Commissioning
33
Uni Condens 8000 F – 6720867056 (2016/10)
8 Commissioning
NOTICE:
System damage through incorrect burner adjustment
(overloading)!
Make sure that the value set does not exceed the rated heat output
Qn(Hi) stated on the data plate.
NOTICE:
Risk of boiler damage through contaminated combustion air!
Never operate the boiler in very dusty conditions, e.g. if building work
is taking place at the installation location.
Ensure adequate air supply.
Never use or store chlorinated cleaning agents or halogenated
hydrocarbons (as contained in spray cans, solvents or cleaning
agents, paints and adhesives, for example) at the installation
location.
A burner contaminated during building work must be cleaned before
commissioning.
Complete the commissioning report ( chapter 14.4, page 42).
8.1 Purge the heating system
If the heating system contains several heating circuits, these must be
purged one after the other.
To prevent contamination in the boiler, flush the heating system prior to
commissioning.
Purge the system prior to connection to the boiler.
-or-
Isolate the heating flow and return at the boiler.
Connect the heating flow to a water connection.
Connect hose to the heating return of the heating system.
Route hose from the heating return to a drain.
Open connected consumers (e.g. radiators).
Purge the heating system with potable water until clear water
emerges from the heating return.
Drain the heating system down.
8.2 Carrying out a leak test
The test pressure depends on the actual pressure in the heating system
and should be 1.3 times the prevailing pressure or at least 1 bar.
Carry out a leak test according to locally applicable regulations.
8.3 Filling the heating system
CAUTION:
Health risk through contaminated drinking water!
Observe all country-specific regulations and standards regarding the
prevention of drinking water contamination. In Europe, observe
standard EN 1717.
NOTICE:
System damage due to temperature stresses!
Only fill the heating system when cold
(the flow temperature must not exceed 40 °C).
During operation, only fill the heating system via the filling facility in
the heating system pipework (return).
Open the automatic air vent valve only briefly for ventilation.
The fill and top-up water quality must comply with the specifications in
the operator's log supplied ( chapter 4.6, page 14).
The pH value of the heating water increases after the heating system has
been filled.
During initial maintenance (after three to six months) check whether
the pH value of the heating water has settled down.
Adjust the pre-charge pressure of the expansion vessel to the
required pressure (only for sealed unvented systems).
Open the mixing and shut-off valve on the hot water side.
Fill the heating system slowly using an on-site filling device and
observe the pressure gauge whilst doing so.
Vent the heating system via the radiator air vent valves.
If the operating pressure drops as a result of venting the system:
Top up the system with water.
Carry out a tightness test in accordance with locally applicable
regulations.
After the tightness test, reinstate all components that were taken out
of operation.
Ensure that all pressure, control and safety equipment is functioning
correctly.
Once the boiler has been tested for tightness and no leaks have been
found:
Set the correct operating pressure.
Close the automatic air vent valve.
8.4 Setting the minimum and maximum pressure limiters
(accessories)
8.4.1 Setting the maximum pressure limiter
The maximum pressure limiter must be set in such a way that the
pressure relief valve is prevented from responding. To achieve this, a
safety margin of 0.2 bar compared to the excess pressure of the
pressure relief valve must be maintained. The maximum excess pressure
of the boiler's pressure relief valve depends on the size of the boiler
( tab. 18, page 41).
Example:
Pressure relief valve excess pressure: P
SV
= 5 bar
Setting value, maximum pressure limiter: 5 bar - 0.2 bar = 4.8 bar
To set the pressure limiter, refer to documentation of the pressure
limiter.
8.4.2 Setting the minimum pressure limiter
The minimum pressure limiter must be set in such a way that no steam
bubbles form in the boiler, and that the boiler still operates safely.
This setting depends on the system conditions and the siting situation of
the boiler system.
A minimum value of 1 bar must always be set for rooftop infrastructure
centres. We recommend using a low water indicator with rooftop
infrastructure centres.
For the setting value, the boiling pressure associated with the setting
value of the high limit safety cut-out is relevant as is the consumer at the
highest geodetic level above the boiler.
The available geodetic level calculated lies between the highest point of
the consumer and the installation location of the pressure maintaining
system.
33

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Bosch Uni Condens 8000 F bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Bosch Uni Condens 8000 F in de taal/talen: Engels als bijlage per email.

De handleiding is 10,41 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Andere handleiding(en) van Bosch Uni Condens 8000 F

Bosch Uni Condens 8000 F Gebruiksaanwijzing - Nederlands - 12 pagina's

Bosch Uni Condens 8000 F Gebruiksaanwijzing - Deutsch - 16 pagina's

Bosch Uni Condens 8000 F Gebruiksaanwijzing - English - 12 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info