12
Testing the strength of reception
1.
Press and hold B on the wireless
receiver for approx. 5 s until LED
flashes.
2. Carry out the following settings on
the Vitotrol 100:
Operating instructions
Open the flap of the Vitotrol 100.
3. Press twice.
4. Select "Settings" with / .
5. Confirm with OK.
6. Select "Service" with / .
7. Press OK four times to confirm.
"Transmitting" appears on the dis-
play.
The transfer takes approx. 30 s.
If the signal strength is sufficient, LED
shows green; otherwise it shows red.
Then check the installation location of
the Vitotrol 100.
Testing switching outputs
1.
Press B on the wireless receiver
(see diagram on page 11) repeatedly
until the required condition is reached
(see following table).
2. Terminate the function:
Press
B
.
or
automatic if the switching output is
closed via the setting on the
Vitotrol 100.
Function LED r LED
Central heating and DHW heating off OFF OFF
Central heating off, DHW heating enabled OFF ON
Central heating enabled, DHW heating off ON OFF
Central heating and DHW heating enabled ON ON
Commissioning
Commissioning the wireless receiver
(cont.)
5457 286 GB