English / Page 26
Tests instructions:
• Interrupt the light path in the bottom door seal; this can be achieved by
deforming the seal or by removing the transmitter or receiver bung.
• It should now not be possible to subsequently close the door by press and
release.
• Make the light path in the bottom door seal clear again.
• It should now be possible again to close the door by press and release.
7. Connection of closing edge safety device
Displays on the optosensor circuit board:
GREEN LED: Voltage
YELLOW LED Static current circuit closed (should go out when cable slack
or wicket door device actuated)
RED LED Optosensor function indicator
(should go out when light beam interrupted)
Operational check
of the closing edge safety device:
• Switch on at the mains.
• Operate the door to arrive at its OPEN travel limit
• Press the CLOSE button (12).
- The door should close by press and release.
-> If this is not the case, check the optosensor (see test instructions).
• Whilst the door is still closing, press the bottom door seal together.
- The door should come to a halt, then rise a short distance.
-> If this is not the case, check the optosensor (see test instrcutions)
• Switch off at the mains.
Operational check of the optosensors:
Attention!
The function of optosensors should be checked at least once a
year in order to guarantee safe operation of the door system.