583652
22
Verklein
Vergroot
Pagina terug
1/188
Pagina verder
22
Space Sensor Control
Space sensor staging control is an adaptive anticipation control that
weighs the actual space demand against the trend of that demand.
It also honors stage time guards and supply air limits. The demand
for heating in the space is displayed as the Heating Demand (Run
StatusHEATDMD.H). The control tries to anticipate the
change in the space because of its current stage status. This
anticipation is based on the Heat Demand Trend (Operating Modes
HEATTRD.H). This trend will show the control how the
space is reacting to the current running conditions and help it
decide when to add or remove one stage from the requested stages.
The Heat Stage Increase Time (ConfigurationHEATH.INC)
or the Heat Stage Decrease Time (ConfigurationHEAT
H.DEC) has to expire before another stage can be added or a
stage can be subtracted. If at any time the SupplyAir Temperature
(SAT) rises above the Maximum Supply Air Temperature Lower
Level (ConfigurationHEATSATSAM.L), the requested
stages will not be allowed to increase. If at any time the SAT rises
above the Maximum Supply Air Temperature Upper Level
(ConfigurationHEATSATSAM.U), the requested stages
will be reduced by one without honoring H.DEC.
Heat Relay Control
The heat relay control is responsible for energizing or
deenergizing the MBBs heat stage relays and works hand in hand
with the staging control. As the staging control requests stages, the
heat relay control determines what actual heat relays are available
or energized and tries to provide stages for what is requested. The
availability of a heat relays depends on heat being installed, how
many stages, and time guards. The type of Heat Installed
(ConfigurationHEATHT.TY) must be set for gas or electric
for any stages to be available. The Number of Heat Stages
(ConfigurationHEATN.HTR) configuration tells the control
how many heat relays can be used. Heat Stage 1Timeguard (Run
StatusHEATTG.H1) and Heat Stage 2 Timeguard (Run
StatusHEATTG.H2) display the time a respective heat relay
has before it is available for use. The available stages at any given
time are displayed as Available Heating Stages (Run Status
HEATAVL.H). The actual heat relays on at any given time
are displayed as Actual Heating Stages (Operating ModesHEAT
ACT.H). Heat Stage 1 Relay (Run StatusHEATHT.1) and
Heat Stage 2 Relay (Run StatusHEATHT.2) are displayed on
when the respective relay is energized. There are time guards to
protect from short cycling, Heat Minimum On Time
(ConfigurationHEATMRT.H) and Heat Minimum Off Time
(ConfigurationHEATMOT.H) apply before a heat relay can
be turned back on or turned off.
Integrated Gas Controller (IGC)
The heat staging is determined as described above and the
Integrated Gas Controller (IGC) initiates the gas heat module
startup. The Integrated Gas Controller (IGC) minimum ontime
of 1 minute will be followed even if Heat Minimum On Time
(ConfigurationHEATMRT.H) is lower and during Service
Test. If the IGC temperature limit switch opens within 10 minutes
of the end of the gas heat cycle, the next fan off delay will be
extended by 15 seconds. The maximum delay is 3 minutes. Once
modified by the IGC, the fan off delay will not change back to the
configured Fanoff Delay, Gas Heat (ConfigurationHEAT
FOD.G) unless power is reset to the control. A light emitting
diode (LED) is provided on the IGC to indicate status. During
normal operation the LED is continuously on. See the
Troubleshooting section if the LED is off or flashing. The IGC is
located behind the gas section access panel door.
When the control energizes Heat Stage 1 Relay (Run Status
HEATHT.1), power is sent to the W terminal on the IGC
board. A check is made to ensure that the rollout switch and limit
switch are closed. The induceddraft motor is then energized, and
when speed is proven with the Hall Effect sensor on the motor, the
ignition activation period begins. The burners will ignite within 5
seconds. If the burners do not light, there is a 22second delay
before another 5second attempt. If the burners still do not light,
this sequence is repeated for 15 minutes. After the 15 minutes have
elapsed, if the burners still have not lit, heating is locked out. The
control will reset when the request for heat is temporarily removed.
When ignition occurs, the IGC board will continue to monitor the
condition of the rollout switch, limit switches, the Hall Effect
sensor, as well as the flame sensor. If the unit is controlled through
a room thermostat or space sensor set for fan auto, 45 seconds after
ignition occurs the indoorfan motor will be energized (and the
outdoorair dampers will open to their minimum position). If for
some reason the over temperature limit opens prior to the start of
the indoor fan blower, on the next attempt, the 45second delay
will be shortened to 5 seconds less than the time from initiation of
heat to when the limit tripped. Gas will not be interrupted to the
burners and heating will continue. Once modified, the fan on delay
will not change back to 45 seconds unless power is reset to the
control. When the control energizes Heat Stage 2 Relay (Run
StatusHEATHT.2), power is supplied to the second stage of
the main gas valve. If both stage 1 and stage 2 of the gas valve
close, gas will be turned off to the main burners.
48/50PG and PM
22

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Carrier 48 50PM C16-28 bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Carrier 48 50PM C16-28 in de taal/talen: Engels als bijlage per email.

De handleiding is 9,71 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info