LCD+
User Guide GB
LCD+ solar Controller 3 - 17
Bedienungsanleitung D
LCD+ Solarregler 18 - 35
Controller solare LCD+ 44-53
2
LCD+ LCD solar Controller
Installation and Operation Manual
IMPORTANT!
Before starting work the installer should carefully read this
Installation & Operation Manual, and ensure all instructions are
observed and understood.
The Solar controller should be mounted, operated and
maintained by trained personnel only. Individuals in training are
only allowed to install the product under the supervision of a
qualified installer.
Instructions in this Installation & Operation manual must be
observed when working with the controller. Incorrect operation
shall render the warrenty void. WATTS shall not be liable in the
case of improper usage. Any modifications or alterations are
not allowed for safety reasons. The Solar controller
maintenance may only be performed by service centres
approved by WATTS.
The functionality of the controller is dependant upon the model
and ancillary equipment. This installation leaflet is part of the
product and has to be kept and maintained with the controller.
APPLICATION
The Solar controller is developed for a Solar heating system.
The temperature of the tank water is controlled by temperature
difference “dt” between the solar collector and tank.
The controller is normally used in conjunction with a solar
station which includes a circulation pump and mechanical
pressure Safety valve.
The controller has been designed for use in dry environments,
e.g. in residential rooms, office spaces and industrial facilities.
Verify that the installation complies with local regulations
before operation.
SAFETY INSTRUCTIONS
Before starting work disconnect power supply!
All installation and wiring work related to the controller must be
carried out only when de-energized. The appliance should be
connected and commissioned by qualified personnel only.
Make sure to adhere to local electrical safety regulations.
The controllers are neither splash- nor drip-proof. Therefore,
they must be located in a dry environment.
Do not interchange the connections of the sensors and the
230V connections under any circumstances! Interchanging
these connections may result in life endangering electrical
hazards or the destruction of the unit and other connected
sensors and appliances.
TABLE OF CONTENTS
MAIN CHARACTERISTICS ....................................................... 3
TECHNICAL CHARACTERISTICS ............................................ 3
PRESENTATION (Display, keys)............................................... 4
Main menu: 4
1 Quick start menu .................................................... 4
2 Services ................................................................. 5
2.1 Language ............................................................... 5
2.2 Time & Date ........................................................... 5
2.3 System ................................................................... 6
2.3.1 System 1 ................................................................ 6
2.3.2 System 2 ................................................................ 6
2.3.3 System 3 ................................................................ 7
2.3.4 System 4 ................................................................ 7
2.3.5 System 5 ................................................................ 7
2.3.6 System 6 ................................................................ 7
2.3.7 System 7 ................................................................ 7
2.3.8 System 8 ................................................................ 7
2.4 Outputs configuration ............................................. 8
2.4.1 P1 ........................................................................... 8
2.4.2 P2 ........................................................................... 8
2.4.3 Pump P3 ................................................................ 9
2.5 Inputs configuration .............................................. 10
2.5.1 If no flow meter ..................................................... 10
2.5.2 Grundfos sensors ................................................. 11
GDS2 (Grundfos Direct Sensor) .............................................. 11
2.5.3 Impulse Flow meter: ............................................. 11
2.5.4 Temperature Sensor ............................................ 11
2.6 Energy measurment: ............................................ 11
2.6.1 Solar Energy ........................................................ 12
2.6.2 2nd Energy ............................................................ 12
2.7 Protection function ............................................... 13
2.7.1 Max temp collector ............................................... 13
2.7.2 Overheat protection .............................................. 13
2.7.3 Cooling ................................................................. 13
2.7.4 Recooling ............................................................. 13
2.7.5 Freeze protection ................................................. 13
2.8 Degrees................................................................ 13
2.9 Tubes collector ..................................................... 13
2.10 Factory setting ...................................................... 13
3 Settings Menu ...................................................... 13
3.1 Maxtemp tank1 ..................................................... 13
3.2 dTON tank1 .......................................................... 13
3.3 dTOFF tank1 ........................................................ 13
3.4 dTFS: Fullspeed ................................................... 14
3.5 Mintemp collector ................................................. 14
3.6 Maxtemp tank2 ..................................................... 14
3.7 DtON tank2 .......................................................... 14
3.8 dTOFF tank2 ........................................................ 14
3.9 dTON return ......................................................... 14
3.10 dTOFF return ....................................................... 14
3.11 Thermostat Function ............................................ 14
3.11.1 Start...................................................................... 14
3.11.2 Hysteresis ............................................................ 14
3.11.3 Delay .................................................................... 14
3.11.4 Legionella ............................................................. 14
3.11.5 Timer .................................................................... 15
3.12 Cooling Function .................................................. 15
3.12.1 Cooling start ......................................................... 15
3.12.2 Cooling hysteresis ................................................ 15
3.13 Diff control Function ............................................. 15
3.13.1 Max cold tank ....................................................... 15
3.13.2 Min warm tank ...................................................... 15
3.13.3 dTMax .................................................................. 15
3.13.4 dTMin ................................................................... 15
3.14 Antistagnation Function ........................................ 15
3.14.1 Start Level ............................................................ 15
3.14.2 Stop Level ............................................................ 15
4 Operation Menu ................................................... 15
4.1 Automatic and Off operation................................. 15
4.2 Chimney sweep function ...................................... 16
4.3 Manual testing operation: ..................................... 16
5 Operation hours Menu ......................................... 16
5.1 Data logger set with WATTS software and SD
card 16
6 Temperatures Menu ............................................. 17
7 Special Functions ................................................. 17
7.1 Pump exercise function ........................................ 17
7.2 Dimmer function ................................................... 17
7.3 Security function ................................................... 17
8 Others .................................................................. 17
9 Notes .................................................................... 17
3
Menu structure
Service
English “Language”
Time and date
o Time
o Date
o 24/12h clock
o DST
System
o System 1 - 8
o System Parameter (if available)
Outputs Configuration
o P1 “Information of the use”
o P2 “Information of the use”
o P3 “Information of the use”
Inputs Configuration
o Fixed Flowrate value
Flow (l/min)
o Grundfos sensors
GDS1”Sensor choice”
GDS2 ”Sensor choice”
o Impulse flow meter
T6
Liter/Impulse
o Temperature Sensors
T1- T5
Calibration (Pt-1000)
Energy Measurements
o Solar Energy
Adjustments
o 2nd Energy
Adjustments
Protection func.
o Max temp coll.
o Overheat prot.
Overheat temp
o Cooling
Max temp
o Recooling
Min temp
o Freeze prot.
Freeze Temp
Degrees °C/°F
Tube collectors
Factory setting
Quick start menu
o Configuration sequence
Settings
Maxtemp tank1
dT.ON tank1
dT OFF tank1
“Only available with system with 2 tanks”
Maxtemp tank2
dT.ON tank2
dT OFF tank2
“Only available with system 6”
dT.ON return
dT OFF return
dT FS
Mintemp coll.
“Only available if P3 is used as an Extra function”
Extra Function adjustments
Operation
Automatic
Off
Chimney sweep
Manual testing
Operation h
Operation
dT
Power
Energy
SD card
Temperatures
T1
T2
T3
T4
T5
MAIN CHARACTERISTICS
- Large graphic display with backlight
- Easy use interface (4 keys with scroll menu).
- Several languages available
- SD card interface to save the recorded statistics
(Temperatures, Power, Energy, Time operation…) and
parameters.
- 2 energy counters (1 for solar energy and 1 free to specify).
- 1 Bus connection (RJ45) for Extension module (MULTIPLEX)
and communication option.
- Graphic view for Temperature, power, energy…
- 8 working systems with several extra functions possibility
- 5 Inputs for temperature sensors (PT1000 type)
- 1 Logical Input for Impulse flow meter input (for energy
measurement).
- 2 Analogue inputs for Grundfos direct sensors (Flow,
Pressure and temperature sensor)
- 2 electronics outputs for pump (Standard or PWM) with pump
exercise function.
- 1 standard output for Extra function (to control additional
heat, cooling system…)
- Automatic, Off, Manual test mode and chimney sweep
function.
- Sensors Auto checks (Short circuit and breaks)
- Collector protection (Freeze and overheat)
- Permanent memory storage
TECHNICAL CHARACTERISTICS
Operating temperature
0°C 50°C
Electrical Protection
Installation Category
Pollution Degree
IP20
CLASS I
2
Fusible
Power supply
Maximum Power
Consumption
(with all outputs activated)
5AType Fuse 230Vac
(5x20mm)
230Vac +/- 10% 50Hz
4,7A (~ 1080W)
Outputs:
P1 (Main pump with standard
or PWM speed regulation):
P2 (Pump with standard or
PWM speed regulation, valve):
P3 (Extra, Additional heat,
cooling…)
Triac max. 1A 230VAC.
Minimum power switching
>1W
Triac max. 1A 230VAC.
Minimum power switching
>1W
Relay max. 2A 230VAC
* Higher power
consumption: only possible
with external power relay
Inputs:
T1 (Collector1):
T2 (Tank1):
T3 (Extra sensor):
T4 (Extra sensor, Tank2,
Collector2):
T5 (Collector return):
T6 (Flow meter):
GDS1 & GDS2 (Grundfos
sensor):
Flow or pressure.
PT 1000 type
PT 1000 type
PT 1000 type
PT 1000 type
PT 1000 type
Impulse type (low voltage
5V)
Analogue type
(Grundfos VFS, RPS)
Sensors delivered with the
product:
2 Collectors sensor (red)
1 Tank (grey)
1 Extra (grey)
PT1000 (1.5M 180°C)
PT1000 (3M 105°C)
PT1000 (3M 105°C )
Software version
Displayed during
initialisation
Higher Version 11xx
28
Mit Drucksensor „RPS
* Hinweis: Echtzeitwerte für den Durchfluss bzw. Druck
werden auf der Hauptzeile des GDS1 Menüs angezeigt.
GDS2 (Grundfos Direct Sensor)
Dieser Eingang hat dieselbe Funktion und bietet dieselben
Möglichkeiten wie der Eingang GDS1.
2.5.3 Durchflussmessung (Impuls-Meter oder Flow-
Meter)
Wenn ein Imp. Meter installiert ist (an T6 / PF), die Option
„Impuls“ wählen und
mit den Tasten (+) und (-) die Durchflusswerte in Liter/Impuls
eingeben
(Einstellmöglichkeit von 1 bis 25 L/Imp, Werkseinstellung 10
L/Imp).
Wird ein Imp. Meter zur Energiemessung verwendet,
den Sensor T5 am Kollektor-Rücklauf anschließen, um ein
genaueres Ergebnis zu erzielen.
Bemerkung: Imp. Meter nicht an T6 anschließen, wenn ein
digitaler Druckmesser oder Durchflussmesser an GDS2
angeschlossen ist!
2.5.4 Temperatursensor
In diesem Untermenü können Sie den aktuellen Status aller
Temperatursensoren anzeigen, die an den Regler
angeschlossen sind. Sie können den vom Regler gemessenen
Istwert ablesen und sehen, ob er verwendet wird bzw. ob der
Sensor defekt ist.
Drücken Sie die Taste (►), um auf die Sensorkalibrierung
zuzugreifen.
Achtung: Vor dem Einstellen des Wertes den Istwert der
Sensoren mit einem geeichten Thermometer überprüfen
(Kalibrierbereich: -3°C bis +3°C, Werkseinstellung 0°C).
2.6 Energie-Bilanzierung:
Der Regler verfügt über zwei Energie-Bilanzierungsblöcke. Sie
können für beide Blöcke Sensoren konfigurieren, die für die
Energieberechnung verwendet werden.
Berechnungslogik der Energiemessung:
Für die Energieberechnung sind mehrere Elemente
erforderlich: zwei Temperaturmesspunkte "Warm" und "Kalt",
der Durchflusswert und die Eigenschaften der
Wärmeübertragungsflüssigkeit.
2.6.1 Solarenergie
Der erste Block ist für die Berechnung der Solarenergie
reserviert. Sie können die für die Berechnung verwendeten
Sensoren auswählen.
Zum Ändern des gewählten Sensors mit der Taste (►) auf
die Zeile gehen und den gewünschten Wert mit der Taste
(+) oder (-) gemäß der Installation wählen.
Durchflusssensor
- "Auto"
Der Regler verwendet den theoretischen Durchfluss (Liter /
Minute), der in der Konfiguration der Eingänge eingegeben
wurde, sofern kein Durchflusssensor verfügbar ist.
- T6
Der Regler verwendet den Impuls-Messer, der an den Eingang
"T6" angeschlossen ist.
- "GDS1"
Der Regler verwendet den Grundfos
Strömungsdurchflusssensor "Typ VFS", sofern dieser am
Eingang GSD1 angeschlossen ist.
 GDS1---- --- -
GDS1 RPS 0 - 4 bar
Druck x,x bar
Temp GDS1 xxx°C
 T6 --- -
Impuls-Durchflussmesser Nein
 T6 --- -
Impuls-Durchflussmesser Ja
Liter / Impuls 10
 Einstellung Eing.---- -
Temperatursensor
T1 xxx°C
T2 xxx°C
T3 xxx°C
T4 Ausser Betrieb
T5 Ausser Betrieb
 T1 --- -
Pt1000
Kalibrierung 0°C
Wärmepunkt
P1
Funktionaler Einsatz für
die Berechnung der
Solarenergiebilanz.
Kältepunkt Durchflussmesser
 Solar-Energie -
Durchflusssensor Auto
Sensor warm Auto
Sensor kalt Auto
Flüssigkeit Glycol
Mixed 40%
D-Fluss xxxxm3
Energie 0kWh
Leistung 0.0kW
28

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Watts Solar Controller LCD PLUS bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Watts Solar Controller LCD PLUS in de taal/talen: Duits, Engels als bijlage per email.

De handleiding is 1.12 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info