805499
17
Verklein
Vergroot
Pagina terug
1/28
Pagina verder
GB
1
Climatic Control H&C
User Guide
PPLIMW08157Ch
EN
wattswater.eu
GB
2
INSTALLATION AND OPERATION MANUAL
ClimaticControl-HC Heating & Cooling Controller
IMPORTANT!
Before starting work the installer should carefully read this Installation & Operation Manual, and make sure all
in- structions contained therein are understood and observed.
ClimaticControl-HC should be mounted, operated and maintained by specially trained personnel only. Personnel
in the course of training are only allowed to handle the product under the supervision of an experienced fitter.
Subject to observation of the above terms, the manufacture shall assume the liability for the equipment as
provided by legal stipulations.
All instructions in this Installation & Operation manual should be observed when working with the control. Any
other application shall not comply with the regulations. The manufacturer shall not be liable in case of
incompetent use of the control. Any modifications and amendments are not allowed for safety reasons.
ClimaticControl-HC mainte- nance may be performed by service shops approved by the manufacturer only.
The functionality of the control depends on the model and equipment. This installation leaflet is part of the product
and has to be obtained.
Subject to technical modification!
Table of content
1. Application ..................................................................................................................................................... 3
2. References, Symbols and Abbreviations ...................................................................................................... 3
3. Safety Instructions ......................................................................................................................................... 3
4. Display ........................................................................................................................................................... 4
5. Installation and Electrical connections .......................................................................................................... 4
5.1 ClimaticControl-HC Installation ..................................................................................................................... 4
5.2 Electrical connections.................................................................................................................................... 5
5.3 Hydraulic installation ..................................................................................................................................... 6
5.4 Room Temperature – Direct Plug In ............................................................................................................. 9
6. Types of operating modes / Program menu ................................................................................................ 14
6.1 Heating and cooling switch ......................................................................................................................... 14
There are several ways to switch the system between heating and cooling. .................................................................. 14
Use parameter #0 Type (See Chap 7.1) ..................................................................................................... 14
Use the user interface of the Climatic Control HC if parameter #0 Type=Rev (See Chap 7.1) .................. 14
Use the user interface of the paired MILUX-RF HYGROSTAT if parameter #0 Type=Rev ....................... 14
Use Input 1 parameter #11 In1=HC or Input 2 parameter #12 In2 =HC (See Chap 5.4.7 and Chap 7.1) . 14
6.2 Types of operating modes ........................................................................................................................... 14
6.3 Program Mode ............................................................................................................................................. 16
7 System Parameter Menu ............................................................................................................................ 18
7.1 System parameters setting ......................................................................................................................... 18
7.2 Heating & Cooling curves ............................................................................................................................ 24
7.3 Corresponding value for sensors. ............................................................................................................... 24
8.Technical Data / Materials ............................................................................................................................................. 24
9. TROUBLE-SHOOTING ............................................................................................................................... 25
GB
3
1. Application
ClimaticControl-HC is developed for variable flow temperature control in heating and cooling systems particular
in low-temperature installations like floor heating and cooling systems. The flow temperature is controlled de-
pending of the outside temperature following a curve.
Using the ClimaticControl-HC the operation of a water floor system can be adapted to the actual demands of the
system. In particular, the control can be used in apartments where users have their own individual living habits.
A room temperature thermostat can also be connected. The control has a 7-day programmer including 9 factory
set programs and 4 user defined programs.
The control is normally used in conjunction with a hydraulic control unit which includes circulation pumps, a two-
or three-way mixing valve and a valve actuator.
The ClimaticControl-HC has been designed for use in dry environments, e.g. in residential rooms, office spaces
and industrial facilities.
Verify that the installation complies with existing regulations before operation to ensure proper use of the instal-
lation.
2. References, Symbols and Abbreviations
For better understanding in this document references are used in the form of symbols and abbreviations, which are
described below.
Reference to further documents
FlH
Floor heating
Important information and application hints RaH Radiant heating (general)
Safety information or
Important information about functions
FRG Hydraulic control unit with pump and mixing
valve
OK-button (OK) HKV Manifold
Control button Left (◄) MuB Installation and operation manual
Control button Right (►) TB Temperature limiter
Plus button (+) UWP
Circulation pump
Minus button (-) WE Boiler / heat generator
3. Safety Instructions
Before starting work disconnect power supply!
All installation and wiring work on the ClimaticControl-HC must be carried out only when de-energized.
The appliance should be connected and commissioned by qualified personnel only. Make sure to ad-
here to valid safety regulations, in particular to VDE 0100 (German standard governing power installa-
tions of nominal voltages ≤ 1000 VAC).
The ClimaticControl-HC is neither splash, nor drip-proof. Therefore, they must be mounted at a dry place.
Do not interchange the connections of the sensors and the 230V connections under any circumstances! Inter-
changing these connections may result in life endangering electrical hazards or the destruction of the appliance and
the connected sensors and other appliances.
GB
4
4. Display
10
11
12
13
6
14
Dimensions
86 mm 47 mm
Fig.3
5. Installation and Electrical connections
5.1 ClimaticControl-HC Installation
The ClimaticControl-HC can be installed directly on a solid base (e.g. a wall). For this purpose the front panel of the
ClimaticControl-HC must be removed (fig. 4a) and the back section should be fastened using appropriate screws
and pins (these are not included in the scope of supply) (fig 4b) Fix the climatic control HC on a plane surface (wall…)
If the ClimaticControl-HC has been factory fitted with cables for connecting to a pump, valve drive, temperature
limiter, sensors etc., take care not to damage or crack the cables during the installation. Furthermore these cables
should not subjected to any tensile stress during installation. The cables will be fixed by means of the device for
strain relief at the ClimaticControl-HC.
If the ClimaticControl-HC is delivered together with a hydraulic control unit (for example FRG or FlowBox) and if it is
not attached to that unit by any installation plate or support, it should be installed next to that unit.
Pay attention to the correct connection of the cables if the ClimaticControl-HC is not installed directly on a hydraulic
control unit but at some other place for the reason of better access.
Refer to the directions about this in section 5.2 Electric connections.
Details Pos. 6
a
b
4
Fig.2
1:
Operating modes
2: Keyboard is locked
3: Service Installation Menu
4: Manual operation / program override active
(display of temperature offset)
5: a) display temperature (°C / °F)
b) display time (12 h / 24 h)
6: Type of temperature displayed
Water temperature
Outside temperature
Room temperature (if RF room thermostat con-
nected)
7: Program graphic of the current day
Comfort temperature
Reduced temperature
8: Pump indicator
9: Demand indication
Heating / Cooling / Humidity function
10: Current day of the week (1 = Monday; 7 = Sunday)
11: RF reception indicator (optional).
12: a) Symbol temperature indication in °C / °F
b) Symbol AM / PM if 12 h mode
13: a) Outside temperature (°C / °F)
b) Time (12 h / 24 h)
14: Mixing valve activity indicator
O
K
160, mm
GB
5
OK
Strain relief
Fig. 4b Fig. 4c
After making the electric connections, refit the front panel (fig. 4с).
5.2 Electrical connections
All electric connections must be made by an authorized specialist according to the local regulations on electric in-
stallations. The electrical cables must not come into contact with any hot components. Because of available
space, we recommend that you unsheath the cables just after the cable clamp to facilitate connection:
Power supply
230 VAC, 50 Hz
L
N
Circulateur P1
230 VAC 50 Hz
“Mixing circuit”
Return Water temperature.
(Option)
Outside Temperature
(if wired sensor)
(Possible RF Outdoor
sensor in option)
3-Point actuator
WATTS
EVO2
Cooling output
230VAC/50Hz
or
P2 Pump
230 VAC/50 Hz
‘’ Direct circuit ‘’
L
N
Fig
. 5a
Heating output
(Heating demand for the boiler)
Free contact
N
L
N
Option :
Optional connection – temperature limiter TB (option) for
pump1 only.
The connection is factory fitted with a cable bridge. It must be removed if
connecting TB.
Logical inputs
o2
o4
oIn2
oIn1
Logical features :
-> See 5.3 & 5.5
Fig. 5
Black
Brown
Closing
Blue
Blue
Comm
on
B
rown
Black
Opening
Supplied Water temperature
Cable
c
Retainer
M
M
Standard
installation
3 point actuator
installation according to
3-ways mixing valve
installation.
(See hydraulic modul or
EVO2 leaflet)
Closing
Comm.
Opening
ARA 600
O
COM
COM
F
F
O
Black
Brown
Blue
Blue
Brown
White
NR230
O
K
O
K
Fig. 4a
GB
6
M
5.3 Hydraulic installation
The configuration is defined by the System parameter #4: INST (See Chap 7.1 System parameters setting) and induces a
different usage of the ouputs:
5.3.1
Single circuit hydraulic installation: Parameter #4 INST=Act
Security Contact thermostat
Optionnal Return sensor (Used when no RF thermostat is installed)
Supply water sensor
Main pump
Mixing 3 way valve
Boiler control
1 2
M
3 way valve signal (On in cooling mode)
Parameter #4 INST=Act Heating Mode Cooling mode
Heating demand output driving the
boiler or Stage 2 heating (if PE=yes)
Active (Contact closed) when the pump
1 is active or when there is a domestic
hot water demand or PE=Yes with Ext
Temp < PE t
Always OFF (Contact opened)
Cooling demand output (Pump 2
output) driving a 3 way On/Off valve to
choose between Heating or cooling
water
Always OFF (Contact opened)-> HOT Always ON (Contact closed)->COLD
Pump 1 output with wired TH1
thermostat
Active if the thermostat is in heating
demand
Active if the thermostat is in cooling
demand
Pump 1 output with RF TH1 thermostat Active if the thermostat is in heating
demand
Active if the thermostat is in cooling
demand
Paramter #4 INST
Act
SEP
2P.1 or 2P.2
Output Directive valve Cooling demand Pump 2
Paramter #4 INST
Act
SEP
2P.1 or 2P.2
Output Heating demand
or Stage 2 heating (if
PE=yes)
Heating demand
or Stage 2 heating (if
PE=yes)
Heating or cooling demand
or Stage 2 heating (if
PE=yes)
Paramter #4 INST
Act
SEP
2P.1 or 2P.2
Output
Pump 1
Pump 1
Pump 1
Pump2/Cooling ouput :
Heating ouput :
Pump1 output :
GB
7
5.3.2
Single circuit hydraulic installation: Parameter #4=SEP
Security Contact thermostat
Optionnal Return sensor (Used when no RF thermostat is installed)
Supply water sensor
Main pump
Mixing 3 way valve
Boiler control Water chillers signal
Heating Mode
Cooling mode
Heating demand output driving the boiler or
Stage 2 heating (if PE=yes)
Active (Contact closed) when the pump 1 is
active or when there is a domestic hot water
demand or PE=Yes with Ext Temp < PE t
Always OFF (Contact opened)
Cooling demand output driving a water chiller
Always OFF (Contact opened) Active (Contact closed) when the pump 1 is
active
Pump 1 output with wired TH1 thermostat
Active if the thermost
at is in heating demand
Active if the thermostat is in cooling demand
Pump 1 output with RF TH1 thermostat
Active if the thermostat is in heating demand
Active if the thermostat is in cooling demand
5.3.3
Dual circuit hydraulic installation: Parameter #4=2P.1 or 2P.2 with wired thermostat:
(*)
2P.1 with wired thermostats: Thermostat 2 for direct circuit is a non-reversible model (Contact when ambient temperature is below
setpoint). In cooling mode, the climatic control will automatically reverse the contact information.
2P.2 with wired thermostats: Thermostat 2 for direct circuit must be a reversible model (Contact when heat or cool demand).
2P.1 or 2P.2
with wired thermostat
Heating Mode
Cooling mode
Heating or cooling demand output informing the
heat pump or Stage 2 heating (if PE=yes)
Active (Contact closed) when the pump 1 or
pump 2 is active for heating circuits (IN1=TH1,
IN2=TH2) or PE=Yes with Ext Temp < PE t
Active (Contact closed) when the pump 1 or
pump 2 is active for cooling circuits (IN1=TH1,
IN2=TH2) or PE=Yes with Ext Temp < PE t
Pump 2 output
Active (Contact closed) if heat demand on direct
radiator circuit thermostat 2
Active (Contact closed) if cold demand on direct
radiator circuit thermostat 2 (*)
Pump 1 output Active if the wired thermostat 1 is in heating
demand
Active if the wired thermostat 1 is in cooling
demand
Security Contact thermostat
HeatPump
signal
Aquastat
Pannel heater
pump 2
Supply water sensor
WFH Main pump1
Mixing 3 way valve
1
2
HP
GB
8
M
5.3.4
Dual circuit hydraulic installation: Parameter #4=2P.1 or 2P.2 with RF thermostat:
2P.1 or 2P.2 with RF thermostats have the same behavior: In cooling mode, the climatic control will automatically reverse the
cooling demand if the thermostat 2 is not reversible
2P.1 or 2P.2 with RF thermostat Heating Mode Cooling mode
Heating or cooling demand output
informing the heat pump or Stage 2
heating (if PE=yes)
Active (Contact closed) when the pump
1 or pump 2 is active for heating
circuits
OR when there is a domestic hot water
demand through Aquastat input (IN1 or
IN2)
OR PE=Yes with Ext Temp < PE t
Active (Contact closed) when the pump
1 or pump 2 is active for cooling circuits
OR PE=Yes with Ext Temp < PE t
Pump 2 output
Active (Contact closed) if heat demand
on direct radiator circuit RF thermostat
2
Active (Contact closed) if cold demand
on direct radiator circuit RF thermostat
2
Pump 1 output Active if the RF thermostat 1 is in
heating demand and Ambiant
temperature is lower than Setpoint
+1°C
Active if the RF thermostat 1 is in
cooling demand and Ambiant
temperature is higher than Setpoint -
1°C
-
Security Contact thermostat
HeatPump
signal
Aquastat
Pannel heater
pump 2
Supply water sensor
WFH Main pump1
Mixing 3 way valve
HP ST
GB
9
4 4 2 1
L
TH Output
5.4 Room Temperature – Direct Plug In
As an option you can plug in a room thermostat to the ClimaticControl-HC. Direct plug in of a room thermostat op-
timizes the operational time of the circulation pump and even the supply flow temperature depending on the condi-
tions in the main room.
5.4.1
Mixed circuit (Water Floor), standard room thermostat, wired type
If a wired type of a standard room thermostat is plugged in and the preset room temperature is reached in
the room, the under floor circulation pump switches off after pump delay time. (PUMP: System parame-
ters: pump delay time)
WFHT-BASIC WFHT-LCD MILUX xxx
5.4.2
Direct circuit (Panel Heater), standard room thermostat, wired type
If a second circulation pump is installed and managed by the ClimaticControl-HC (Inst: System param-
eters: installation type, “2P.x”), you can install a second wired room thermostat to manage the working of
the high temperature pump.
This pump will work in the following way: If the preset room temerature is reached in the room the High
water temperature circulation pump switches off after pump delay time. (PUMP: System parameters:
pump delay time)
WFHT-BASIC WFHT-LCD MILUX xxx
< °C
Fig. 6
< °C
Fig. 7
In1 In2
4 2
In1 In2
4 2
In1 In2
4 2
4 4 2 1
TH Output
In1 In2
4 2
GB
10
5.4.3
Wireless room thermostat (Water Floor thermostat “trF1”) with WFHT-RF (BASIC, LCD or
MILUX)
WFHT-RF BASIC WFHT-RF LCD MILUX-RF-xxx MILUX-RF-Hygrostat
Only RF thermostats from the WFHT-RF series or the MILUX-RF series can
be used with an active antenna 433,92.
The MILUX-RF Hygrostat can be used only with the 433,92Mhz frequency
RF thermostat initialization to the Controller:
SYSTEM PARAMETERS MENU, section
RADIO-CONFIGURATION with RF room thermostat
fig.8
If a radio frequency room thermostat is plugged in, the flow temperature calculated on the basis of outdoor
temperature and the curve (= flow temperature preset value) is optimized depending on the main room tempera-
ture.
The offset value is calculated in the following way:
Adjustment = preset value of supplied temperature + (room temperature - actual value) х compen-
sation offset
(Compensation offset: System parameters: “tr1o” Flow temperature offset for “trF1”)
Example 1: preset calculated value of flow temp. = 35 °C; room temperature: preset value = 21 °C,
actual value = 19 °C; offset (tr1o) = 1,5
Estimation 1: 35 °C + (21 °C – 19 °C) × 1,5K =>> flow temperature increased by 3,0K to 38 °C
Example 2: preset value of flow temperature = 35 °C; room temperature: preset value = 21 °C,
actual value = 22 °C; offset (tr1o) = 1,5
Estimation 2: 35 °C + (21 °C – 22 °C) × 1,5K =>> flow temperature decreased by 1,5K to 33,5 °C
The pump will be switched off when room temperature will be 1°C upper the setting temperature
of the thermostat.
If a Milux-RF-Hygrostat is used, the program feature (See Chapter Error! Reference source not found.) is deported on the
thermostat user interface.
5.4.4
Wireless room Hygrostat (Water Floor thermostat “trF1”)
If a radio frequency room Hygrostat is plugged in, the flow temperature calculated on the basis of outdoor
temperature and the curve (= flow temperature preset value) is optimized depending on the main room
temperature. (See the previous part for more explanation)
The working mode (Heating or Cooling) of the installation could be managed by the end user directly on
the room hygrostat. (See the MILUX humidity leaflet for more explanation)
The residual humidity will be supervised by the MILUX-RF hygrostat in the house. If humidity is detected
the “Wcal“ temperature will be increased by step of 0.1°C/minute to avoid a too cold water on the hydraulic
circuit and risk of condensation in the house.
5.4.5
Wireless RF room thermostat (High temperature circuit thermostat “trF2”)
If a second circulation pump is installed and managed by the ClimaticControl-HC (Inst: System param-
eters: installation type, 2P.x), you can install a second radio frequency room thermostat to supervise the
working of the high temperature pump.
This pump will work in the following way: If the preset room temerature is reached the High water
temperature circulation pump switches off after pump delay time. (PUMP: System parameters: pump
delay time)
Note: Only a standard room thermostat could be installed on the second circuit.
Ex: WFHT-RF (BASIC, LCD or MILUX).
GB
11
5.4.6
Wireless RF outside sensor (Inst:  System parameters: Input, “OUSE”).
As an option you can plug in a wireless RF outside sensor room thermostat to the ClimaticControl-HC. This solu-
tion is very interesting in rehabilitation, to avoid wires trough the wall, in a building management with several CC-
HC, in this case only one outside sensor can be installed to manage all the building.
WIRELESS OUTSIDE
SENSOR
The wireless outside sensor can be used only with the 433,92Mhz frequency
RF outside sensor initialization to the Controller:
SYSTEM PARAMETERS MENU, section
(Inst: System parameters: “OUSE”)
fig.9
RF supervising function.
If the ClimaticControl-HC is installed with RF thermostat(s) and there is no radio signal received during more than 2
hours, a display alarm will be activated,the backlight and the small RF antenna logo radio will blink.
1.
To stop the alarm, maintain the (OK) button pressed for about 10 seconds.
2.
Check the batteries of the RF thermostat(s) or outside RF sensor. Please replace them if exhaust-
ed.
3.
Check the position in which the antenna was installed. It must be installed in vertical position.
Installation in or on a metal body can abate the power of radio transmission. Minimize the distance
to the RF thermostat.
If radio alarm is displayed:
-
Due to the wireless thermostat, the regulation will continue to work as an installation without thermostat (no com-
pensation).
-
Due to the Wireless outside sensor, the regulation will continue to work with the last value received from the out-
side sensor.
5.4.7
Inputs functions (In1 & In2)
If no wired thermostat is installed in the house, you will have the possibility to use the two available inputs of your
ClimaticControl-HC for different functions (Inst: System parameters: Input, “In1 & In2”).
1)
Input1
Inst: System parameters: Input, “HC
You could use the input 1 to connect the an external signal which give the Heating or Coling working mode
of the installation (This signal could be done directly by a reversible input).
Inst: System parameters: Input, “Aqu
1/ You could use the input 1 to connect the an imersion thermostat witch schould be placed in a storage
tank. In Heating mode this immersion thermostat will be use to switch off the circulation pump (Pump1) to
avoid cold water circulation in the circuit if the storage tank is discharged. (This solution is generally use
when solid wood burner is installed)
2/ You could also use this input to have a priority on domestic hot water.
In this case the pump of the heating circuit will be stopped to keep the priority on the domestic hot water. This
configuration is not compatible with the Efficiency Point PE=Yes as the output is used to control the heating stage
2 (See parameter #15 in Chap 7.1 System parameters setting)
Note:
-
The heating output will stay activated even if the aquastat have stopped the circulation pump.
-
To avoid problem in cooling mode, if the storage tank is filled with cold water (by heat pump...) the
aquastat function will be automatically desactivated.
Radio
alarm:
GB
12
Inst: System parameters: Input, “C_b
In case of mutizone regulation “WFHC Master RF with or without Heat&Cool function” is installed you
could use the input 1 to connect the pump relay output to swtich off the circulation pump1 in case of no
water circulation demand is asked in the house.
Note:
-
The heating output will follow the circulation demand from the pump1.
2)
Input2
Inst: System parameters: Input, “HC
You could use the input 2 to connect the an external signal which give the Heating or Coling working mode
of the installation (This signal could be done directly by a reversible input).
“HC” is only available if Input1 is set on “no or Aqua”
Inst: System parameters: Input, “Aqu
You could use the input 2 to connect the an immersion thermostat witch schould be placed in a storage
tank. In Heating mode this immersion thermostat will be use to switch off the circulation pump to avoid cold
water circulation in the circuit if the storage tank is discharged.
The immersion thermostat connected on the Input2 will manage the working of the main circula-
tion pump (Mixed circuit) if the ClimaticControl-HC drive only one pump.
In the installation with two circulations pumps, the immersion thermostat connected on the Input2
will manage the working of the 2nd circulation pump (direct circuit).
Note:
-
The heating output will stay activated even if the aquastat have stopped the circulation pump.
-
To avoid problem in cooling mode, if the storage tank is filled with cold water (by heat pump...) the
aquastat function will be automatically desactivated.
Inst: System parameters: Input, “C_b
In case of mutizone regulation “WFHC Master RF with Heat&Cool function” is installed you could use the
input 2 to connect the pump relay output to swtich off the circulation pump in case of no circulation demand
is asked in the house.
The WFHC connecting box connected on the Input2 will manage the working of the main circula-
tion pump (Mixed circuit) if the ClimaticControl-HC drive only one pump.
In the installation with two circulations pumps, the WFHC connecting box connected on the Input2
will manage the working of the 2nd circulation pump (direct circuit).
Example 1: Reversible installation with circulation pump (UFH application).
In1 Used to change the working mode of the installation, signal from Heat Pump (Inst: System parameters: Input, “HC”)
In2 used to stop the pump when D.H.W is in demand (Inst: System parameters: Input, “Aqu”)
Closed =
Cooling
Mode
Attention:
In case of the CLIMATICCONTROL-HC must be linked with the Heat pump (from the Heat /
Cool switch)
Pay attention to check the compatibility of the electrical signal before connection.
The inputs 1 or 2 (Inst: Parameter menu: In1, In2 “HC”) need a live signal “Phase L” to works
in cooling mode.
Fig. 10
> T °C
Immersion
thermostat
Heating &
Cooling signal
L
L’
2
1
C
In1 In2
4 2
GB
13
Example 2: Under floor heating installation with multizones connecting boxes.
In1 used to stop the pump when no heat demand is asked in the house. (Inst: Parameters menu: In1, “C_b”)
In2 used to stop the pump when the storage tank is empty (Inst: Parameters menu: In2, “Aqu”)
Example 2: Installation with 2 circulation pumps (Under floor heating and panel heater).
In1 used to stop the pump when the heat storage is empty (Inst: Parameters menu: In1, “Aqu”)
In2 used to stop the pump when the heat storage is empty (Inst: Parameters menu: In2, “Aqu”)
In2 :
Immersion thermostat
Use to stop the pump2
> T °C
In1:
Immersion thermostat
Use to stop the pump1
> T °C
Fig. 12
Pump signal
closed = pump On
WFHC
Aquastat
(storage tank
temperature
supervising)
> T °C
C 1 2
Fig. 11
In1 In2
4 2
In1 In2
4 2
2
C
1
2
C
1
6. Types of operating modes / Program menu
6.1 Heating and cooling switch
There are several ways to switch the system between heating and cooling.
Use parameter #0 Type (See Chap 7.1)
Use the user interface of the Climatic Control HC if parameter #0 Type=Rev (See Chap 7.1)
Use the user interface of the paired MILUX-RF HYGROSTAT if parameter #0 Type=Rev
Use Input 1 parameter #11 In1=HC or Input 2 parameter #12 In2 =HC (See Chap 5.4.7 and Chap 7.1)
6.2 Types of operating modes
Selection of the operating mode is done using the arrow keys (◄) and (►). The cursor must be positioned on the
symbol of the relevant operating mode.
COMFORT mode of operation
Unlimited operation in COMFORT mode .
The system runs in constant comfort mode. The ClimaticControl-HC adjusts the flow temperature depend-
ing on the outdoor temperature and the selected curve. No temperature setback.
The display Pos. 5 shows the current flow temperature and the outside temperature at 13 (damped val-
ue). By pressing the button (OK) the preset value of flow temperature appears for about 3 seconds at 5.
At the same time the manually selectable deviation is displayed at 13 (factory setup: 00.0 = no deviation).
Using the buttons (+) or (-) you can adjust the preset value of the flow temperature. If changed, the sym-
bol
appears on the display.
In heating mode of operation if no room thermostat is installed ( MuB: 5.3), the circulation pump is
running continuously. The pump switches off if the mixing 3 way valve is closed for the setting time
(PUMP: System parameters: pump delay time). That is the case when the room heating is sufficient
and the room thermostat closes all heating circuits by means of actuators. The same happens when the
value of flow temperature calculated by the ClimaticControl-HC becomes lower than the actual tempera-
ture value because of rising outdoor temperatures. If the actual value of the flow temperature falls below
the preset value, the pump will restart.
In this case to ensure a correct measure of the water temperature the pump will be start each 30min
for a short time to measure the real temperature of water inside the hydraulic circuit.
To ensure energy saving operating mode of the pump it could be switched by a “pump logic” of a elec-
tric connecting box. The connecting box is normally used together with room thermostats and electro-
thermic actuators. The “pump logic” is a potential free switching relay, the contact of which is closed
whenever higher temperature is demanded in any of the rooms. If all rooms are warm enough, the contact
opens and the pump turns off. ( MuB: 5.5)
If the heat generator / boiler (WE) is in temperature setback and the temperature supplied by the WE
is below the preset temperature calculated by the ClimaticControl-HC, heating mode is not available.
However if the circulation pump is actually running and the 2/3-way valve may also be opened by the 3-
point actuator because of room heating demand, the preset value of flow temperature may be exceeded
for a short period of time when the WE switches to heating mode. In this case, if a temperature limiter is
available, the pump might switch off and then pump operation will be possible only after the temperature
drops below the preset maximum temperature of the TB.
Trouble-shooting: The TB should be installed at a greater distance from the control unit. If necessary you
can set the TB to a higher temperature until the pump starts. After a few minutes of pump operation the
maximum allowable temperature set on the TB should be restored. Alternatively you can remove the TB
from the pipe for a while and leave the pump running for a few minutes. Then refit the TB again to the
pipe.
AUTOMATIC mode of operation
Automatic mode of operation using the built-in or user programs.
The ClimaticControl-HC is controlled according to the selected built-in or user program ( 6.2.).
The flow temperature is controlled depending on the outdoor temperature and the curve with room com-
pensation if RF thermostat is installed. ( 5.3.3 – 5.3.5).
The room compensation function will be different depending of the RF thermostat installed:
* With WFHTRF-BASIC or LCD (Non programmable thermostat)
The room temperature compensation will be taken in account only during Comfort period of the pro-
gram. During the Reduced period the Water temperature will follow the curve minus the temperature
setback offset.
*
With
MILUX RF (Programmable
thermostat)
The room temperature compensation will be taken in account during Comfort and Reduced period
of the program. In this case the program of the MILUX RF should be the same of the water program ad-
justed on the CC-HC to have the best optimising energy consumption (the water temperature will be re-
duced due to the CC-HC program (in ) and by the setting temperature reduced also in the room due to
the MILUX RF program.
*
With MILUX-RF HYGROSTAT (Programmable Heat and Cool thermostat with Humidity supervising)
The program will be now done on the MILUX-RF HYGROSTAT (Program made on Zone1 see the user
guide of the MILUX-RF HYGROSTAT for more explanation).
The room temperature compensation will be taken in account during Comfort and Reduced period
of the MILUX-RF HYGROSTAT program.
The Comfort and Reduced manual offsets added or subtracted to the calculated water temperature will be
always adjusted on the both working mode of the CC-HC ( 0.00°C & -10.0°C by default).
For the operation of the circulation pump please refer to the section of COMFORT mode of operation.
REDUCED TEMPERATURE mode of operation
Unlimited operation in REDUCED TEMPERATURE mode .
This is a constant mode of operation of the system. The ClimaticControl-HC adjusts the flow temperature
continuously on the basis of outdoor temperature and the selected curve and substracting the value of
temperature setback (factory setting -10.0 К in Heating mode & +3.0 К in Cooling mode).
The display indicates the current flow temperature at 5 and the outside temperature at 13. By pressing the
button (OK) the preset value for the supply flow temperature reduced by the setback in temperature is
displayed at 5 for 3 seconds. Simultaneously the reducing difference appears in 13 (without deviation =
-10.0). It can be changed by the buttons (+) or (-).
For the operation of the circulation pump please refer to the section of COMFORT mode of operation.
See the previous part for more explanation concerning the room compensation function when RF
thermostat is installed.
ABSENCE/VACATION mode of operation
Time-limited operation of REDUCED TEMPERTURE mode .
Duration can be set between 1 and 24 hours and up to a maximum of 44 days. When this period is ex-
pired the ClimaticControl-HC switches back to operating mode .
By means of the arrow keys (◄) the cursor is first moved to . Then appears on the display at 13.
The duration of absence can be changed using buttons (+) or (-).
Example:
= 1 hour; = 1 day
Both symbols and start blinking. The remaining time is displayed at 13.
To discontinue this mode of operation before time you have to set the remaining time at 13 to using
the
(
-
)
key.
STOP mode
This mode is used to switch off the system.
The device switches off the system. The ClimaticControl-HC software version is indicated on the display
for about 3 seconds and then switches off (no indications).
By pressing any of the keys the ClimaticControl-HC can be switched on.
REMARK: When the ClimaticControl-HC is in STOP mode,
In Heating mode only an Anti-freeze function can restart heat relay and circulation pump to maintain the
water temperature above 10°C.
Heat & Cool Mode
Use this mode to change the working mode of your installation, Heating or cooling mode.
This mode will be only displayed if:
-
The CC-HC is configured to manage a reversible installation (Inst: Parameters menu: Type, Rev”)
-
No MILUX-RF HYGROSTAT is installed ( 5.3.4) and configured to manage the Heat and Cool mode.
-
No CC-HC inputs (In1 or In2) have chosen for a H_C signal input. ( 5.5)
Carfull:
IF Heat pump or other system is used and not linked with the ClimaticControl-HC, pay attention to change
the working mode on it before change on the ClimaticControl-HC. Because in this case the regulation will
not work in the correct way.
TIME AND DATE – setting
In this menu you can set the actual time and date as well as the day of the week.
Using the cursor select first and then press the (OK) key.
By keys (+) or (-) set the minutes; confirm by pressing (OK).
By keys (+) or (-) set the hour; confirm by pressing (OK)
By keys (+) or (-) set the day of the week; press (OK) to confirm.
(1 = Monday; 7 = Sunday)
6.3 Program Mode
This mode will be only displayed if no MILUX-RF Hygrostat is installed ( 5.3.4)
PROGRAM menu
In this menu you choose the program of the Controller (duration of the periods for operation in reduced temperature and
heating mode), which is to be followed in operating mode . You can choose between factory set
programs from P1 to P9 ( 6.2.1.) and one of the user’s programs from U1 to U4.
First you select with the help of the cursor. The indication appears at 5. Press the (OK) key and the
indication
starts blinking. By the keys (+) or (-) now you can select the program you need and confirm it by pressing (OK).
User-defined Programs (U1 – U4)
If you choose one of the user programs from U1 to U4, you can program the REDUCED temperature and NORMAL
heating times directly. Proceed as follows:
The key (+) allow you to choose a COMFORT period at the blinking cursor time. The key (+)
allow you to choose a REDUCED period at the blinking cursor time.
At 13 the time indication blinks and day 1 is highlighted, while at 7 the time cursor blinks at 0 h on the sym- bol (heating
mode). Pressing the (-) key you can move the time cursor to the symbol (REDUCED tem- perature
mode). Then the time cursor jumps to the next hour. Thus COMFORT and REDUCED tempera- ture cycles are selected
using the (+) and (-) keys.
the programmed values for day 1 are stored. Programming other days is done using identical procedure
moving the cursor by pressing (►). When you switch over to programming the next day the program for the
previous day is saved. On completing the programming of the last day 7, the indication first switches to the
program menu , and in about 15 seconds back to .
If during programming no inputs are made within 20 seconds, indication switches first to the program menu
, and in another 15 seconds it returns to . The inputs were not stored.
Factory / built-in programs (P1 – P9)
If you select any of the factory programs from P1 to P9, you confirm it by pressing the key (ОК). Then
pressing the arrow key (◄) scroll back to the menu for selecting an operation mode (if the arrow key is not
pressed in about 15 seconds the display turns back to operating mode ).
6.3 Factory set COMFORT & REDUCED temperature times in programs P1 - P9
P1: Morning, Evening & Week-end P6: Morning, Afternoon & Week-end
P2: Morning, Midday, Evening & Week-end P7: 7h - 19h (Office)
P3: Day & Week-end P8: 8h – 19h , Saturday (Shop)
P4: Evening & Week-end P9: Week-end (Secondary House)
P5: Morning, Evening (bathroom)
Day of the week
Cursor time
The ClimaticControl-HC program operates only in mode according to the selected COMFORT and
REDUCED temperature periods.
7 System Parameter Menu
7.1 System parameters setting
This menu is used to set the most important parameters for the operation of the system.
To access this menu keep the (OK) key pressed for 10 seconds (in Comfort, Auto, Reduced modes).
The display shows as well as the preset curve (for example ).
Parameters are selected by pressing the (◄) or (►) keys.
To change the parameters press (ОК) and using (+) or (-) change them. To leave the menu goes to the parameter
End” and press the (OK) key.
SYSTEM PARAMETERS
Values Parameters description
Factory
setting
Alternative
setting
setting
_
_
_
Type
0
Type of installation
Following your choice, the list of
parameter will be different.
Ex: The Cooling “curve” parameter will
be not displayed if you choose “Hot”
installation.
Hot
Cld, rEv
Hot
For Heating installation only
CLd
For Cooling installation only
rEv
For reversible installation
Heating parameters
1
Heating curve value (see fig. 7)
supplied water T° = curve(outside T°)
0.7
0.1 to 5
2
Maximum value of flow temperature in
Heating mode
45 °C
(Lo+5°C) – 100 °C
3
Minimum value of flow temperature in
Heating mode 10 °C 1 – (Hi-1°C)
Remark: The thermostat has the priority over the water law limits on the pump and heating outputs.
Thus the 3-way valve will always follow the limits set above.
Cooling parameters
1
Cooling curve value (see fig. 7)
supplied water T° = curve(outside T°)
0.4
0.1 to 5
2
Maximum value of flow temperature in
Cooling mode
30 °C
(Lo+5°C) – 100 °C
3
Minimum value of flow temperature in
Cooling mode 15 °C 1 – (Hi-1°C)
Remark: The thermostat has the priority over the water law limits on the pump and cooling outputs.
Thus the 3-way valve will always follow the limits set above.
_
_
_
Inst
4
Configuration of the hydraulic installa-
tion
SEP
Act,
Act: installation with actuators
The “Cold output” will manage a 3
way On/Off valve to choose Heating
or cooling input.
The “Heat output” will manage the
Boiler.
See hydraulic
example
section
SEP: Installation with separate
system (Boiler and chillers)
One output for each element will be
available.
The two following parameters are
specially made for WATTMIX regula-
tion or all others applications with 2
pumps circuits, The second pump
will follow the 2nd wired thermostat,
and will be wired on the “Cold
output”.
2P.1: Panel Heaters + water floor
heating and cooling system
2P.1
The second pump for
direct temperature
circuit (panel heater)
will be stopped in
cooling mode.
No cold water in panel
heater!
2P.2: Fan coil units and Water Floor
Heating and Cooling system
2P.2
The second pump is
used to control a fan
coil circuit.
_
_
_
th
5
Thermostat selection menu:
No: Installation without thermostat
Yes: Wired thermostat(s) is installed.
rF: Wireless RF thermostat(s) is in-
stalled.
No
No, Yes, rF
The following parameter is only available if “th” parameter is set to “Yes”
_ _ _ thty
6
Wired thermostat type selection:
Std:
Standard Heat only thermostat
rEv:
Reversible Heat&Cool thermostat
Std
Std, rEv
S
YSTEM PARAMETERS
Value Parameters description
Factory
setting
Alternative
setting
setting
The following parameter is only available “th” parameter is set to “Yes” or “no” and if water sensor is mounted on
the return pipe of the hydraulic circuit.
_
_._
b
AP
7
bGAP Boost function
The incoming water temperature will
be increased by +20%* if the return
temperature is less than calculated
water temperature minus bGAP set-
ting.
Wret < Wcal – bGAP => WCal +20%*
Press on the (OK) to view the instan-
taneous value of the return sensor.
Remark: if no water return sensor is
wired then this boost function is
bypassed.
*Remark2: in Cold mode
Wret > Wcal + bGAP => WCal +20%
10.0°C
1 to 20°C
The following parameter is only available if “th” parameter is set to “rF
_
_
_
t
F1
8
RADIO-CONFIGURATION with RF thermostat for room temperature (trF1)
1.
Press the (OK) key. Using the (+) or (-) keys to set the Controller into rf init mode.
„INI thrF“ appears on the display.
2.
Set the RF thermostat into rf init mode ( MuB).
3.
If successful rf initialisation the RF thermostat sends a radio signal to the Controller.
The actual value of room temperature appears flashing on the display instead of ”INI”.
4.
The process is completed by pressing the (OK) key of the Controller.
5.
Exit the rf init mode of the RF thermostat. (
MuB).
Selecting „no thrF“ disconnects the RF thermostat from the Controller and
discontinues the room temperature plug-in function respectively.
Connection of wireless room thermostat is only possible using appropriate device.
The following parameter is only available if “th” parameter is set to “rF”
and if “inst” parameter is set to “2P.1” or “2P.2” (2 pumps mode)
_
_
_
t
F2
9
RADIO-CONFIGURATION with RF thermostat for WATTMIX system (trF2)
(2 pumps system with panel heaters or fan coils)
same radio configuration sequence as parameter “
trF1
” just above
The following parameter is only available if “th” parameter is set to “rF”
_ _ _
t
1o
10
Flow temperature offset for RF thermostat for room temperature (trF1)
See the working explanation ( 5.3.3).
SYSTEM PARAMETERS
_
_
_
in1
11
Wired Input1 selection: ( 5.5.1).
th1: the wired room thermostat should be
wired on Input1 becauseth” parameter is set
to “YES”)
no: Input1 not used (nothing wired)
no
th1
un-adjustable
no, Aqu,
HC or C_b
Aqu:
A water Aquastat contact is wired on Input1.
If over temperature is reached (contact open)
then Pump1 circulator is stopped and the
mixing valve is closed.
HC:
A Heat/Cool switching signal is wired on In-
put1 to manage the working mode of the in-
stallation. (contact between point 2 and In1 or
phase signal on In1)
Heating = no signal (open circuit )
Cooling = Phase signal (closed circuit)
The HC signal
could be done by a
heat pump.
Check the electri-
cal compatibility
before connection
C_b:
A pump signal from a connecting box is wired
on Input1 to manage the working of the
pump1.
(contact between point 2 and In1 or phase
signal on In1)
Pump ON = Phase signal (closed circuit)
Pump OFF = no signal (open circuit )
_
_
_
in2
12
Wired Input2 selection: ( 5.5.2).
th2: the wired thermostat for second pump
system should be wired on
Input2 (because “th” parameter is set to “YES
and “instis set to “2P.x”)
no: Input2 not used (nothing wired)
no
th2
not-adjustable
no, Aqu,
HC or C_b
Aqu:
A water Aquastat is wired on Input2.
If over temperature is reached (contact open)
then:
-
if “inst”=”Act or SEP”, Pump1 circulation is
stopped & mixing valve is closed.
-
if “inst”=”2P.x”, direct circuit Pump2 circula
tion is stopped
HC:
A Heat/Cool switching signal is wired on In-
put1 to manage the working mode of the in-
stallation. (contact between point 2 and In1 or
phase signal on In1)
Heating = no signal (open circuit ) Cooling =
Phase signal (closed circuit).
The HC signal
could be done by a
heat pump.
Check the
electri- cal
compatibility
before
connection
C_b:
A pump signal from a connecting box is wired
on Input1 to manage the working of the
pump1.
(contact between point 2 and In1 or phase
signal on In1)
Heating = no signal (open circuit )
Cooling = Phase signal (closed circuit).
-
if “inst”=”Act or SEP”, water floor Pump1
circulation is stopped & mixing valve is closed.
-
if “inst”=”2P.x”, direct circuit Pump2 circula-
tion is stopped.
_
_
_
OUSE
13
Outside sensor menu:
Yes: Wired outside sensor is installed.
No: Installation without outside sensor
The regulation will work like a “thermostat”
with a adjustable “Wcal” temperature injected
on the circuit.
rF: Wireless RF outside sensor is installed.
Yes
No, rF
The following parameter is only available if no outside sensor is installed and the “OUSE” parameter is set to “no”.
_ _ _ OU
t
14
Outside temperature:
This menu is used to fix the outside tempera-
ture to have the desired calculated water
temperature in accordance to the curves.
Example:
Ou t = 0°C, Curv = 1
Wcal => 40°C
You could adjust with more accuracy the
Wcal” temperature since the main screen
with the “Comfort” and “Reduced” offset.
00.0°C
-49.0°C to
50.0°C
The following parameter is only available if “OUSE” parameter is set to “rF
14
RADIO
-
CONFIGURATION with RF
sensor for outdoor temperature
Same radio configuration sequence as parameter 8 “trF1” above.
PR
PE (Efficiency
Point)
15
For an installation requiring additional external
heat (e.g. electrical back-up, boiler, heat pump).
This function can be activated in order to control a
backup stage 2 heat generator using the free
contact (5A 220V AC) "Heating output".
No Yes
If PE = No Conventional operation of the free
contact "Heating output" (See Chap 5.3)
If PE = Yes See below explanations on “PE t”
-------------
PE t
(Efficiency Point
temperature
setpoint)
15
Setting the desired PE outdoor temperature.
If PE = Yes
• If the outdoor temperature is lower than the
Efficiency Point temperature setpoint and if a
heating request occurs, then the free contact of
the “heating output” will be closed to control an
auxiliary heat generator.
• If the outdoor temperature is higher than the
Efficiency Point temperature setpoint, and if a
heating request occurs, then the free contact of
the “heating output” will remain opened, f
orbidding
to switch on a backup heat generator.
-7°C
-20°C to
+ 15.0°C
16
Temperature indication in °C or °F °C
°F
17
Time indication mode
24 hours or 12 hours
24H
12H Am/Pm
18
Side
-
track protection
YES (ac-
tive)
NO (inactive)
When YES is selected the pump and the auxiliary actuator are activated at midday 12 hrs, if they
haven’t been active for a period of 24 hours. (12h00: Pump ON 1min, 12h01: Open actuator 2min,
12:03: Close actuator 2min)
The following parameter “Pumpis only used when no RF thermostats are installed and if no inputs (In1 & In2)
are used for connecting box (C_b) and aquastat (Aqu) function.
_ _ _ PUMP
19
Pump delay time:
Time duration to switch off the pump
after the stop demand from the
wired thermostat or after complete
close of the 3 way mixing valve.
This function is also interesting to
avoid permanent ON/OFF cycle of
the pump when “PWM” thermostat is
installed.
030
For best use
the duration
should be =>
2xPWM cycle
of the thermo-
stat
001 to 060,
and above “- - -“
= infinite delay, the
pump will be ON
all the time
20
Manual mode (or test function) for valve drive respectively 2/3
-
way valve
By pressing the (+) key the valve drive opens. The display shows “OPEN“ and .
By pressing the (–) key the valve drive closes. The display shows “CLOSE“ and ▼
By pressing the (◄) or (►) key current position of the valve drive is kept. Displays “STOP“
There is a actuator security anti-short delay: when switching from “OPEN“ to “CLOSE“
or “CLOSE“ to “OPEN“, the actuator will be stopped during 15s
Floor / screed preheating
program.
0 PrH
7 PrH
_ _ _ PrH
21
The program is started by selecting „7 dry“ and runs automatically.
For a period of 3 days the flow temperature is kept at 25 °C (days 7, 6, 5). For next 4 days the flow
temperature is maintained at its preset maximum value (days 4, 3, 2, 1).
The number of the days until the end of the heating program is displayed.
Floor / screed dehumidifi-
cation program
0 drY
Default value after
“ON”
=> 13 Days
7 to 60 days
22
The program is started by selecting the desired numbers of days and runs automatically.
Example: 13 days selected: (3days rise + 7days at Hi + 3days decrease)
For a period of 3 days the flow temperature will be increased up to the “Hi” value, then the tempera-
ture will be kept at the “Hi” value during 7 days. For the last 3 days the temperature will be decreased
up to the “Lo value.
Example2: 7 days selected: (3days rise + 1day at Hi + 3days decrease)
The number of the days left until the end of the fllor dehumidification program is displayed.
23
Reset function
By keeping the (OK) key pressed for about 5 seconds all system parameters, time and day
of the week as well as user programs in are reset to the factory setting. Established
radio configuration to rf thermostats, if any, is also erased. The cursor moves to .
End
24
Press on the (OK) key to exit the installer menu and come back to the main menu in
mode.
7.2 Heating & Cooling curves
Fig. 9
7.3 Corresponding value for sensors.
To be checked with an ohmmeter with sensor unplugged.
Temperature (°C) Resistance value (Ohm) Temperature (°C) Resistance value (Ohm)
-
20°C
~94 k
40°C
~5,3 k
-
10°C
~54 k
50°C
~3,6 k
0°C
~32 k
60°C
~2,5 k
10°C
~20 k
70°C
~1,8 k
20°C
~12,5 k
80°C
~1,3 k
30°C
~8 k
8.Technical Data / Materials
Measured temperature accuracy:
0,1 °C
Operating temperature:
0
-
50 °C
Flow temperature control range:
0
-
100 °C
Regulation characteristics: Non-linear logarithmic PID control
Intelligent 3-point control (automatic detection of operating point)
Electrical protection:
Class II
IP 30
Supply voltage:
230 V (±10%), 50 Hz
Outside temperature (°C)
Outputs: pump:
Cold:
Heat:
3-point control:
5 A / 250 V relay (L, N, PE)
5 A / 250 V relay (L, N, PE)
5 A / 250 V relay (Free contact)
2 TRIACS => 75 W max.
"Maximum opening time 240 seconds; Suitable for actuators that have an
opening time below 240 Seconds”
Sensors: outside temperature:
supplied temperature:
return temperature:
CTN 10 K
at 25 °C (class II, IP55)
CTN 10 K at 25 °C (class I, IP68, no coupling)
CTN 10 K at 25 °C (class I, IP68, no supply)
Software version: _. (displayed when switched off – STOP mode).
9. TROUBLE-SHOOTING
X. TROUBLE
X.X
Possible reason Elimination
1. The display shows
1.1
at 13
Disconnected outside temperature sensor
Check whether the connection of sensor cable is correct.
Check the cable for damages.
Replace the cable or the sensor, if necessary.
1.2
at 5
Disconnected flow temperature sensor
Check whether the connection of sensor cable is correct.
Check the cable for damages.
Replace the cable or the sensor, if necessary..
2. Incorrect flow temperature
2.1
Incorrect flow setting temperature
The displayed calculated temperature is not in
accordance with the regulation curve.
Check if no offset are adjusted ( 6.1).
COMFORT and REDUCED temperature Offset.
2.2
Too high flow temperature due to incorrectly con-
nected valve drive (reverse action)
Check the connection of the valve drive ( 5.2).
2.3
Too low flow temperature due to incorrectly con-
nected valve drive (reverse action)
Check the connection of the valve drive ( 5.2).
2.4
Incorrect selected operation mode Select the correct mode of operation.
2.5
When ClimaticControl-HC operating in AUTO-
MATIC mode:
-
incorrect programming of built-in or user pro-
gram
-
incorrect setting of time / day of the week
-
Check the factory program or the user program settings
and pay attention to the correct setting of COMFORT and
REDUCED temperature periods of operation.
-
Check the setting of the time / day of the week.
3. The pumps or the valve drive does not work
3.1
Cable connections reversed. Check the electric connections ( 5.2).
3.2
Pump connected to temperature limiter.
-
Check the electric connection ( 5.2).
-
Check the maximum temperature setting of the TB.
-
Check the ambient temperature of the TB. If necessary,
change its position.
-
Check the TB operation. Replace it if necessary.
Remark:
Lock function
To prevent mistakes after installation, all critical parameters are not accessible any more after 4 hours power on. If
you want to modify these parameters, you must unplug and plug in controller. No settings are lost when unplug-
ging, or after a power failure.
After 4 hours you can still change all the other parameters to optimize your system.
PLIMF08157Ch EN
17

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Watts Climatic Control Heating and Cooling bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Watts Climatic Control Heating and Cooling in de taal/talen: Engels als bijlage per email.

De handleiding is 2.88 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info