17
Double-power operation
Current limits
Secure base load
(min. xx A)
Secure max. load
(max. xx A)
Single-power operation
Current limits
Secure load
1/N/PE~230V
2/N/PE~230V
1kW
2kW
3kW
1kW
2kW
3kW
1 kW 1/N/PE~230 V // 1 x min 10 A
2 kW 1/N/PE~230 V // 1 x min 10 A
3 kW 1/N/PE~230 V // 1 x min 16 A
1 kW 2/N/PE~400 V // 2 x min 10 A
2 kW 2/N/PE~400 V // 2 x min 10 A
3 kW 2/N/PE~400 V // 2 x min 16 A
1/N/PE~230V
2/N/PE~230V
1 - 3 kW 1/N/PE~230 V min 10 A // max 16 A
2 - 3 kW 1/N/PE~230 V min 10 A // max 16 A
1 - 3 kW 2/N/PE~400 V min 10 A // max 16 A
2 - 3 kW 2/N/PE~400 V min 10 A // max 16 A
Boiler mode operation
Current limits
Secure load
1/N/PE~230V
1/N/PE~230V
1/N/PE~230V
2/N/PE~230V
2/N/PE~230V
2/N/PE~230V
1kW
2kW
3kW
1kW
2kW
3kW
1 kW 1/N/PE~230 V // 1 x min 10 A
2 kW 1/N/PE~230 V // 1 x min 10 A
3 kW 1/N/PE~230 V // 1 x min 16 A
1 kW 2/N/PE~400 V // 2 x min 10 A
2 kW 2/N/PE~400 V // 2 x min 10 A
3 kW 2/N/PE~400 V // 2 x min 16 A
Technical data
MODEL
Volume litres 30,0
Weight when full kg 49
Maximum operating pressure MPa (bar) 0,6 (6)
Degree of protection IP 25D
Water connection G1/2A
Time taken to heat to approx. 85 °C, Hours 1 kW 2,8
at a cold water supply temperature of 15 °C 2 kW 1,5
3 kW 1
MODEL
Energy class D
Load profile S
Power consumption yearly in kWh (kWh) 627
Power consumption daily in kWh (kWh) 3,082
Sound power level in dB (dB) 15
Warm water efficiency in % (%) 29,4
Mixing water (I) 53