Flow (Volume)
- View of the cumulated volume in m3.
It is possible to reset the stored value by holding down on the
(►) & (-) keys for 5 sec.
Energy
- View of the cumulated energy in kWH.
It is possible to reset the stored value by holding down on the
(►) & (-) keys for 5 sec.
Power
- View of the instantaneous power in W.
2.7 Protection function
With this menu it is possible to select and adjust all the
protective functions and parameters of your installation.
2.7.1 Max temp collector
- Setting the start level of the overheat protection for the
collector array.
(Adjustable 110 to 150°C with factory value 120°C)
2.7.2 Overheat protection
This function will stop all collector circulation (P1 and P2) when
the collector temperature increases above “Maxtemp” plus an
offset value (+10°C default value, can be changed). This
function is used to protect the elements of the installation
(Pipe, fitting, ring rubber...)
- To activate the function, press (+) or (-) to select the
Overheat prot.“ line and press (►) to active “yes” this
function with (+) or (-).
- It is now possible to adjust the offset level
(Adjustable +10°C to +30°C with factory value +10°C)
IMPORTANT: For safety reasons this function should
always be “Yes
2.7.3 Cooling
- When the “cooling” function is active “Yes”, it is also possible
to activate the “Recooling” function.
This option is used to protect the collector heat transfer fluid
and system as follows; it activates the solar pump P1 or P2 if
temperature of the collector arrays T1 or T4 exceeds the “Max
temp coll.” value even if the set maximum temperature in the
tank is exceeded.
The circulation stops when:
- Temperature in the collector has dropped 10°C.
- Temperature in the tank reaches the cooling “Max Temp
level (MaxTemp Tankx + xx°C) adjustable 5°C to +40°C with
default value of +10°C.
- If the water temperature in the tank reaches 95°C.
2.7.4 Recooling
When the water temperature inside the tank is above the
setting level “Maxtemp tank X” and the collector temperature is
10°C under the pump is activated to cool the tank through the
collector array (during the night).
The pump will be turned off when:
- The water temperature inside the tank has dropped to the
setting level recooling “MinTemp”“(MinTemp Tankx - xx°C)
adjustable -5°C to -40°C with default value -10°C.
- When the difference between the tank and collector array
temperature is below 2°C.
2.7.5 Freeze protection
This option will keep the solar panel temperature T1 or T4
above the Freeze setting level (see below) by activating the
pump P1 or P2.
This option can be used to reduce snow accumulation on the
panel and increase the efficiency during the day or to avoid
damage by the freezing and expansion of the heat transfer
fluid.
Careful: it is preferable not to use this function in very cold
regions in order not to use too much the energy stored in the
tank
- To activate the freeze and snow protection, press (+) or (-) to
select the “Freeze prot“ line and press (►) to active “yes” this
function with (+) or (-).
- It is now possible to adjust the Freeze setting level
(Adjustable -20°C to + 7°C with factory value 3°C)
2.8 Degrees
- On this menu you can choose the displayed units.
°F: °F, 12H am/pm, Liter, KW and KWh
°C: ° C, 24H, Liter, KW and KWh
2.9 Tubes collector
Select the lines “Tubes collector” and press (►) to highlight
the line.
- Now select with (+) or (-) yes” if your installation use vacuum
tubes collector. (This choice can be use with flat collector when
the sensor is mounted on the external parts of the collector).
- This function could be used if the collector sensor is not
directly mounted on the collector.
This function works in the following way.
Each 30 minutes the pump will be activated 30 seconds to
measure the correct value on the collector to avoid short
charge cycle.
2.10 Factory setting
Important: For reasons of error protection the selected system
and time settings will not be reset!
- If you want to reload all parameters with factory value select
press (►) to highlight the line. Then select “yes” with (+) key.
- Now press (◄) repeatedly to return to the main menu.
3 Settings Menu
On this menu you have all basic adjustable settings of your
installation.
3.1 Maxtemp tank1
- Maximum value of desired water temperature on the tank1
during normal operation. (Adjustable 15 to 95°C with factory
value 65°C)
3.2 dTON tank1
- Difference between collector temperature T1 and Tank1
temperature T2 to start the main pump1. (Adjustable 4 to 40°C
with factory value 15°C)
3.3 dTOFF tank1
- Difference between collector temperature T1 and Tank1
temperature T2 to stop the main pump1. (Adjustable 2°C bis
35°C (dTMin <=2°C dTMax Tank 1 with factory value 7°C)
 Protection Function -
Max temp coll. 120°C
Overheat prot. Yes
Overheat temp. +10°C
Cooling Yes
Max temp (xx°C) +40°C
Recooling Yes
Min temp (xx°C) -40°C
Freeze prot. Yes
Freeze prot. Temp. -20°C
13

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Watts Solar Controller LCD PLUS bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Watts Solar Controller LCD PLUS in de taal/talen: Duits, Engels als bijlage per email.

De handleiding is 1.12 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info