GB OPERATING INSTRUCTIONS
These operating instructions contain detailed information on the installation, commissioning and setting
options of the product described. The current version of this document is available on the respective
product page at www .esylux.com and can be printed out in A4 format. Read the operating instructions
carefully and observe all safety instructions and warnings.
1 • SAFETY INSTRUCTIONS
CAUTION: Electrical devices connected to a 230 V mains supply may only be assembled and
commissioned by electrical installation technicians or trained electricians, taking country-specific
regulations into account.
Use this product only as intended (as described in the user instructions). Changes or
modifications to the product or painting it will result in loss of warranty. You should check
the device for damage immediately after unpacking it. If there is any damage, you should
not install the device under any circumstances.
If you suspect that safe operation of the device cannot be guaranteed, you should turn the
device off immediately and make sure that it cannot be operated unintentionally.
2 • DESCRIPTION
Motion and presence detectors are passive infrared detectors that automatically switch
connected lighting depending on natural light and presence / movement and are suitable
for use indoors. An additional “HVAC” switch contact (depending on detector type)
can be used for controlling another light source / panel light or for controlling heating,
ventilation and air conditioning (HVAC), depending on presence.
3 INSTALLATION / ASSEMBLY / CONNECTION
Please refer to the supplied leaflet for instructions.
4 • START-UP
Connect the power supply
A warm-up phase of approx. 25 seconds is initiated.
The red (channel 1 = C1), green (channel 2 = C2 / if present) and blue LEDs flash alternately.
The connected lighting is switched on.
The remote controllable detectors are supplied with factory settings and are therefore
immediately ready for use after the warm-up phase.
Overview of factory settings:
Detector type MD-C 360i/8 PD-C 360i/8 PD-C 360i/8plus
MD-C 360i/8 MIC PD-C 360i/8 MIC PD-C 360i/24plus
MD-C 360i/24 PD-C 360i/24 PD-C 360i/32plus
MD-C 360i/32 PD-C 360i/24 DRY
MD-C 360i/32 Corridor PD-C 360i/32
PD-C 360i/32 Corridor
Light value 1 Passageway
(approx. 100 lux)
Working area
(approx. 400 lux)
Working area
(approx. 400 lux)
“Light channel” time setting 5 min. 5 min. 5 min.
“HVAC channel” time setting 60 min.
Mode Fully automatic Fully automatic Fully automatic
4.1 Function after the warm-up phase
Fully automatic mode – switching channel “lighting-C1”
If the ambient lighting level is higher than the default light value, the red LED and the
connected lighting will be switched off.
Automatic switch-on: if the detector has been triggered by movement and the ambient
lighting level has fallen below the default light value.
The red LED is enabled to indicate motion detection: two short flashes each time movement
is detected.
Automatic switch-off: if movement is no longer detected, the lighting will be switched off
once the set time has elapsed.
Note on presence detectors: However, should the natural lighting level increase and the ambient
lighting level exceed the preset light value, the detector will automatically switch the lighting off
5 minutes after reaching the preset light value, regardless of any movement / presence.
The lighting can subsequently be switched back on manually at any time.
Delay
When persons are present, in order to avoid sudden changes in brightness caused by
undesired switching on / off of the lighting, the detector will only be triggered after a
time delay.
Example: A passing cloud could potentially cause unnecessary switching.
Time delay from light to dark: 30 sec. = red LED lights up during this period.
Time delay from dark to light: 5 min. = red LED flashes slowly during this period.
Fully automatic mode – switching channel “HVAC-C2” (heating, ventilation, air conditioning or lighting / if present)
Automatic switch-on: The contact is independent of the light value and will only be triggered
by movement.
The green LED is enabled to indicate motion detection: two short flashes each time
movement is detected (no LED indication for DUO version).
Automatic switch-off: If movement is no longer detected, the contact will be switched off
once the set time has elapsed.
ESYLUX GmbH • An der Strusbek 40
22926 Ahrensburg / Germany
info@esylux.com • www.esylux.com
BA01635504
Individual adjustments can easily be made by remote control or manually by means of adjusting elements
selected by operating the selector switch DIP 1 (see illustration).
5.1 Settings and functions via remote control
See page 3.
5.2 Settings and functions via adjusting elements
Control: lux light values
= light value is approx. 5 lux = daytime operation
For ease of use, the lux scale is calibrated according to the scope of application:
• Passageways = 1 - 2 (approx. 40 - 200 lux)
• Working areas = 2 - 3 (approx. 200 - 600 lux)
• Activities requiring a high level of lighting = > 3 (> 600 lux)
NB: When turning the lux control (starting from the moon symbol), if the current ambient
light value is reached, the red LED will light up (as a setting aid). The LED will automatically
go out after 30 seconds.
Function short pulse” for “lighting” channel
Once the detector has been triggered by movement (lighting is below preset ambient
lighting level), the lighting and the red LED will be switched on for 1 second and then off
for 9 seconds.
Function “short pulse” for “HVAC” channel
Once the detector has been triggered by movement, the channel and the green LED will be
switched on for 5 seconds and then off for 5 seconds.
“Test” function: checking the range / detection using test mode
Connected lighting turns on – for clear inspection / pacing out of a detector’s field of
detection. Real-time, load-free indication of movement given by 2 flashes of the blue LED.
5 • INDIVIDUAL SETTINGS AND FUNCTIONS
Clear pre-selection of functions using DIP switches directly on the detector
DIP switches on the detector
DIP 2 3 41
DIP switch 1
Time setting (light) Light value Time setting (HVAC)
Item number Order description
EP10055393 MD-C 360i/8
EP10425875 MD-C 360i/8 MIC *
EP10425059 PD-C 360i/8
EP10425882 PD-C 360i/8 MIC *
EP10425042 PD-C 360i/8plus
EP10055317 MD-C 360i/24
EP10428067 PD-C 360i/24
EP10425288 PD-C 360i/24plus
EP10425707 PD-C 360i/24 DRY *
EP10427749 MD-C 360i/32
EP10427756 PD-C 360i/32
EP10427763 PD-C 360i/32plus
EP10428128 MD-C 360i/32 Corridor *
EP10428180 PD-C 360i/32 Corridor *
(* see table chapter 7)
MD-C / PD-C ... 8
MD-C / PD-C ... 24 ... 32
1

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Esylux MD-C serie bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Esylux MD-C serie in de taal/talen: Engels als bijlage per email.

De handleiding is 0.57 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Andere handleiding(en) van Esylux MD-C serie

Esylux MD-C serie Gebruiksaanwijzing - Nederlands - 35 pagina's

Esylux MD-C serie Gebruiksaanwijzing - Deutsch - 3 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info