6CIVIC1-MOI-IT-W-ML-09-18-Rev.1
Watts Water Technologies, Inc.
EN
Once the failure is fixed, the control unit needs to be reset to its
normal operating status. Press the “Reset/Test button on the
front of the control unit to reset it.
Caution. It is advisable to repeat the operating test at least
once a year, or after a prolonged period of stoppage and in any
case, every time the detector is replaced.
Caution. The average lifetime of the UR13 and UR20S detec-
tors is 5 years from installation date. They must be replaced
before the end of the 5th year of use. The average lifetime of
detectors is calculated for use in a typical environment, nor-
mally free from polluting agents (gases, solvents etc.).
More frequent and higher concentrations of these substances
can accelerate the normal oxidisation process of the sensing
element, subsequently shotening its lifetime.
Gas Alarm
If an alarm signals a gas leak or the presence of carbon
monoxide, proceed as follows:
- put out flames and switch off all gas equipment;
- do not for any reason switch on or off lights or any electrical
equipment;
- open doors and windows to air the environment;
- look for and eliminate the cause of the alarm. If this is not
possible, leave the building and contact emergency services
from outside.
Environmental compatibility and
disposal
This product has been designed and constructed using
materials and processes that take into account the
environmental issue. Refer to the following notes for
disposal of the product at the end of its working life,
or when it is replaced:
- for disposal purposes, this product is classified
as an
electric and electronic device: do not dispose of it with
normal household waste, in particular as regards the
printed
circuit;
- comply with all local laws in force;
- as far as possible reuse basic materials to keep
environmental impact to a minimum;
- use local depots and waste recycling companies, or contact
the supplier or manufacturer to return used products or to
ask for information on environmental compatibility and waste
disposal;
- the product packaging can be reused. Keep it for future use
or to return the product to the supplier.
Problem Possible cause
NC valve does not open
- Valve not connected
- Alarm in progress
- Detector warm-up phase in
progress
- All detector defective
- General failure event occurring
NO valve does not close
- Valve not connected
- Connection cables cut
- No alarm active
“Reset/Test” button
does not reset to initial
conditions
- Alarm in progress
- Failure occurring in control unit
Troubleshooting
+ Power supply 12 Vac/dc (positive)
+ OC output 12 Vac/dc (positive)
C Alarm Alarm relay output (common)
NC Alarm Alarm relay output (Normally Closed contact)
NO Alarm Alarm relay output (Normally Open contact)
C Abnormality Alarm relay output (common)
NC Abnormality Alarm relay output (Normally Closed contact)
NO Abnormality Alarm relay output (Normally Open contact)
UR13 detector connections
C1,C2,C3,C4 Detector input (C, common)
S1,S2,S3,S4 Detector input (S, signal)
A1,A2,A3,A4 Detector input (A, power supply 6.5V)
UR20S detector connections
C1,C2,C3,C4 Detector input (-12...24V, negative power supply/signal)
S1,S2,S3,S4 Detector input (+4...20mA, positive signal)
A1,A2,A3,A4 Detector input (+12...24V, positive power supply/signal)
1. TB1 - Power supply terminals 12 Vac/dc
2. Protection fuse 1A
3. TB2 - “Alarm” relay terminals
4. TB3 - “Abnormlity” relay terminals
5. CN1 connector and service Jumper J1
6. Set up jumper:
E1 – operating mode
E2 – Alarm relay operating mode
E3 – omitted=UR13 on input 1 and 2, A=UR20S on inputs 1
B=UR20S on inputs and 2
E4 – omitted=UR13 on input 1 and 2, A=UR20S on inputs 1
B=UR20S on inputs and 2
7. Connector P1 (communication – not used)
8. LED signalling presence of voltage
9. LED signalling general failure
10. Reset/Test button
11. TB7 - B4 gas detector connection terminals
12. Jumper E11÷E12 for configuration of inputs B4 detector:
E11 - Sel. power supply: A=6.5V (UR13), B=12V (UR20S)
E12 - Sel. input A=threshold (UR13), B=4...20mA (UR20S)
Jumper E9÷E10 for configuration of inputs B3 detector:
E9 - Sel. power supply: A=6.5V (UR13), B=12V (UR20S)
E10 - Sel. input A=threshold (UR13), B=4...20mA (UR20S)
13 TB6 - B3 gas detector connection terminals
14 TB5 - B2 gas detector connection terminals
15 Jumper E7÷E8 for configuration of inputs B2 detector:
E7 - Sel. power supply: A=6.5V (UR13), B=12V (UR20S)
E8 - Sel. input A=threshold (UR13), B=4...20mA (UR20S)
Jumper E5÷E6 for configuration of inputs B1 detector:
E5 - Sel. power supply: A=6.5V (UR13), B=12V (UR20S)
E6 - Sel. input A=threshold (UR13), B=4...20mA (UR20S)
16 TB4 - B1 gas detector connection terminals
17 Gas alarm LED
18 Detector failure LED
Terminal board
6

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Watts CIVIC 4 bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Watts CIVIC 4 in de taal/talen: Engels, Italiaans als bijlage per email.

De handleiding is 1.17 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info