current room temperature using the “TEMP”
button.
Set “Cool” mode using the “MODE” button.
Please note that the full cooling capacity is not
achieved until the device has been operating for
approx. five minutes.
Check all the functions as described in the
operating instructions.
Measure and document all the required values
and check the safety functions.
Check the condensate line by pouring distilled
water into the condensate tray, ideally using a
long neck bottle.
If the indoor/outdoor temperature is outside the
“Cool” temperature range (see section 3), press
the emergency switch twice to put the device into
forced cool mode (see section 9). Then carry out
the commissioning process.
b) Heat mode
Adjust the temperature setting to higher than the
current room temperature using the “TEMP”
button.
Set “Heat” mode using the “MODE” button.
Please note that the full heating capacity is not
achieved until the device has been operating for
approx. five minutes.
Check all the functions as described in the
operating instructions.
Measure and document all the required values
and check the safety functions.
Then switch off the system, install any parts that you
have removed and show the operator how to use the
system.
GB
21