IMPORTANT INFORMATION
Correct usage will ensure you have valuable extra
time to escape. Every correctly installed smoke
alarm will increase your potential escape time.
A smoke alarm is not a fire-prevention measure.
Install the smoke alarm in the correct place, if pos-
sible in the middle of the ceiling.
Keep the smoke alarm out of the reach of children.
Test the unit on a monthly basis and after any peri-
od of absence. When the alarm does not sound,
have your smoke alarm inspected by the service
point or when the smoke alarm is more than 10
years old discard the alarm.
CAUTION: Never test with fire!
Clean the smoke alarm regularly (once a month)
using the soft brush from a vacuum cleaner. In
addition the smoke alarm can also be cleaned
using a moist cloth.
If the smoke alarm emits a beeping sound every 40
seconds, this means that the battery is nearly flat
and that you should replace the smoke alarm.
The lifespan of smoke alarms is 10 years.
A false alarm can be silenced by briefly pressing
the test and silence button for < 1 second.
You can make your Model ASD-10Q smoke alarm
less sensitive for 8-9 minutes by briefly pressing
the test button for < 1 second. The smoke alarm
will none-theless sound the alarm if the quantity of
smoke is too significant.
IMPORTANT INFORMATION IN CASE OF
ALARM IN THE EVENT OF A FIRE
• Plan TWO escape routes and practice these with
all members of the family.
Agree upon a location, where everyone goes to in
case of a fire.
In the event of a fire:
Leave the building immediately and go to the
agreed location.
Make sure everyone has left the building.
Close the doors behind you and never open a
warm door. In case of a warm door, choose a diffe-
rent escape route.
In the event of considerable build-up of smoke,
crawl out of the building keeping as close to the
floor as possible.
Wherever possible, breathe through a cloth (pre-
ferably moist), or else hold your breath as much as
you can. The majority of deaths and injuries are
caused by smoke inhalation rather than fire itself.
Call the fire brigade outside or at the neighbours.
NEVER go back into a burning building.
Additional information can be obtained at the local
fire department.
SPECIFICATIONS
Power: 3 V (DC) Lithium AA-Batterie
Battery life: 10 years under normal condi-
tions
Usage: < 8 μA continuous
< 60 mA in alarm
Usage temperature: 0 ºC - 55 ºC
Humidity: ± 3% at 93% RH at 40ºC
Sensitivity: In accordance with EN14604
Alarm volume: >85dB at 3 metres
&HUWLILFDWLRQ .ULZDQ(1±9G6
vfdb 14-01, CE-15.
Self-test: each 10 seconds:
Battery satus
Smoke chamber pollution
Smoke sensor function
POSITIONING THE SMOKE ALARM
Recommended locations:
Optimal protection:
In all rooms, such as bedrooms, living room, study
and suchlike, as well as along escape routes such
as corridor or hallway.
Maximum protection:
- smoke alarm in all rooms (with the exception
of bathrooms, kitchen, garages, etc.)
- Heat alarms can be installed in bathrooms,
kitchens, airing cupboards, utility rooms, etc.
within 5 metres of a potential source of fire.
The smoke alarm should preferably be installed in
the middle of the ceiling, at least 50 cm from the
wall.
In the case of pitched roofs, install the smoke alarm
on the sloping wall, at least 90 cm (measured
vertically) from the ridge of the roof.
Ensure that the smoke alarm can always be
reached for testing and cleaning.
Never fit a smoke alarm:
In bathrooms, kitchens, shower rooms, garages,
etc. Places where a smoke alarm may go off nee-
dlessly due to condensation, normal smoke or
gases. A smoke alarm should be fitted at least 5
metres from such sources of smoke.
Places where the temperature may exceed 55° C
or fall below 0° C, e.g. attics, just above a fire-
place, etc.
In the vicinity of (or adjacent to) decorative objects,
doors, sockets, lights, fittings, windows, wall
ventilators, etc. which could mean that smoke does
not reach the smoke alarm. Minimum 50cm away.
Surfaces that are usually warmer or colder than the
rest of the room. Differences in temperature can
prevent smoke from reaching the smoke alarm.
Adjacent to or directly above stoves or heaters.
In very high or difficult to reach places. This makes
it hard to reach the smoke alarm to test or clean it.
In very dusty or dirty places. Accumulation of dust
will prevent smoke from reaching the smoke cham-
ber and in time will lead to a false alarm.
1772
EN14604:2005/AC 2008
Essential characteristics: Performance:
1RPLQDODFWLYDWLRQFRQGLWLRQVVHQVLWLYLW\UHVSRQVHGHOD\UHVSRQVHWLPH
DQGSHUIRUPDQFHXQGHU¿UHFRQGLWLRQV
Passed
Fito Products BV
De Langkamp 12a
3961 MS Wijk bij Duurstede
The Netherlands
15
1772-CPR-140007
Operational reliability: Passed
Tolerance to supply voltage: Passed
Durability of operational reliability and response delay, temperature
resistance:
Passed
Durability of operational reliability, vibration resistance: Passed
Optical smoke alarm, alerts
you in the event
RI¿UHRUVPRNHDQGLV
suitable for residential
buildings.
Durability of operational reliability, humidity resistance: Passed
Durability of operational reliability, corrosion resistance: Passed
Durability of operational reliability, electrical stability: Passed
Within 1 metre of dimmer switches and wiring.
Some dimmer switches can trigger a fault in the
smoke alarm.
Within 1.5 metres of fluorescent lights. Electrical
impulses can adversely affect the functioning of the
smoke alarm.
Outdoors and in spaces where a large number of
insects are found. Small insects in the unit’s detec-
tion chamber can disrupt the functioning of the
smoke alarm.
The labels on the rear side of the smoke alarm
contain important information.
ATTENTION: The smoke alarm should be tempora-
rily removed during renovation work or structural
alterations and stored in a dust-free environment.
Clean the smoke alarm with the soft brush from a
vacuum cleaner once the day’s work is complete,
and then replace the smoke alarm, always testing it
by pressing the test button once it has been reinstal-
led.
INSTALLATION
1. Choose a location that satisfies the conditions as
described in: Positioning the smoke alarm.
2. Remove the base plate of the smoke alarm
(figure 4) by turning the
base plate anticlockwise
(to the left).
3. Mark the mounting holes
in the base plate and drill
the holes (use a 6 mm
drill). If not using the
screw plugs, then use a 3
mm drill. Screw the base
plate securely onto the
ceiling. Make sure that
the base plate is tight
against the ceiling so that
no air
circulation above the smoke alarm is possible,
which could impede smoke detection. If the
opening is too large, this should be remedied
using the kit.
4. Place the smoke alarm on the base plate and turn
it until the smoke alarm clicks into the base plate.
Turn the smoke alarm clockwise (to the right from
the OFF to the ON stripe) to secure the smoke
alarm and activate it. (See figure 5)
5. Check that the smoke alarm is working and that
the battery has been activated by pressing the test
button for more then 2 seconds. A beeping noise
that stops of its own accord indicates that the
smoke alarm has been activated.
SOUND TEST
Test your smoke alarm immediately after installation:
press the test button for more than 2 seconds
DORXGVLJQDOZLOOVRXQGDQGWKH/('ZLOOÀDVKHYHU\
0,5 sec., this will stop once the test button has been
released.
Test your smoke alarm monthly and after a period of
absence. When the alarm does not sound, have your
smoke alarm inspected by the service point or when
the smoke alarm is more than 10 years old discard
the alarm.
CAUTION: Never test with fire! Every correctly
installed nad maintained smoke alarm will
increase your potential escape time.
FUNCTION AND MEANING OF THE LIGHT AND
SOUND SIGNALS:
Normal situation: The red LED light will flash once
every 5 minutes.
Alarm: Whenever the smoke alarm detects smoke, it
will emit an alarm, 3 loud beeps pause 3 beeps etct.
and the red LED light will flash continuously until the
smoke has cleared.
Low battery signal: A beeping signal every 40
seconds means that the battery is nearly flat and the
smoke alarm needs to be replaced. This signal will
sound for 30 days.
When properly maintained, as described under
IMPORTANT INFORMATION, the battery and the
smoke alarm should continue to work for over a
decade before reaching the end of their lifespan. You
should remove the smoke alarm and base plate from
the ceiling and install a new smoke alarm.
HUSH Button: Your smoke alarm is fitted with a
pause button (see figure 4). This is the same button
DVWKHWHVWEXWWRQ3UHVVWKHSDXVHWHVWEXWWRQEULHIO\
for less than1 second. Your smoke alarm will then go
into a so-called reduced sensitivity mode for 8-9
minutes. The red LED light will flash every 10
seconds to indicate that the Hush button has been
activated. The smoke alarm will nonetheless sound
the alarm if the smoke is dense or increasing in
quantity.
False Alarm: Press the test button briefly for less
than 1 second to stop the alarm. (See Hush button)
Pre-alarm status: The red LED light flashes every
second to indicate that the smoke chamber has been
contaminated to such an extent that the smoke alarm
is close to going into alarm phase and needs to be
cleaned. If thorough vacuuming does not help, then
the contamination is so serious that the detector
must be returned to the factory.
Dust warning: 3 short beep signals every 40
seconds means dust in the smoke chamber. You
have to clean the smoke alarm by using clean
compressed air.
CAUSES OF FALSE ALARM
The smoke alarm can be activated by steam, con-
densation, dust, smoke and small insects. These are
to be prevented as far as possible. See section:
Never fit a smoke alarm. If a smoke alarm is fre-
quently giving a false alarm, it might be necessary to
install the smoke alarm in another location.
Maintenance:
Test your smoke alarm monthly and after a period
of absence. As described in “SOUND TEST”
• Clean the smoke alarm regularly (once a month)
using the soft brush from a vacuum cleaner. In
addition the smoke alarm can also be cleaned by
using a moist cloth.
• The smoke alarm should be temporarily removed
during renovation work or structural alterations.
Clean the smoke alarm with the soft brush from a
vacuum cleaner once the day’s work is complete,
and then place the smoke alarm back on the base.
Always test the smoke alarm by pressing the test
button once it has been reinstalled.
• Repairs must be carried out by the manufacturer.
Never allow the smoke alarm to come into contact
with fluids.
CAUTION: Never apply paint to the smoke alarm
and do not cover it.
LIMITATIONS OF SMOKE ALARMS
In countries where they are commonly in use, smoke
alarms have contributed to reducing deaths and inju-
ries. Independent bodies have established that they
were insufficient in around 35% of fires, namely in
the following situations:
Where the battery had been removed or was not
working. For that reason, you should test the unit
regularly.
Where smoke is not able to reach the smoke alarm
in the event of a fire, meaning the unit cannot be
set off. Examples include a fire on another floor
where there is no smoke alarm, a fire behind
closed doors, a fire in a chimney or smoke being
blown away from the smoke alarm. For that reason,
smoke alarms are recommended in all rooms, or at
any rate on every floor.
Where the alarm is not heard. A person may not be
woken by the alarm if that person had consumed
H[FHVVDOFRKRODQGRUGUXJV
A few fires are not always detected on time, e.g.
smoking in bed, if there is no smoke alarm in the
bedroom. In the case of escaping from gas or
violent explosions, improperly storing explosive pro-
ducts and flammable liquids (petrol, paint, methyla-
ted spirit, etc.), electrical faults, acids, children
playing with matches (fire).
The lifespan of smoke alarms is 10 years.
IMPORTANT INFORMATION IN CASE OF
ALARM IN THE EVENT OF A FIRE
• Plan TWO escape routes and practice these with
all members of the family.
Agree upon a location, where everyone goes to in
case of a fire.
In the event of a fire:
Leave the building immediately and go to the
agreed location.
Make sure everyone has left the building.
Close the doors behind you and never open a
warm door. In case of a warm door, choose a diffe-
rent escape route.
In the event of considerable build-up of smoke,
crawl out of the building keeping as close to the
floor as possible.
Wherever possible, breathe through a cloth (pre-
ferably moist), or else hold your breath as much as
you can. The majority of deaths and injuries are
caused by smoke inhalation rather than fire itself.
Call the fire brigade outside or at the neighbours.
NEVER go back into a burning building.
Additional information can be obtained at the local
fire department.
PRODUCT WARRANTY
If used and maintained properly, the manufacturer
JXDUDQWHHVWKLVSURGXFWDJDLQVWPDWHULDODQGRU
manufacturing faults for a period of 10 years from
the original date of purchase by the consumer, with a
maximum of 11 years after production date. This
guarantee only applies if the smoke detector is
activated within 14 months after the production date.
Exceptions include damage arising from accidents or
misuse. If the product becomes defective within the
stated period, then it will be repaired or replaced free
of charge. Please do not attempt to repair the pro-
duct yourself or tinker with it, which will invalidate the
warranty.
DOP (Declaration of Performance)
The DoP can be downloaded on our website
www.fito.eu
INSTRUCTIONS FOR REMOVAL
Do not dispose of your old smoke alarm in
the bin, but rather hand it in to a local
collection point for small, domestic waste.
MADE IN EUROPE
EUROPEAN SUPPLIER:
Fito Products BV
De Langkamp 12a
3961 MS WIJK BIJ DUURSTEDE
The Netherlands
info@fito.nl - www.fito.eu
Kitchen
Living room
Bathroom
Bedroom
Bedroom
Bedroom
Hallway
Bedroom
Figure 1
Bedroom Hallway
Kitchen Living
room
Figure 2
Hallway
Bedroom
60-90cm
Figure 4
mounting holes
2021-7 vers. 1
SAFETY ISSUES:
Do not paint to the smoke alarm and do not cover it.
• Never install smoke alarm in rooms with a high humidity, such as
bathrooms, showers, kitchens and saunas.
• Test your smoke alarm regularly, once a month and always after
a period of absence. Test by pressing the test button for at least 2
seconds, a loud alarm will follow. Keep a distance of at least 50 cm.
between the smoke alarm and your ears.
• Never open the smoke alarm, this will invalidate the warranty.
Figure 5
Test-/pause
button
LED-light
Instruction manual
OPTICAL SMOKE ALARM WITH A BUILT-IN 3V BATTERY 10 YEARS LIFETIME
Model: ASD-10Q
(1$&
YIGE
1772-CPR-140007
DoP no: 10Q14
15
RETAIN THESE INSTRUCTIONS FOR FUTURE USE!
These instructions for use contain important information for correct
installation and use of your smoke alarm. Please read this informati-
on carefully and retain these instructions for reference.
&KDUDFWHULVWLFVFHUWL¿HG
Ceiling mount YES
Battery powered YES
Battery lifetime 10 years YES
Individual Alarm Indicator YES
Alarm silence facility YES
Suitable for installation in a
caravan NO
Interconnectable NO

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Fito ASD-10Q bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Fito ASD-10Q in de taal/talen: Engels als bijlage per email.

De handleiding is 0.36 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Andere handleiding(en) van Fito ASD-10Q

Fito ASD-10Q Gebruiksaanwijzing - Nederlands - 1 pagina's

Fito ASD-10Q Gebruiksaanwijzing - Deutsch - 1 pagina's

Fito ASD-10Q Gebruiksaanwijzing - Français - 1 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info