656389
4
Verklein
Vergroot
Pagina terug
1/4
Pagina verder
BA SC2819-SC88-SC98-pro MP; DE, GB - 22476 - 2008.05-03
Instruction Manual (Site 2/2)
GB
Time switch (weekly or yearly program)
SC 28.19 pro / SC 88.X0 pro / SC 98.X0 pro 172 419 pro / 179 4X0 pro / 179 6X0 pro
16.Special program Entry (within yearly time switches)
** The cycle function will only be offered if it is activated (point 13)
The yearly function of the switch is realised by special (weekly) programs which can be called up by date. Up to 10
special (weekly) programs can be entered (Program-Number 01 –> Program-Number 10).
Execution of the Special program only after activation by date (SP activation see point 17).
Some rules for the programming of Special programs
Define the program number in which the new step will be an element before a new switching step is entered.
(Program-number 01 Program-number 10)
The number of switching times which can be programmed in each special program is only limited by the total number
of free memory locations:
(SP on, SP off, SP cycle, SP pulse)
The dates of the year during which the special program should be applied can be entered within the activation menu
(point 17)
Each special program can be activated as often as there are memory locations are available (point 17)
During the activation dates of special programs only switching steps of the special program with highest priority will
be executed. Remaining special and standard programs are disabled.
Please note the priorities of the different switching programs (point 15)
Information: You can easily transfer switching times from one channel to the other if you use the copy function.
17. Special program activation by date (within yearly time switches)
A special program will only be executed if it is activated (and if it has the highest priority of all active
switching programs (point 15)). Special programs can be activated as often as free memory locations are
available. You can choose the special program (Program-Number), the dates for activation (Start-
date until End-date) and additionally following options:
Without special function: Special program will be applied each year fixed to the entered
dates
With Easter function: The time switch takes into account the yearly shift for Easter holiday for
the following years and corrects the activation dates. (For programs relative to Easter, Pentecost
Carnival, Ascension,...)
With 1xfunction: Special program will be applied only once.
Information: You can easily transfer switching times from one channel to the other if you use the
copy function.
18. Extra switching time (within yearly time switches) 19. Permanent program
Program -> new program -> channel A/B/C/D -> Extra switching time ->
These programming steps are single switching times by date. Extra switching times do not disable switching programs with lower priority.
Adjust the switching function (AT on, AT off, AT cycle, AT pulse) and the date on which the extra switching time will be executed. The
following options are additionally available for the Extra switching time:
Without special function: The switching time will be applied each year fixed to the entered date.
With weekday function: The switching date takes into account the yearly shift of the weekday of the month.
(E.g.: The switching date is always the second Saturday in February for the current and the following years)
With 1xFunction: The switching time will be applied only once.
Program -> new program -> channel A/B/C/D -> permanent ->
The permanent by date program (holiday program) is a permanently on or off status of the channel for the
programmed dates. The number of switching times is only limited by the total number of free memory
locations. Adjust channel, switching function and the duration by date. The following options are additionally
available for the permanent by date program:
Without special function: The program will be applied each year fixed to the entered dates.
With Easter function: The time switch takes into account the yearly shift for Easter holiday for
following years and corrects the activation dates. (For programs relative to Easter, Pentecost Carnival,
Ascension,...).
With 1xfunction: The Program will be applied only once.
20. External Input (within 70 mm time switches) 21. Switchoff warning
Options -> Input->
The external input can be connected to a switched contact such as a push-button or light switch. Therefore you can activate and de-activate functions from a remote
location or automatically from a control system:
Connection external inputs:
Connect the voltage/frequency as stated on the product label!
External input 1: A switch or pushbutton can be connected to EXT 1: Terminal 6 (Voltage EXT 1 = Supply voltage of the time switch)
External input 2: A potential free switch or pushbutton can be connected to EXT 2: Terminals 13 u. 14 (potential free = 0V)
Functional options of the „external input“:
Within menu Options and submenu Input you have to define if a switch or a push-button-signal will be applied to the external input. Furthermore you can choose the
channel(s) which react to the external signal:
Using the -buttons select if you are connecting a pushbutton or a switch and confirm by pressing .
Select the channel(s) which will be controlled by the external signal with the buttons (channel … yes) and confirm by pressing . Channels which should not
be controlled by the external signal remain deactivated, confirm channel … no then press to confirm
Define a response function within menu Options and submenu Channel-keys. This function will be performed by the output channel when the external input is
activated!
The pre-defined (default) setting is the standard ‘Change function’ which changes the switching status from ON to OFF and vice versa.
Options -> Switchoff warning ->
Within menu Options and submenu Switchoff warning the early warning
switch off function can be activated and deactivated:
Warning No: The function remains inactive.
Warning Yes: The function is activated and the switch off is signalled in
advance (For illumination purposes the warning is signalled by the flashing of the
light according DIN 18015-2 = warning to avoid sudden darkness).
An activated warning affects all channels and all OFF switching times
22. Channel keys
Options -> channel-keys ->
Within the Options menu you will find submenu channel-keys. Here you have the
opportunity to assign different response functions to the output channels.
These response functions will only be carried out when using the channel-keys of the time
switch (manual over-ride) or optionally when activating the channel with the external input. Thus,
a programmed switching time will be executed as usual, independent of the settings within this
channel-key-menu.
The correlation between the channel-keys and the channels is as follows:
channel A => channel key A (push-button “A” of the device) / channel B => channel key B …
** The cycle function will only be offered if it is activated (point 13)
Overview „channel-keys“ functions:
If you have assigned a specific response function to a channel, this switching function will occur if you push the channel-button on the front plate of the time
switch (or if the external input for this channel is activated and a signal is applied to the input). For each channel one out of the following functions can be
defined:
Change function (default setting): By pressing the channel key (or optionally using the external input) the switching status changes from ON to OFF or
OFF to ON. This corresponds to a standard manual over-ride of the channel.
Timer function: By pressing the channel key (or optionally using the external input) the Timer starts and the corresponding channel switches ON. After
the expiry of the Timer-time the channel switches OFF. If the channel receives another signal before the expiry of time the time switch reacts as follows:
After pressing the channel-button = Timer stops and the channel switches OFF.
Signal on the external input = Timer restarts/ Staircase lighting timer -> Resettable.
Cycle 1 – 4: By pressing the channel key (or optionally using the external input) the cycle function starts. Attention: This function is only available if
the cycle is activated and defined in advance within menu Options and submenu Cycle.
Perm on: By pressing the channel key (or optionally using the external input) the channel switches permanently ON. This status remains active until the
channel key of the device is pressed again.
Perm off: By pressing the channel key (or optionally using the external input) the channel switches permanently OFF.
This status remains active until the
channel key of the device is pressed again.
The Change function, Timer function and Cycle functions will be overridden by the regular switching program or by a manual over-ride!!!
23. Additional adjustments 24. Program modify
Menu Main menu Application
Program query
Program
To query the programming steps and remaining memory locations
Program copy
Program
Copy from one channel to another. Memory of the channel won’t be
overwritten; the copied switching steps appear additionally.
!
Permanent by date function is not copied!
Program delete
Program
Deletion of switching time(s). The program for all channels, single
channels and single programming steps within on channel can be
deleted.
Date-Time
Adjustment
Adjustment of date and time
Summertime
Adjustment
Adjustment of the daylight saving time mode (ON/OFF)
Language
Adjustment
Choice of languages
Program -> Program modify ->
Within Program modify each single switching time can be modified.
25. Data-key
Factory Defaults
Adjustment
Reset to the state of delivery.
!
Date, time and switching program will be lost!
Counter
Options
Displays the hour counter and pulse counter for each channel and
the time switch itself.
PIN-Code
Options
The time switch can be locked with a 4-digit PIN-Code. The code
can be adjusted, activated and deactivated. If you have forgotten
the Code please call customer service.
Reset-Function
Press all front keys for 2 seconds. The time switch is reset. The values for date and
time will be deleted and have to be re-entered. The switching program has not
been deleted!
With a Data-key following activities are possible:
Save data: Writes the data from the time switch into the memory of the Data-key.
Program timeswitch: Writes the data located inside the Key into the memory.
Key function: The time switch will solely apply programming steps from the Data-key. The
switching program of the time switch is suppressed.
Key readout: To query the switching program of the Data-key.
4

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Muller SC98 pro bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Muller SC98 pro in de taal/talen: Duits, Engels als bijlage per email.

De handleiding is 2,48 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Andere handleiding(en) van Muller SC98 pro

Muller SC98 pro Gebruiksaanwijzing - Nederlands, Svenska - 4 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info