8 Operating and display functions
18 Installation instructions 0020237057_00
A
B
15 10 5 0 -5 -10 -15 -20
20
30
40
50
60
70
80
90
1.2
1.5
1.822.533.54
0.8
1.0
0.4
0.2
0.1
0.6
A Outside temperature °C B Target flow temperature
°C
The illustration shows the possible heating curves of 0.1 to
4.0 for a target room temperature of 20 °C. If, for example,
heating curve 0.4 is selected, a flow temperature of 40 °C is
maintained at an outside temperature of -15 °C.
A
B
CD
18
22
20
0.4
70
60
50
40
30
15 10 5 0 -5 -10 -15 -20
A Outside temperature °C
B Target flow temperature
°C
C Target room temperat-
ure °C
D Axis a
If the heating curve 0.4 is selected and 21 °C is specified for
the target room temperature, the heating curve is then trans-
lated, as shown in the figure. The heating curve is displaced
according to the value of the room target temperature along
axis a which is angled at 45°. At an outside temperature of
-15 °C, the control system provides a flow temperature of
45 °C.
8.7.16 Activating Room temp. mod.
Menu Installer level System configuration [HEAT-
ING1 ----] Room temp. mod.
This function allows you to define whether the temper-
ature sensor integrated in the controller or in the remote
control unit should also be used.
The prerequisite for this is:
The controller is installed in the living room.
Any remote control unit that is present is installed in the
living room.
In the Zone assignment function, the controller or, if
required, the remote control unit is assigned to the zone
in which the controller or remote control unit is installed.
If you do not assign any zones, the Room temp. mod.
function is ineffective.
None: Temperature sensor is not used for control.
Temp. mod.: The built-in temperature sensor measures the
current room temperature in the reference room. This value
is compared with the target room temperature and, if there
is a difference, results in adjustment of the flow temperature
by means of the so-called "Effective target room temperat-
ure". Effective room temp. target = set room temp. target +
(set room temp. target - measured room temp. target). The
effective target room temperature is then used for controlling
instead of the set target room temperature.
Thermost.: Works in the same way as temperature control,
however the zone is also switched off when the measured
room temperature is + 3/16 K greater than the set target
room temperature. When the room temperature falls + 2/16
K back below the target room temperature set, the zone is
switched on again. The use of room thermostat control, in
combination with careful selection of the heating curve, leads
to optimum control of the heating installation.
8.7.17 Activating Cooling possible
Menu Installer level System configuration [HEAT-
ING1 ----] Cooling possible
When a heat pump is connected, you can activate the
Cooling function for the heating circuit .
8.7.18 Activating the dew point monitoring
Menu Installer level System configuration [HEAT-
ING1 ----] Dew point monitoring
You can use this function to activate the dew point monit-
oring.
If the dew point monitoring has been activated, the controller
compares the set minimum cooling target flow value with the
dew point+offset. The controller always selects the higher
temperature so that no condensate can form.
8.7.19 Setting the end cooling temperature
Menu Installer level System configuration [HEAT-
ING1 ----] End OT cooling
You can use this function to set the temperature
threshold from which cooling switches off. If the outside
temperature is lower than the temperature threshold set,
the controller ends cooling mode.
8.7.20 Setting the dew point offset
Menu Installer level System configuration [HEAT-
ING1 ----] Offset dew point
You can use this function to set the dew point offset.
The offset is a safety margin that is added to the dew point.
The controller selects the maximum for the flow temperature
calculated from the flow temperature that is set and the dew
point + offset.
8.7.21 Reading the status of the external heat
demand
Menu Installer level System configuration [HEAT-
ING1 ----] Status ext. heat dem.
You can use this function to read the status on the ex-
ternal input to see whether there is a heat demand.
18

Hulp nodig? Stel uw vraag in het forum

Spelregels
1

Forum

Vaillant-VRC-700F-4

Zoeken resetten

  • Beste,
    Ik kan mijn temperatuur niet regelen voor de nacht, wel inde dag met de tijdsprogramma's.
    Hoe kan ik dat verhelpen Gesteld op 10-1-2024 om 11:32

    Reageer op deze vraag Misbruik melden

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Vaillant VRC 700F-4 bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Vaillant VRC 700F-4 in de taal/talen: Engels als bijlage per email.

De handleiding is 1,3 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info