587981
16
Verklein
Vergroot
Pagina terug
1/60
Pagina verder
Operating structure
Standard display
Display of the operating values
Medium outlet B2
Current actual temperature
value (inlet flow)
Medium inlet B1
Current actual temperature
value (return)
Medium inlet FC
Current actual temperature
value (return) in free-cooling
mode
Ambient temperature
Current actual temperature
value of the ambient tempera-
ture (unit air inlet).
Ambient temp. Free-cool.
Current actual temperature
value of the ambient tempera-
ture (unit air inlet).
Condensation
Current pressure value of the
hot-gas line for Circuits 1
(CdP1) and 2 (CdP2) via "SET"
(>5 sec.).
Low pressure
Current actual pressure value of
the suction-gas line for Circuits
1 (LP1) and 2 (LP2) via "SET"
(>5 sec.).
Change in set values
Set value, cooling
Current set value in cooling
mode, value settable between
9.0 and 20.0°C
Set value, heating
Current set value in heating
mode, value settable between
30.0 and 50.0°C
Time setting
Hour entry
Value change
between
0 and 23 via the
"/" button,
save via "SET."
Minute entry
Value change
between
0 and 59 via the
"/" button,
save via "SET."
Day entry
Value change
between
1 and 31 via the
"/" button,
save via "SET."
Month entry
Value change
between 1 and 12
via the "/"
button, save via
"SET."
Year entry
Value change
between 2000
and 2099 via the
"/" button,
save via "SET."
Current fault list
Current, non-resettable faults are indicated
with "No", resettable with "rSt", reset via
the "SET" button.
Compressor/pump operating hours
Value in hours for compressors (CO..H) and
pumps (EP..H) by pressing the "SET" button,
resettable after maintenance (5 sec.).
Actuation of the condenser fans
Value in % as actuation of the controller for
winter fan control, for example (currently an
accessory).
Number of compressor starts 1-6
Number of starts of compressors 1-6
(CO..S). Reset of the value using the "SET"
button (5 sec.).
Disable/enable of compressors 1-6
For example, enable (En) or disable (diS)
of the compressors (CO..E) during mainte-
nance, etc. by pressing the "SET" button
(5 sec.).
Disable/enable of circulation pumps 1-2
For example, enable (En) or disable (diS)
of the circulation pumps (PE..E) during
maintenance, etc. by pressing the "SET"
button (5 sec.).
Parameter transfer to/from USB
Using an inserted USB stick, the current
parameterisation of the controller can be
transferred to/from the stick.
Current operating state
Display of the current operating state of
the unit.
Software version
Display of the current software version
(APP), unit IP (IP), and address (Adr)
Fault history
Faults are displayed according to the order
n01 (oldest) to n99 (most recent). Reset
under "ArSt."
Current operating state of the inputs/
outputs
Display of the sensors (Pb), digital inputs (di)
and outputs (rL) as "On," "Off," or "Not
used" (nc).
Menu without password
Set values (available parameters)
Level PAS 1 PAS 2 PAS 3
From St 1 1 1
To St 1 32 32
Display (available parameters)
Level PAS 1 PAS 2 PAS 3
From dP - 1 1
To dP - 11 11
Configuration (available parameters)
Level PAS 1 PAS 2 PAS 3
From CF - - 1
to CF - - 10
Setup (available parameters)
Level PAS 1 PAS 2 PAS 3
From SP - - 1
To SP - - 18
Dynam. set value (available parameters)
Level PAS 1 PAS 2 PAS 3
From Sd - 1 1
To Sd - 6 6
Energy savings (available parameters)
Level PAS 1 PAS 2 PAS 3
From ES 1 1 1
To ES 25 25 25
2. Heat generator (available parameters)
Level PAS 1 PAS 2 PAS 3
From AH - - 1
To AH - - 16
Compressor (available parameters)
Level PAS 1 PAS 2 PAS 3
From CO - - 1
To CO - - 71
Compressor levels (available parameters)
Level PAS 1 PAS 2 PAS 3
From SL - - 1
To SL - - 10
Circulation pump (available parameters)
Level PAS 1 PAS 2 PAS 3
From PA - 1 1
To PA - 30 30
Pumpdown cooling circuit (available
parameters
)
Level PAS 1 PAS 2 PAS 3
From Pd - - 1
To Pd - - 9
Unloading (available parameters)
Level PAS 1 PAS 2 PAS 3
From Un - - 1
To Un - - 17
Condenser fan (available parameters)
Level PAS 1 PAS 2 PAS 3
From FA - - 1
To FA - - 44
Anti-frost protection (available parameters)
Level PAS 1 PAS 2 PAS 3
From Ar - - 1
To Ar - - 11
Thawing (available parameters)
Level PAS 1 PAS 2 PAS 3
From dF - - 1
To dF - - 33
Heat recovery(available parameters
)
Level PAS 1 PAS 2 PAS 3
From rC - - 1
To rC - - 15
Household water heating (available
parameters)
Level PAS 1 PAS 2 PAS 3
From - - 1
To - - 56
Free-cooling (available parameters)
Level PAS 1 PAS 2 PAS 3
From - - 1
To - - 31
Relay outputs (available parameters)
Level PAS 1 PAS 2 PAS 3
From - - 1
To - - 44
Faults (available parameters)
Level PAS 1 PAS 2 PAS 3
From 34/41 34/41 1
To 34/41 34/41 71
Electrical valve (available parameters)
Level PAS 1 PAS 2 PAS 3
From - - 1
To - - 64
Parameter with password
< 2 sec.
< 2 sec.
< 2 sec.
< 2 sec.
+
> 5 sec.
< 2 sec.< 2 sec.
< 2 sec.
< 2 sec.
< 2 sec.
> 5 sec.
< 2 sec.
< 2 sec.< 2 sec.
< 2 sec.
< 2 sec.
+
< 2 sec.
Open parameter
Raise value/parameter
Open submenu/value
Close parameter
Lower value/parameter
Close submenu
+
+
Level 1 access
(without password)
Password 2 entry
(PW required)
Password 3 entry
(PW required)
REMKO KWG
16
16

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw REMKO KWG500 bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van REMKO KWG500 in de taal/talen: Engels als bijlage per email.

De handleiding is 7,1 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Andere handleiding(en) van REMKO KWG500

REMKO KWG500 Gebruiksaanwijzing - Deutsch - 60 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info