01/2014
DUSPOL
®
digital
8
O
symbol for external conductor test (phase indication)
P , symbol of the phase sequence indication (left /
right)
Q
Display for voltage (V)/resistance (kΩ)
R
+/- of the polarity indication
S VDC/VAC voltage type (direct/alternating voltage)
T Frequency indication (Hz)
symbol for diode test
symbol for discharged battery
symbol for resistance measurement
3. Functional test before use to ensure the absence of
voltage of an installation (gure A)
- Check the voltage tester for correct functioning immedi-
ately before and after using it!
- It must be possible to switch the voltage tester on as fol-
lows:
automatically, if a voltage of 6 V or more is applied to
the probe tips L1/-
2
and L2/+
3
,
by actuating the push-button
7
of the display handle
L2
9
,
by short-circuiting the probe tips L1/-
2
and L2/+
3
.
- If the symbol is shown on the LC display
6
, the bat-
tery must be replaced.
- The device is switched off automatically after 10 seconds.
- Activation of the self-test:
Short-circuit the probe tips L1/-
2
and L2/+
3
.
Press and hold the push-button
7
of the display han-
dle L2
9
for approx. 3 seconds to start the self-test.
The buzzer sounds and all segments of the LC dis-
play, all LEDs (running light) as well as the back-
ground and measuring point illumination must be
functioning.
- Test the voltage tester with familiar voltage sources, e.g.
with a 230 V socket.
- Do not use the voltage tester, if the voltage indication, the
phase indication and the vibration motor are not working
properly!
4. Checking the absence of voltage of an installation (g-
ure B/C)
For checking the installation, please test the absence of vol-
tage by checking the voltage indication, the phase indication
(the phase indication only works in an earthed AC voltage
mains) and the vibration motor (the vibration motor is activated
by actuating both push-buttons). The installation is only free
of voltage, if all three test circuits (voltage indication, phase
indication and vibration motor) are signaling the absence of
voltage.
- Apply the two probe tips L1/+
2
and L2/-
3
to the system
parts to be tested.
- The voltage tester switches on automatically as soon as a
voltage ≥ 6 V is applied.
- The level of voltage applied is indicated by means of the
LED step indicator
J
and the digital display
6
.
The 400 V LED of the LED step indicator 10 covers
the voltage range from 400 V AC/DC to 1,000 V AC/
1,200 V DC.
- Alternating voltages are indicated by means of the VAC
symbol on the LC display
6
. Additionally, the frequency
T
of the AC voltage applied is displayed.
-
Direct voltages are indicated by means of the VDC symbol
on the LC display
6
. Additionally, the polarity indication
R
shows the polarity (+ or -) applied to the probe tip L2/+
3
.
- To differentiate between low-energy and high-energy volt-
ages (e.g. capacitively induced interference voltages), an
internal load in the voltage tester can be connected by ac-
tuating both push-buttons (see section 5).
Voltage test < 6 V (low-volt) (gure D)
In order to measure voltages lower than 6 V, short-circuit the
probe tips L1/-
2
and L2/+
3
and press the push-button
7
of the display handle L2
9
three times until the „Lo U“ symbol
is shown on the LC display
6
.
- In the low-volt range, voltages from 1.0 V to 11.9 V can be
measured.
- After being activated, the low-volt range is active for ap-
prox. 10 seconds.
- By applying a voltage 12 V, the device automatically
switches over to a higher voltage range.
Note:
In the low-volt range, the frequency indication
T
is deactivated.
Overload indication
If the voltage applied to the probe tips L1/-
2
and L2/+
3
is
higher than the admissible nominal voltage, the „OL“ symbol is
shown on the LC display
6
and all LEDs of the step indica-
tor
J
are ashing. Overload is indicated from 1,050 V AC,
1,250 V DC on.
5. Load connection with vibration motor (gure B/C)
Both handles L1
8
and L2
9
are equipped with push-buttons
7
. Here, voltage is applied to a vibration motor (motor with
unbalanced mass) in the display handle L2
9
. From approx.
200 V on, this motor is set in rotary motion. With the voltage
increasing, the motor‘s speed and vibration increases as well.
The duration of the test with a lower internal resistance (load
test) depends on the level of voltage to be measured. In order
to avoid an inadmissible warming of the device, it is provided
with a thermal protection (controlled reduction). With this con-
trolled reduction, the speed of the vibration motor is reduced
and the internal resistance increases.
The load connection (with both push-buttons being actuated)
can be used ...
- to suppress reactive voltages (inductive and capacitive
voltages),
- to charge capacitors,
- to trip 10/30 mA FI safety switches. The tripping of the FI
8

Hulp nodig? Stel uw vraag in het forum

Spelregels
1

Forum

Benning-Duspol-Digital

Zoeken resetten

  • Duspol digital LC IP 64 werkt na sluiting op een van de pennen niet meer, zit er in de meter een zekering die vervangen kan worden?

    met vriendelijke groet,

    Bonno Ruigrok Gesteld op 9-1-2016 om 21:35

    Reageer op deze vraag Misbruik melden

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Benning Duspol Digital bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Benning Duspol Digital in de taal/talen: Nederlands, Duits, Engels, Frans, Italiaans, Spaans, Pools, Turks, Deens, Zweeds, Noors, Fins als bijlage per email.

De handleiding is 14,29 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info