latched on, will unlatch.
To use as an INSTANTANEOUS AND TIME DELAY CONTACT timer,
follow the description under Mode 8.
MODE 10 OUTPUT 1 TURN OFF AT ZERO, LATCH OUTPUT 2 AT ZERO,
MANUAL RESET TO PRESET 2, TIME STOPS AT PRESET 2
(INTERVAL, TIME DOWN)
In this mode, as the unit times down from preset 2, output 1 will
turn on when preset 1 is reached. When zero is reached, output 2
will turn on and output 1 will turn off. Output 2 will remain latched
on until a manual reset occurs, and the unit will stop timing when zero is
reached. This mode also has an input tracking feature where if preset 1 is set
to zero, output 1 will turn on when the input is activated, and it will turn off
when the input is deactivated. (After zero is reached output 1 will turn off and
stay off, regardless of the input condition, until a manual resetoccurs.) When
a manual resetoccurs, the unit will Reset to Preset 2 and the outputs, if
latched on, will unlatch.
MODE 11 OUTPUT 1 TURN OFF AT ZERO, LATCH OUTPUT 2 AT ZERO,
MANUAL RESET TO PRESET 2, TIME CONTINUES AT PRESET 2
(INTERVAL, TIME DOWN)
In this mode, as the unit times down from preset 2, output 1 will
turn on when preset 1 is reached. When zero is reached, output 2
will turn on and output 1 will turn off. Output 2 will remain latched
on until a manual reset occurs, and the unit will continue to accumulate time
after zero is reached. This mode also has a input tracking feature where if
preset 1 is set to zero, output 1 will turn on when the input is activated, and it
will turn off when the input is deactivated. (After zero is reached, output 1 will
turn off and stay off, regardless of the input condition, until a manual reset
occurs.) When manual resetoccurs, the unit will Reset to Preset 2, and the
outputs, if latched on, will unlatch.
MODE 12 TIMED OUTPUT AT PRESET 1 AND ZERO, MANUAL RESET TO
PRESET 2, TIME STOPS AT ZERO
In this mode, as the unit times down from preset 2, output 1 will
turn on when preset 1 is reached, and output 2 will turn on when zero
is reached. The outputs will turn off after their respective
programmed time values have occurred. Also, the unit will stop timing when
zero is reached. When a manual resetoccurs, the unit will Reset to Preset 2.
Manual resetwill terminate the timed outputs, if the outputs are still turned on.
- Manual reset, either by front panel reset (if enabled) or remote reset, is
always active, and will override any present condition or state of the timer.
MODE 13 TIMED OUTPUTS AT PRESET 1 AND ZERO, AUTOMATIC RESET
TO PRESET 2 AFTER TIMED OUTPUT 2 (TWO LOBE OFF/ON
RECYCLING, TIME DOWN)
In this mode, as the unit times down from preset 2, output 1 will
turn on when preset 1 is reached and output 2 will turn on when
zero is reached. The outputs will turn off after their respective
programmed time values have occurred. Also, at the end of timed output 2, the
unit will automatically Reset to Preset 2 and start the cycle over. Manual
resetwill turn off both outputs, if turned on, and reset the time to preset 2.
When used as an OFF/ON RECYCLING timer, the total cycle time is equal
to the sum of the preset 2 value and the programmed timed output 2 value. The
first lobe of the cycle will use output 1. The first ON delay is equal to the
programmed timed output 1 value.✝✝ The second lobe of the cycle will use
output 2. The second ON delay is equal to the programmed timed output 2
value.✝✝ When “RUN” is at a low level, time will decrement. Output 1 (first
ON delay) will activate when preset 1 is reached, and output 2 (second ON
delay) will activate when zero is reached. The unit will recycle at the end of
timed output 2.
MODE 14 TIMED OUTPUTS AT PRESET 1 AND ZERO, AUTOMATIC RESET
TO PRESET 2 AT ZERO (TWO LOBE OFF/ON RECYCLING, TIME
DOWN)
In this mode, as the unit times down from preset 2, output 1 will
turn on when preset 1 is reached and output 2 will turn on when
zero is reached. The outputs will turn off after their respective
programmed time values have occurred. Also when zero is reached, the unit
will automatically reset the time to preset 2 and start the cycle over. (Output 2
will remain on until its time value has occurred.) Manual resetwill turn off
both outputs, if still turned on, and reset the time to Preset 2.
When used as an OFF/ON RECYCLING timer, the total cycle time is equal
to the preset 2 value. The first lobe of the cycle will use output 1. The first ON
delay is equal to the programmed timed output 1 value.✝✝ The second lobe of
the cycle will use output 2. The second ON delay is equal to the programmed
timed output 2 value.✝✝ When “RUN” is at a low level, time will decrement.
Output 1 (first ON delay) will activate when preset 1 is reached, and output 2
(second ON delay) will activate when zero is reached. The unit will recycle at
the beginning of timed output 2.
MODE 15 OUTPUT 1 TURN OFF AT ZERO, TIMED OUTPUT 2 AT ZERO,
AUTOMATIC RESET TO PRESET 2 AFTER TIMED OUTPUT 2
(INSTANTANEOUS & TWO LOBE OFF/ON RECYCLING, TIME
DOWN)
In this mode, as the unit times down from preset 2, output 1 will
turn on when preset 1 is reached. When zero is reached output 2
will turn on and output 1 will turn off. Output 2 will turn off after
its programmed time value has occurred. At the end of Timed output 2, the unit
will automatically Reset to Preset 2 and start the cycle over. This mode also
has an input tracking feature (INSTANTANEOUS CONTACT) where if preset
1 is set to zero, output 1 will turn on when the input is activated, and off when
the input is deactivated. (After zero is reached, Output 1 will turn off and stay
off, regardless of the input condition, until a reset occurs.) Manual resetwill
turn off both outputs, if turned on, and reset the time to preset 2.
When used as an OFF/ON RECYCLING timer, the total cycle time is equal
to the sum of the preset 2 value and the programmed timed output 2 value. The
first lobe of the cycle will use output 1. The first ON delay value is equal to
the difference between preset 1 and zero (this is because output 1 will turn off
at zero). The second lobe of the cycle will use output 2. The second ON delay
value is equal to the programmed timed output 2 value.✝✝ When “RUN” is at
a low level, time will decrement. Output 1 (first ON delay) will activate when
preset 1 is reached, and output 2 (second ON delay) will activate when zero is
reached (output 1 will deactivate when zero is reached). The unit will recycle
at the end of timed output 2.
- The timed output value must be less than the value required to time from
the reset condition to the preset point. Otherwise, the output will appear to
be latched on.
✝✝ - The maximum ON delay is 99.99 seconds.
Note: Many other modes of operation, too numerous to mention here, are
possible with the Libra Timer. These “extra” modes of operation are
accomplished by tying inputs to outputs, by using power up reset
functions, etc.
MODES OF OPERATION FOR DUAL PRESET LIBRA TIMER (Cont’d)
5

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Red Lion Libra Series Timers bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Red Lion Libra Series Timers in de taal/talen: Engels als bijlage per email.

De handleiding is 0.34 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info