Operating and display functions 8
0020237057_00 Installation instructions 17
8.7.7 Setting the target return temperature for the
"increase in return flow" circuit type
Menu Installer level System configuration [HEAT-
ING1 ----] Target return temp.
You can use this function to set the target return temper-
ature for the "increase in return flow" circuit type.
8.7.8 Setting the minimum cooling flow target
value
Menu Installer level System configuration [HEAT-
ING1 ----] Min. cool. fl. tgt temp.
If a heat pump is connected and the Cooling possible
function is activated for the heating circuit, you can set
the minimum target flow value for the Cooling possible
mode.
The controller regulates the heating circuit at the minimum
cooling target flow value, even if the operator has set a lower
desired temperature for cooling.
8.7.9 Reading the current temperature
Menu Installer level System configuration [HEAT-
ING1 ----] Current temperature
You can use this function to read the current temperature
of the heating circuit.
8.7.10 Setting the excess temperature
Menu Installer level System configuration [HEAT-
ING1 ----] Excessive temp.
You can use this function to set the excess temperature.
The excess temperature increases the current set target
temperature of the heating circuit by the value that is set.
On mixer circuits with fixed mixing, this function means that
the set target temperature can be reached in pre-heat mode,
even though the temperature of the mixer circuit drops sub-
stantially.
The function also allows for an optimal control range for op-
erating the mixer valve. Stable operation is only possible if
the mixer valve only rarely has to move to the limit stop. This
ensures improved quality of control.
8.7.11 Setting the temperature threshold for
deactivating the heating circuit
Menu Installer level System configuration [HEAT-
ING1 ----] Max limit outs.temp.
You can use this function to set the temperature
threshold. If the outside temperature is greater than the
switch-off threshold set, the controller deactivates heating
mode.
8.7.12 Setting the minimum flow temperature for
the heating circuit
Menu Installer level System configuration [HEAT-
ING1 ----] Minimum temperature
You can use this function to specify a minimum value for
the flow temperature in heating mode for each heating
circuit; the control system will not fall below this value.
The controller compares the calculated flow temperature
with the value set for the minimum temperature and, if
there is a difference, adjusts this to the higher value.
8.7.13 Setting the maximum flow temperature for
the heating circuit
Menu Installer level System configuration [HEAT-
ING1 ----] Maximum temperature
You can use this function to specify a maximum value for
the flow temperature in heating mode for each heating
circuit; the control system will not exceed this value. The
controller compares the calculated flow temperature with
the value set for the maximum temperature and, if there
is a difference, adjusts to the lower value.
8.7.14 Specifying controller behaviour outside
time periods
Menu Installer level System configuration [HEAT-
ING1 ----] Auto Off mode
This function enables you to specify, for each heating
circuit separately, the controller functions in automatic
mode outside active time periods. Default setting: Eco
You can select from two controller behaviours, which you
can adapt further by using the room temperature control.
If you have set the Thermost. value in the Room temp.
mod. function, the Auto Off mode function is ineffective.
The controller always brings the target room temperature to
5 °C.
Eco: The operating mode Auto Off mode, Auto (outside
of the time period) and off are switched off. If a mixer cir-
cuit is connected, the heating pump is switched off and
the heating circuit mixer is closed. The outside temper-
ature is monitored. If the outside temperature falls be-
low 4 °C, the controller switches the heating function on
after the end of the frost protection delay time. The heat-
ing pump is activated. If a mixer circuit is connected, the
heating pump and the heating circuit mixer are activated.
The controller regulates the target room temperature at
the set temperature Set-back. Despite the heating func-
tion being switched on, the heat generator is only active
on demand. The heating function remains active until the
outside temperature rises above 4 °C, after which the
controller switches the heating function off again, but the
outside temperature monitoring remains active.
Set-back: The heating function is switched on and the
target room temperature is set to and maintained at the
set Set-back temperature.
8.7.15 Setting the heating curve
Menu Installer level System configuration [HEAT-
ING1 ----] Heating curve
If the heating curve setting is not sufficient to control the
living room climate according to the operator's wishes,
you can adapt the heating curve setting made during
installation.
If you activate the Adaptive heat. curve function, you must
always adjust the value for the heating curve to the heating
surface design.
17

Hulp nodig? Stel uw vraag in het forum

Spelregels
1

Forum

Vaillant-VRC-700F-4

Zoeken resetten

  • Beste,
    Ik kan mijn temperatuur niet regelen voor de nacht, wel inde dag met de tijdsprogramma's.
    Hoe kan ik dat verhelpen Gesteld op 10-1-2024 om 11:32

    Reageer op deze vraag Misbruik melden

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Vaillant VRC 700F-4 bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Vaillant VRC 700F-4 in de taal/talen: Engels als bijlage per email.

De handleiding is 1,3 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info