583652
24
Verklein
Vergroot
Pagina terug
1/188
Pagina verder
24
Free Cool PreOcc Time (FC.TM)
FC.TM is the configuration that determines how many minutes
before occupancy that free cooling can occur when set for
Preoccupancy (UEFC = 2).
Free Cool Low Temp Limit (FC.LO)
Unoccupied free cooling cannot occur if the Outdoor Air
Temperature (Temperature AIR.T OAT) is less than FC.LO.
Power Exhaust
To enable power exhaust, ConfigurationECONPE.EN must
be set to ENBL. If power exhaust is enabled, Power Exhaust 1 will
turn on when the economizer position is greater than the value of
ConfigurationECONPE.1. If power exhaust is enabled,
Power Exhaust 2 will turn on when the economizer position is
greater than the value of ConfigurationECONPE.2. There are
small time delays to ensure that rapid cycling does not occur.
Optional HumidiMiZert Dehumidification
System
Units with the factoryequipped HumidiMiZer option are capable
of providing multiple modes of improved dehumidification as a
variation of the normal cooling cycle. The HumidiMiZer option
includes additional valves in the liquid line and discharge line of
each refrigerant circuit, a small reheat condenser coil downstream
of the evaporator, and Motormaster variablespeed control of
some or all outdoor fans. The HumidiMiZer Equipped
(ConfigurationHMZRREHT) configuration is factory set to
Yes for HumidiMiZer equipped units. This enables
HumidiMiZer operating modes and service test.
NOTE: If the unit is a HumidiMiZer unit, this configuration
must always be set to yes. The HumidiMiZer option does affect
the base unit wiring.
HumidiMiZer operation requires installation and configuration of
either a space relative humidity sensor or a relative humidity switch
input. Space Humidity Switch (ConfigurationUNITRH.SW)
set to 1 for use of a normally open switch or 2 for normally closed
switch. The switch is wired to field connection terminal board
terminals labeled HUMDISTAT. Set RH Sensor on OAQ Input
(ConfigurationUNITRH.S) to Yes for use of a 4 to 20 mA
output RH sensor wired to field connection terminal board (TB)
terminals 1 and 4 (for loop powered). RH Sensor Value at 4ma
(ConfigurationAIR.QH.4M) sets the % display for a 4mA
input from the relative humidity sensor. RH Sensor Value at 20ma
(ConfigurationAIR.QH.20M) sets the % display for a 20mA
input from the relative humidity sensor.
Dehumidification Demand
When using a humidistat or switch input, the demand for
dehumidification is seen as Space Humidity Switch (Inputs
GEN.IHUM) being Low or High. A low value means
humidity level is good and a high value means that
dehumidification is needed. When using an RH sensor, the demand
is based on the Space Humidity Sensor (InputsAIR.QSP.RH)
value compared to the Space RH Occupied Setpoint
(SetpointsRH.SP) during the occupied period and Space RH
Unoccupied Setpoint (Setpoints RH.UN) during unoccupied
periods. If the Space Humidity Sensor (SP.RH) value is above the
Space RH Setpoint (RH.SP), then dehumidification is needed. If
the Space Humidity Sensor (SP.RH) value is below the Space RH
Setpoint (RH.SP) minus the Space RH Deadband
(SetpointsRH.DB), then dehumidification is no longer needed.
If the unit is configured for space sensor control
(ConfigurationUNIT U.CTL = 3), then the setpoint Reheat
Heat SP Deadband (SetpointsRH.HB) applies. This
configuration sets the offset above the heating set point at which a
unit in Reheat2 mode will turn off. This is a protection against over
cooling the space and causing a heat demand.
NOTE: When there is a dehumidification demand, the economizer
damper position is limited to its minimum damper position
(Operating ModeECONEC.MP).
Reheat Modes
Dehumidification (reheat) is a cooling mode function. Refer to
Cooling Operation for cooling mode control. With HumidiMiZer
units there are three additional HVAC Mode (HVAC) expanded
texts available for the user: Reheat1, Reheat2, and
Reheat1/Reheat2. Selection of the reheat mode for each refrigerant
circuit is determined by the dehumidification demand and the
cooling demand. Table 10 shows the corresponding circuit mode
and output status for the different demand combinations. Units
with multiple circuits can operate with a combination of Reheat1
and Reheat2 circuits, as determined by the amount of space cooling
demand. See Appendix B for complete tables of unit operation
response to thermostat and humidity inputs.
NOTE: Compressor staging control for HumidiMiZer units
requires that circuit A always operates when either circuits B or C
are on. This applies to normal operation, service test, and for
control alarm responses. This operation difference is required due
to the fact that the Motormaster outdoor fan control senses circuit
A only.
Operation of the revised refrigerant circuit for each mode is
described below.
NOTE: x = refrigerant circuit A, B, or C
Normal Cooling
For 48/50PG0316 units, refrigerant flows from the outdoor
condenser through the normally open Cooling Valve (CV.x) to the
expansion device. Reheat1 Valve (RH1.x) and Reheat2 Valve
(RH2.x) are closed. (See Fig. 9.)
For 48/50PG2028 and 48/50PM1628 units, refrigerant flows
from the outdoor condenser through the deenergized 3way valve
(RH.x) to the expansion device. Reheat2 Valve (RH2.x) is closed.
(See Fig. 12.)
Reheat 1 (Subcooling Mode)
This mode increases latent cooling and decreases sensible cooling
compared to normal cooling.
For 48/50PG0316 units, refrigerant flows from the outdoor
condenser, through the normally open Reheat 1 Valve (RH1.x),
and through the reheat condenser coil to the expansion device.
Cooling Valve (CV.x) and Reheat2 Valve (RH2.x) are closed. (See
Fig. 10.)
For 48/50PG2028 and 48/50PM1628 units, refrigerant flows
from the outdoor condenser, through the energized 3way Valve
(RH1.x), and through the reheat condenser coil to the expansion
device. Cooling Reheat2 Valve (RH2.x) is closed. (See Fig. 13.)
Reheat 2 (Hot Gas Reheat Mode)
This mode provides maximum latent cooling with little to no
sensible capacity. This mode can operate to provide
dehumidification when there is no cooling demand. Similar to
Reheat 1 mode, refrigerant flows from the outdoor condenser,
through the normally open Reheat 1 Valve (RH1.x), or through the
energized 3way valve (RH.1x), and through the reheat condenser
coil to the expansion device. Reheat2 Valve (RH2.x) is open which
provides some compressor discharge gas to the reheat condenser to
further increase the reheat of the evaporator air stream (See Fig. 11
or 14 based on unit and size).
NOTE: HumidiMiZer outdoor fan configurations are dependent
on the specific unit and should not be changed. The configurations
are provided in case a field replacement of a control board occurs
and the settings need to be checked or manually configured. See
Appendix A for range and defaults.
48/50PG and PM
24

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Carrier 48 50PM C16-28 bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Carrier 48 50PM C16-28 in de taal/talen: Engels als bijlage per email.

De handleiding is 9,71 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info