Control unit
Uni Condens 8000 F – 6720867056 (2016/10)
32
Control unit settings
Select temperatures ( tab. 14, page 31) at high limit safety cut-out
and in the control unit.
The maximum temperature demand is not a value that is set directly. The
maximum temperature demand is composed of the set temperature and
the rise.
Example DHW demand:
Sum of the set DHW temperature (60 °C) and the parameter "boiler
temperature increase" (20 °C) in the "DHW" menu:
60 °C + 20 °C = maximum temperature demand 80 °C.
Example heating circuits:
Sum of the set temperature of the heating circuit with mixer with the
highest temperature required (70 °C) and the parameter "boiler
temperature increase" (5 °C) in the "Heating circuit data" menu:
70 °C + 5 °C = maximum temperature demand 75 °C.
All maximum temperature demands must always be 7 K below the
maximum selected boiler water temperature.
7.3.4 Setting control unit parameters
The controller settings listed in tab. 15, page 32 apply for the control
unitsCC 8311and CC 8312.
To ensure that the control unit operates correctly if burner type "dual fuel
burner" is selected, connect a volt-free contact to terminal "ES" to
change the fuel type.
Table 15 Controller settings for CC 8311 and CC 8312 control units
7.4 Settings with third party control units
NOTICE:
System damage due to incorrect sensor position!
The sensors of the high limit safety cut-out (STB) and the temperature
controller (TR) must be fitted at the installation location on the top of the
boiler ( fig. 23, page 24).
In the case of third party control units, match the sensor immersion
sleeve to the diameter of the sensors used.
Do not change the length of the immersion sleeve.
Observe the operating conditions in chapter 2.9, page 9 and observe
chapter 6.14, page 24 when installing sensors.
The third party control unit (building management system or PLC
controllers) must ensure a sufficient difference between the
maximum internal boiler water temperature and the high limit safety
cut-out.
The purpose of optimum control unit settings is to achieve long burner
runtimes and avoid rapid temperature changes in the boiler. Gentle
temperature changes result in a longer service life of the heating system.
The control strategy of the control unit must therefore be prevented from
becoming ineffective, i.e. through the boiler temperature controller
switching the burner on and off.
Observe the following points when selecting the control unit.
The control unit must ensure that the maximum internal boiler
temperature and the high limit safety cut-out are at least 5 K apart.
It must also be ensured that the control electronics rather than the
boiler temperature controller switch the burner on and off.
The control unit must ensure that the burner is switched to low load
before a controlled shutdown. If this is not observed, the safety shut-
off valve (SAV) in the gas train may lock out.
Select and adjust the control unit so as to allow a gentle start-up of
the boiler with a time delay when the system is cold. The heat energy
demand must only be switched on with time delay.
After the burner demand, an automatic timer (for example) should
limit the burner to low load for a period of approx. 150 seconds. A
restricted heat demand will prevent uncontrolled starting and
stopping of the burner.
It must be possible to show the number of burner starts at the control
unit used (or alternatively at the burner control unit).
The maximum number of burner starts must be monitored. There
should be a maximum of 6 burner starts per hour (averaged over
burner runtime on one day). If the number of starts is higher, the user
should be notified. The system must be checked to find out whether
the number of burner starts can be reduced. The customer service of
the manufacturer can provide assistance with optimisation of the
system.
Table 16 Operation conditions
Burner Control unit setting
Burner type for fuel Burner type
to be selected
Burner Gas Oil
Single fuel burner Modulating Modulating
2-stage 2-stage
Modulating 2-stage
2-stage 2-stage
Dual-fuel burner Modulating Modulating Dual-fuel burner
Dual-fuel burner Modulating 2-stage Dual-fuel burner
Unit Value
Time constant on
temperature
controller, max.
s40
Time constant on
temperature switch/
limiter, max.
s 40
Minimum difference
between burner on
and off temperatures
K7
32

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Bosch Uni Condens 8000 F bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Bosch Uni Condens 8000 F in de taal/talen: Engels als bijlage per email.

De handleiding is 10,41 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Andere handleiding(en) van Bosch Uni Condens 8000 F

Bosch Uni Condens 8000 F Gebruiksaanwijzing - Nederlands - 12 pagina's

Bosch Uni Condens 8000 F Gebruiksaanwijzing - Deutsch - 16 pagina's

Bosch Uni Condens 8000 F Gebruiksaanwijzing - English - 12 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info