Once the correct power is supplied, the control unit carries out
the following phases in sequence:
LED and buzzer tests (about 5 seconds)
Whichever operating mode is selected, the LEDs will switch on
in sequence and the buzzer will sound briefly.
Warm-up of detectors (about 1 minute)
During this phase, which brings the detectors up to the
correct operating temperature, the gas detection system is not
operational. During this phase, if the wiring connections
are correct, the control unit display shows the following:
Operating test (about 3 minutes)
Once the detector warm-up phase is complete, the device
enters the operating test phase. During this phase, all internal
timing is reset to ease operating verification of the detectors
(alarm simulation). In this case, the control unit display shows
the following:
Keep the “Reset/Test” button pressed down for over 1 second
to interrupt the operating test phase. To test the detectors
correctly, proceed as follows:
Gas alarm test
Bring the test cylinder close to the detector grille and release
a small amount of gas (caution: if the gas is aimed directly at
the sensor, this will be permanently damaged). For CO testing
of detectors, smoked produced by combustion can be used.
The control unit will signal the alarm as follows:
Keep the “Reset/Test” button pressed down for 1 second to
silence the alarm (if there is no gas remaining) and terminate
the operating test phase. To restart the Test phase, just keep
the relative button pressed down for about 6 seconds. Repeat
the operations described above to test the other detectors.
Interface Positive
logic
Negative
logic
Power supply LED Green Flashing 1 Hz Flashing 1 Hz
General failure LED Yellow On Off
Detector failure LED (4) Yellow On Off
Alarm and line failure
LED (4) Red On Off
Alarm buzzer No sound No sound
Alarm relay Energised De-energised
Failure relay Energised De-energised
Interface Positive logic Negative logic
Detector
alarm LED Red Off On
Alarm buzzer Continuous sound Continuous sound
Alarm relay De-energised
Energised
(permanently or
pulsed depending
on E2)
Interface Positive
logic
Negative
logic
Detector failure
LED Yellow Off On
Alarm buzzer Intermittent
sound
Intermittent
sound
Failure relay De-energised Energised
General failure LED Yellow On Off
Caution The repeated use or high concentration of interfering
substances (alcohol, lighter fluid etc.) can cause permanen
damage to the sensor and put the device out of order.
Detector failure test
Simulate a failure in the detector as follows:
- disconnect the cable of the detector and verify the following alerts:
- reconnect the detector and press the “Reset/reconnect the
detector and press the “Reset/Test” to return the control unit to
normal operating mode, making the sure the conditions of the
various interfaces are reset.
Normal operation
This is the normal operating phase of the control unit during
which both gas alarm monitoring and self-testing of the
instrument (detector) and the system (control unit) are
active. During this phase, where there are no alarms and/or
abnormalities, the control unit display shows the following:
When dangerous concentrations of gas are detected, the
control unit enters the gas alarm phase and carries out the
following operations:
Once the gas alarm condition is normalised, the control unit
needs to be reset to its normal operating status. Press the
“Reset/Test button on the front of the control unit to reset it.
If there are abnormalities (detector and/or control unit), the con-
trol unit will show the following display:
Interface Positive
logic
Negative
logic
Power supply LED Green Flashing 2 Hz Flashing 2 Hz
General failure LED Yellow On Off
Detector failure LED (4) Yellow On Off
Alarm and line failure
LED (4) Red On Off
Alarm buzzer No sound No sound
Alarm relay Energised De-energised
Failure relay Energised De-energised
Interface Positive
logic
Negative
logic
General failure LED
(for control unit failure) Yellow Off On
Detector failure LED
(for detector failure) Yellow Off On
Alarm buzzer Intermittent
sound
Intermittent
sound
Failure relay De-energised Energised
Interface Positive
logic
Negative
logic
Power supply LED Green On On
General failure LED Yellow On Off
Detector failure LED (4) Yellow On Off
Alarm and line failure
LED (4) Red On Off
Alarm buzzer No sound No sound
Alarm relay Energised De-energised
Failure relay Energised De-energised
Interface Positive logic Negative logic
Detector
alarm LED Red Off On
Alarm buzzer Continuous sound Continuous sound
Alarm relay De-energised
Energised
(permanently or
pulsed depending
on E2)
5

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Watts CIVIC 4 bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Watts CIVIC 4 in de taal/talen: Engels, Italiaans als bijlage per email.

De handleiding is 1.17 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info