9
typically installed at entry/exit points of your
property.
The system Exit-Delay may be configured for
between 10 to 250 seconds or disabled
completely.
If a detector on a zone with its Entry-Delay
enabled is triggered, then an alarm will not
sound until the Entry-Delay period has expired.
This allows time for the user to re-enter the
property and disarm the system before an alarm
occurs. Generally only the zones on the main
entry route to the property will be configured with
an Entry-Delay. The remaining zones would be
configured with their Entry-Delay disabled
allowing them to immediately initiate an alarm
the instant a detector on the zone is triggered.
The Entry-Delay for each zone may be
configured for between 10 to 250 seconds or
disabled completely.
Note: To conserve power and maximize battery
life the PIR movement Detector will only detect
movement if there has been no movement
detected within the previous 2 minutes.
Consequently the PIR Detector will not become
active until the protected area has been free
from movement for more than 3 minutes.
ZONES
The system incorporates 32 wireless alarm
zones for the connection of a PIR movement or
door/window contact detector per zone used to
independently monitor different areas of the
property. In addition to standard intruder
protection, each zone can also be configured to
operate in alternative modes.
For example:
– ‘Intruder’ mode provides standard intruder
monitoring.
– ‘24-hour Intruder’ mode provides 24 hour
intruder protection for areas where continuous
monitoring is required, (e.g. gun lockers).
– ‘Fire’ mode provides 24 hour monitoring of any
Smoke detectors incorporated into the system.
– ‘Test’ mode allows a zone to be monitored
while the system is armed. If a detector on a
zone is triggered an entry will be recorded in the
Event Log but an alarm will not occur.
In addition there is the facility to connect up to 4
hard wired zones to the Control Panel, each of
which is configurable with most of the features of
the wireless zones.
ZONE LOCKOUT
If a detector on an active zone is triggered while
the system is armed an alarm will sound. After
the programmed alarm duration has expired the
alarm will stop and the system will automatically
reset.
Subsequent detectors triggered will again trigger
an alarm. If a single zone triggers an alarm more
than 3 times then that zone will be ‘Locked Out’
and any further alarm signals from that zone will
be ignored until the system is disarmed.
Note: The ‘Zone Lockout’ feature can be
disabled if required.
QUICK SET
The system may be fully armed in 10 seconds
using the quick set facility, overriding the
programmed exit-delay. This is useful for setting
the system at night when the Exit-Delay warning
beep will be silenced after just a few seconds.
EVENT LOG
The Control Panel incorporates a memory
capable of storing the last 99 system events.