8.2 MODE LS
Select minimum voltage value for LS link
Select each digit using Ȇ, ȇ keys and press ENTER to confirm (digit by digit selection).
The following text appears on the screen:
Select maximum voltage value for LS link
Select each digit using Ȇ, ȇ keys and press ENTER to confirm (digit by digit selection).
The following text appears on the screen:
Select airflow corresponding to Vmin
Select each digit using Ȇ, ȇ keys and press ENTER to confirm (digit by digit selection).
The following text appears on the screen:
Select airflow corresponding to Vmax
Select each digit using Ȇ, ȇ keys and press ENTER to confirm (digit by digit selection).
The following text appears on the screen:
Select multiplier of LS link (on airflow) when terminals +12V and K3 are closed (‘night’ setup).
Select each digit using Ȇ, ȇ keys and press ENTER to confirm (digit by digit selection).
The following text appears on the screen:
Pressure alarm is optional. Of you do not wish to set a pressure alarm select N(o), otherwise select Y(es) using Ȇ, ȇ keys and press
ENTER to confirm.
If you selected N(o), the following text appears on the screen:
The setup is then completed.
If you selected Y, the following text appears on the screen:
Pressure alarm setup:
Choice of allowed pressure increment (?Pa admitted on filter) at reference airflow
Select value using ?? keys, press ENTER to confirm (digit by digit selection).
Pressure alarm setup:
Definition of reference pressure at reference airflow (optional if previously carried out)
Selectionner Y(es) / N(o) using ?? keys then press ENTER to confirm.
If you selected N(o), the following text appears on the screen:
The setup is then completed.
If you chose Y(es), the following text appears on the screen:
Pressure alarm setup :
Enter airflow to define reference pressure.
Select each digit using ?? keys and press ENTER to confirm (digit by digit selection).
Following texts appear alternatively on the screen and LED Alarm blinks:
Reference pressure initialisation busy….
Display of actual pressure and airflow...
The setup is then completed.
V min?
00,0 V
V max?
10,0 V
m
3
/h
–
–
–
Vmin
xxxx
PRESSURE
ALARM? N
END SETUP
∆P FAN
xxx Pa
INIT Pa
REF? N
m
3
/h
–
–
–
Vmax
xxxx
% ON
K3? 100%
END SETUP
END SETUP
m
3
/h INIT
0000
Pa REF
INIT
xxxxm
3
/h
xxxx Pa