813673
11
Verklein
Vergroot
Pagina terug
1/44
Pagina verder
Operating instructions
for the system user
VIESMANN
Wall mounted gas boiler with black/white screen
VITODENS 100-W/111-W
6167584 GB 11/2023 Please keep safe.
2
Please follow these safety instruc-
tions closely to prevent accidents
and material losses.
Safety instructions explained
Danger
This symbol warns against the risk
of injury.
!Please note
This symbol warns against the risk
of material losses and environmen-
tal pollution.
Note
Details identified by the word "Note"
contain additional information.
Target group
These operating instructions are
designed for heating system users.
This appliance can also be operated by
children aged 8 and older, as well as by
individuals with reduced physical, sen-
sory or mental faculties or those lacking
in experience and knowledge, provided
such individuals are supervised or have
been instructed in the safe use of this
appliance and any risks arising from it.
!Please note
Supervise children in the proximity
of the appliance.
Never permit children to play with
the appliance.
Cleaning and user maintenance
must never be carried out by
unsupervised children.
Safety instructions for working on the system
Connecting the appliance
The appliance may be connected and
commissioned only by authorised con-
tractors.
Only operate the appliance with suita-
ble fuels.
Observe the specified electrical con-
nection requirements.
Modifications to the existing installation
may only be carried out by authorised
specialists.
Danger
Incorrectly executed work on the
heating system can lead to life
threatening accidents.
Work on gas installations may
only be carried out by a registered
gas fitter.
Work on electrical equipment may
only be carried out by a qualified
electrician.
Safety instructions
For your safety
6167584
3
Working on the appliance
All settings and work on the appliance
must be performed as specified in
these operating instructions.
Further work on the appliance may be
carried out only by authorised contrac-
tors.
Do not open the appliance.
Do not remove casings.
Do not modify or remove attachments
or fitted accessories.
Do not open or tighten pipe connec-
tions.
Danger
Hot surfaces can cause burns.
Do not open the appliance.
Never touch the hot surfaces of
uninsulated pipes, fittings or flue
pipes.
Auxiliary components, spare and
wearing parts
!Please note
Components not tested with the
heating system may damage the
system or affect its function.
Have all installation or replacement
work carried out exclusively by your
contractor.
Safety instructions for operating the system
Damage to the appliance
Danger
Damaged equipment poses a
safety hazard.
Check the appliance for external
damage. Never start up a damaged
appliance.
If you smell gas
Danger
Escaping gas can lead to explo-
sions which may result in serious
injury.
No smoking! Prevent naked
flames and sparks. Never switch
lights or electrical appliances on
or off.
Close the gas shut-off valve.
Open windows and doors.
Evacuate any people from the
danger zone.
Notify your gas and power supply
utility and your local heating con-
tractor from outside the building.
Have the power supply to the
building shut off from a safe place
(outside the building).
Safety instructions
For your safety (cont.)
6167584
4
If you smell flue gas
Danger
Flue gas can lead to life threatening
poisoning.
Shut down the heating system.
Ventilate the installation site.
Close all doors in the living space.
If there is a fire
Danger
Fire presents a risk of burns and
explosion.
Shut down the heating system.
Close the shut-off valves in the
fuel supply lines.
Use a tested fire extinguisher,
class ABC.
If water escapes from the appliance
Danger
If water escapes from the appliance
there is a risk of electric shock.
Shut down the heating system at
the external isolator (e.g. fuse
box, domestic distribution board).
Please notify your contractor.
If the heating system develops a fault
Danger
Fault messages indicate faults in
the heating system. If faults are not
rectified, they can have life threat-
ening consequences.
Do not acknowledge fault mes-
sages several times in quick suc-
cession. Notify contractor so the
cause can be analysed and the
fault rectified.
Installation room requirements
Danger
Sealed vents result in a lack of
combustion air. This leads to incom-
plete combustion and the formation
of life threatening carbon monoxide.
Never cover or close existing vents.
Do not make any subsequent modi-
fications to the building characteris-
tics that could affect safe operation
(e.g. cable/pipework routing, clad-
ding or partitions).
Danger
Easily flammable liquids and mate-
rials (e.g. naphtha/petrol, solvents,
cleaning agents, paints or paper)
can cause deflagration and fire.
Never store or use such materials
in the boiler room or in direct prox-
imity to the heating system.
!Please note
Incorrect ambient conditions can
lead to heating system damage and
can put safe operation at risk.
Maintain the permissible ambient
temperatures as detailed in these
operating instructions.
Prevent air contamination by halo-
genated hydrocarbons (e.g. as
contained in paints, solvents or
cleaning fluids) and excessive
dust (e.g. through grinding/polish-
ing work).
Avoid continuously high humidity
levels (e.g. through continuous
drying of washing).
Safety instructions
For your safety (cont.)
6167584
5
Extractors
The operation of appliances that extract
air to the outside (cooker hoods, extrac-
tors, air conditioning units, etc.) can cre-
ate negative pressure. If the boiler is
operated at the same time, this can lead
to a reverse flow of flue gas.
Danger
The simultaneous operation of the
boiler and appliances that extract
air to the outside can result in life
threatening poisoning due to a
reverse flow of flue gas.
Take suitable steps to ensure an
adequate supply of combustion air.
If necessary, contact your contrac-
tor.
Safety instructions
For your safety (cont.)
6167584
6
1. Liability ................................................................................................................ 8
2. Introductory information Symbols ................................................................................................. 9
Terminology ........................................................................................... 9
Intended use .......................................................................................... 10
Product information ................................................................................ 10
Weather-compensated operation ....................................................... 10
Constant operation with time program ................................................ 10
Room temperature-dependent operation ........................................... 10
Individual room control with/without modulation ................................. 11
Operation ............................................................................................ 11
Permissible ambient temperatures in the installation room ................... 11
Software licences ................................................................................... 11
Commissioning ...................................................................................... 11
Your system is preset ............................................................................ 12
Energy saving tips ................................................................................. 13
Tips for greater comfort ......................................................................... 13
3. Operation Operating principles ............................................................................... 14
Status display with Lightguide ............................................................ 14
Displays ................................................................................................. 14
Standby .............................................................................................. 14
Home screen ...................................................................................... 14
Default displays .................................................................................. 14
Buttons and symbols .......................................................................... 15
Overview of main menu ......................................................................... 15
Calling up the main menu ................................................................... 16
Operating programs for central heating and DHW heating ................... 16
4. Time programs Time programs and time phases ........................................................... 17
Procedure for setting a time program .................................................... 17
Adjusting a time program for central heating . .................................... 18
Adjusting a time program for DHW heating . ...................................... 19
5. Central heating Factory settings for the temperature levels ............................................ 20
Switching on the central heating ............................................................ 20
Adjusting the temperature level for central heating . .......................... 20
Adjusting the heating curve . .............................................................. 20
Adjusting the room temperature for longer periods at home ................. 21
Switching the holiday at home function on/off .................................... 21
Saving energy during long absences ..................................................... 21
Switching the holiday program on/off .................................................. 22
Turning off central heating ..................................................................... 22
6. DHW heating Switching on DHW heating .................................................................... 23
Adjusting the temperature for DHW heating . ..................................... 23
Setting the Eco function for DHW heating ........................................ 23
Switching off DHW heating .................................................................... 23
7. Further settings Adjusting the display brightness . ....................................................... 24
Setting standby for the display . ......................................................... 24
Switching the "Lightguide" on and off . ............................................... 24
Setting the date . .............................................................................. 24
Setting the time . ................................................................................. 25
Switching internet access on or off ........................................................ 25
Establishing a WiFi connection ........................................................... 25
Switching the WiFi connection on or off .............................................. 25
Switching the wireless connection for the remote control on or off ........ 26
8. Checks Checking operating data . ................................................................... 27
Index
Index
6167584
7
Checking licences for the integrated communication module ............... 27
Calling up the license information for third party components ............ 27
Third Party Software ........................................................................... 28
Checking WiFi information . ................................................................ 28
Checking fault messages .................................................................. 29
Burner fault ..................................................................................... 29
9. Emissions test mode Switching emissions test mode on and off ........................................ 31
10. Switching on and off Switching the system off ........................................................................ 32
With frost protection monitoring .......................................................... 32
Without frost protection monitoring ..................................................... 32
Switching on the system ........................................................................ 32
11. What to do if... Rooms are too cold ................................................................................ 33
Rooms are too hot ................................................................................. 33
There is no hot water ............................................................................. 34
The DHW is too hot ............................................................................... 34
" " and the fault code are flashing ...................................................... 34
" " is shown ........................................................................................ 34
12. Maintenance Cleaning ................................................................................................. 35
Inspection and maintenance .................................................................. 35
Appliance ............................................................................................ 35
DHW cylinder ...................................................................................... 35
Safety valve (DHW cylinder) ............................................................... 35
Potable water filter (if installed) .......................................................... 35
Damaged cables / lines ......................................................................... 35
13. Appendix Terminology ........................................................................................... 36
Operating program ............................................................................. 36
Heating curve ..................................................................................... 36
Heating circuit ..................................................................................... 37
Heating circuit pump ........................................................................... 37
Room temperature .............................................................................. 38
Safety valve ........................................................................................ 38
Temperature level ............................................................................... 38
Set temperature .................................................................................. 38
Drinking water filter ............................................................................. 38
Flow temperature ................................................................................ 38
Time program ..................................................................................... 38
Information on disposal .......................................................................... 38
Disposal of packaging ........................................................................ 38
Final decommissioning and disposal of the heating system ............... 39
14. Keyword index ................................................................................................................ 40
Index
Index (cont.)
6167584
8
No liability is accepted for loss of profit, unattained
savings, or other direct or indirect consequential losses
resulting from use of the WiFi interface integrated into
the system or the corresponding internet services. No
liability is accepted for losses resulting from inappropri-
ate use.
Liability is limited to typical damage arising if a funda-
mental contractual obligation is violated through slight
negligence, the fulfilment of which is essential for
proper execution of the contract.
The limitation of liability shall not apply if the damage
was caused deliberately or through gross negligence,
or if mandatory liability applies due to product liability
legislation.
The Viessmann General Terms and Conditions apply,
which are included in each current Viessmann pricelist.
The relevant data protection regulations and terms of
use apply to the use of Viessmann apps. Viessmann
accepts no liability for push notifications and email
services, which are provided by network operators.
The terms and conditions of the respective network
operators therefore apply.
Liability
Liability
6167584
9
Symbol Meaning
Reference to other document containing
further information
1.
Step in a diagram:
The numbers correspond to the order in
which the steps are carried out.
Warning of personal injury
Warning of material losses and environ-
mental pollution
Live electrical area
Pay particular attention.
Component must audibly click into place.
or
Acoustic signal
Fit new component.
or
In conjunction with a tool: Clean the sur-
face.
Dispose of component correctly.
Dispose of component at a suitable collec-
tion point. Do not dispose of component in
domestic waste.
Terminology
To provide you with a better understanding of the func-
tions of your control unit, some terminology is
explained. This information can be found in chapter
"Terminology" in the Appendix.
Introductory information
Symbols
6167584
10
The appliance is intended solely for installation and
operation in sealed unvented heating systems that
comply with EN 12828, with due attention paid to
CECS 215-2017 and the associated installation, serv-
ice and operating instructions. It is only designed for
heating up heating water that is of potable water qual-
ity.
Intended use presupposes that a fixed installation in
conjunction with permissible, system-specific compo-
nents has been carried out.
The appliance is intended exclusively for domestic or
semi-domestic use; even users who have not had any
instruction are able to operate the appliance safely.
Commercial or industrial usage for a purpose other
than heating the building or DHW shall be deemed
inappropriate.
Any usage beyond this must be approved by the man-
ufacturer in each individual case.
Incorrect usage or operation of the appliance (e.g. the
appliance being opened by the system user) is prohibi-
ted and will result in an exclusion of liability. Incorrect
usage also occurs if the components in the heating
system are modified from their intended use (e.g. if the
flue gas and ventilation air paths are sealed).
Product information
The control unit is a boiler and heating circuit control
unit for the following operating modes:
Weather-compensated operation
Constant operation with time program
Room temperature-dependent operation:
Constant operation as option with room tempera-
ture controller
OpenTherm controller
Individual room control with/without modulation
Your heating contractor will configure the operating
mode during commissioning in accordance with your
heating system.
These instructions describe all 4 operating modes.
The setting options for room temperature-dependent
operation with an OpenTherm controller via the system
are limited:
OpenTherm controller operating instructions
Weather-compensated operation
In weather-compensated operation, the flow tempera-
ture level is controlled according to the outside temper-
ature. The lower the outside temperature, the higher
the flow temperature. This means that more heat is
provided for central heating on cold days than on
warmer days.
In weather-compensated operation, 1 heating circuit
without mixer and 1 heating circuit with mixer can be
operated with the control unit.
Constant operation with time program
In constant operation, the heat generator provides
heating water with a constant flow temperature regard-
less of the outside temperature.
Heating times are controlled by a time program.
In constant operation, 1 heating circuit without mixer
and 1 heating circuit with mixer can be operated with
the control unit.
Room temperature-dependent operation
In room temperature-dependent operation, the central
heating is switched on or off subject to the room tem-
perature. The flow temperature remains constant.
In room temperature-dependent operation, 1 heating
circuit without mixer can be operated with the control
unit.
Constant operation as option with room tempera-
ture controller
In constant mode with a room temperature controller,
the controller measures the room temperature and
compares it with the selected required room tempera-
ture. If the temperatures are different, the room tem-
perature is regulated to the required value.
Introductory information
Intended use
6167584
11
Note
The heating water temperature must be set high
enough in order to achieve the required room tempera-
ture.
Operating instructions for room temperature
controller
OpenTherm controller
In room temperature-dependent operation, the central
heating is switched on or off subject to the room tem-
perature. The flow temperature remains constant.
Individual room control with/without modulation
In individual room control mode with/without modula-
tion, specific rooms can be heated differently. The
ViCare climate sensors capture the room temperature
and compare it with the required room temperature
that has been set. If the temperatures are different, the
room temperature is regulated to the required value.
Once an internet connection has been successfully
established, operation is possible with the ViCare app.
ViCare thermostat operating instructions
or
www.vicare.info
Operation
The control unit is integrated into the heat generator
and controls all functions of your system. The control
unit is operated via a black/white screen.
A communication module is integrated in the control
unit. This allows the system to be remotely controlled
via the internet using the ViCare app (except when
operating via OpenTherm controller).
Permissible ambient temperatures in the installation room
!Please note
The appliance may develop faults if it is oper-
ated outside the specified temperature ranges.
Ensure that the specified temperature range is
maintained in the installation room.
To prevent malfunctions, ensure that the room is free
from the risk of frost, dry and heated.
Software licences
This product contains third party software, including
open source software. You are authorised to use this
third party software subject to compliance with the rel-
evant licensing terms.
Licences for the integrated communication module:
See page 27.
Commissioning
The commissioning and matching of the appliance to
local conditions and building characteristics, as well as
instructing the user in the operation of the system,
must be carried out by your contractor.
As the operator of new combustion equipment, you
may be obliged to notify the local flue gas inspector of
the installation without delay [check local regulations].
Your local flue gas inspector (where applicable) will
also provide you with information on additional activi-
ties concerning your combustion equipment (such as
regular testing, cleaning).
Introductory information
Product information (cont.)
6167584
12
Your heating system is preset at the factory and is
therefore ready for operation following commissioning
by your contractor:
Central heating in weather-compensated operation
Between 06:00 and 22:00, rooms are heated to
20 °C (standard temperature level "n2").
Between 22:00 and 06:00, rooms are heated to 3 °C
(reduced temperature level "n1", frost protection).
Central heating in constant operation
Between 06:00 and 22:00, the set flow temperature
is 60 °C (standard temperature level "n2").
Between 22:00 and 06:00, the set flow temperature
is 20 °C (reduced temperature level "n1", frost pro-
tection).
Central heating in room temperature-dependent
operation
The rooms are heated in accordance with the set-
tings on your room temperature controller or Open-
Therm controller.
DHW heating
Between 05:00 and 22:00, DHW is heated to 50 °C
(standard temperature level "n2"). Any installed
DHW circulation pump is switched on.
Between 22:00 and 05:00, the DHW cylinder is not
reheated. Any installed DHW circulation pump is
switched off.
Note
Any DHW heating started before 22:00 remains on
until the set DHW temperature has been reached.
Frost protection
Your heat generator and DHW cylinder (if installed)
are protected against frost.
The frost protection function is only possible when an
outside temperature sensor is connected. Frost pro-
tection function is active at outside temperatures
below 5 °C. The burner is switched on and the boiler
water temperature is held at 20 °C.
Wintertime/summertime changeover
This changeover is automatic.
Date and time
The date and time were set by your heating contrac-
tor.
You can change the settings at any time to suit your
individual requirements.
Power failure
All settings are retained if there is a power failure.
Introductory information
Your system is preset
6167584
13
Saving energy when using central heating
Do not overheat your home. Every degree of room
temperature reduction saves up to 6 % on your heat-
ing bills.
Weather-compensated operation and room tempera-
ture-dependent operation:
Never set your standard room temperature (standard
temperature level "n2") higher than 20 °C.
Heat your home to the reduced temperature at night
or during regular absences:
Weather-compensated operation:
Reduced room temperature.
Continuous operation and room temperature-
dependent operation:
Reduced flow temperature.
In constant operation, adjust the time program for
central heating: See page 18.
In room temperature-dependent operation, time pro-
grams for central heating can only be adjusted at the
room temperature controller or OpenTherm control-
ler.
Operating instructions for the room tempera-
ture controller or OpenTherm controller
Saving energy on DHW heating
At night or during regular absences, heat the DHW to a
lower temperature. To do so, adjust the time program
for DHW heating: See page 19.
For additional energy saving functions, please contact
your contractor.
Tips for greater comfort
More comfort in your home
Set your individual preferred temperature: See
page 20.
Adjust the time program for your heating circuits so
that your individual preferred temperature is auto-
matically reached if you are present: See page 18.
In room temperature-dependent operation, time pro-
grams for central heating can only be adjusted at the
room temperature controller or OpenTherm control-
ler. See the operating instructions for the controller.
Only for weather-compensated operation:
Adjust the heating curves so that your home is
heated with your individual preferred temperature all
year round: See page 20.
Sufficient DHW heating for your needs
Adjust the time program for DHW heating so that there
is always sufficient hot water in accordance with your
habitual routines: See page 19.
Example: You need more DHW in the morning than in
the daytime.
Introductory information
Energy saving tips
6167584
14
All your system settings can be made via the program-
ming unit, remote control units or other room tempera-
ture control devices and the ViCare app.
Touchscreen operation
The programming unit is equipped with a display. To
input settings and check information, tap the on-screen
buttons.
Operation via remote control units or room temper-
ature control devices
Separate operating instructions
Operation via ViCare app
The ViCare app allows you to operate your system via
a mobile device, e.g. smartphone.
Available functions depend on the system equipment
e.g. with/without ViCare components for individual
room control.
Check the following system requirements for operation
via the app:
Viessmann system that can be connected via Vito-
connect or an integrated communications module.
WiFi connection from router for control with internet
access
Smartphone or tablet with operating system:
iOS
Android
Further information on using the ViCare app: See
www.vicare.info.
Status display with Lightguide
Depending on the heat generator, a white spot (Light-
guide) is shown on the display.
Meaning of the display:
Lightguide pulsates slowly:
Display is in standby mode.
Lightguide flashes quickly:
There is a fault in the system.
Note
You can switch off the Lightguide. See page 24.
Displays
Standby
The display backlighting is switched off after approx.
2 minutes.
You can deactivate standby mode: See page 24.
Home screen
After switching on or activating the control unit the
home screen is shown.
In the delivered condition, heating circuit 1 is shown
as the home screen.
Call up the home screen:
Standby is active:
Tap any button.
From anywhere in the menu:
Tap until the home screen is shown.
Default displays
On the home screen, you can call up the various
default displays to see the status of the most important
functions.
Default screen displays:
In weather-compensated mode: Set room temper-
ature for heating circuit 1
In constant operation: Flow temperature for heat-
ing circuit 1
In weather-compensated mode: Set room temper-
ature for heating circuit 2
Operation
Operating principles
6167584
15
In constant operation: Flow temperature for heat-
ing circuit 2
DHW temperature
System pressure
DHW ECO function (with combi boilers)
Current fault message (if a fault is present)
To call up the default displays:
1. Tap repeatedly until the home screen is shown.
2. Tap to switch between the default displays.
Buttons and symbols
Fig. 1
AFunction area
BNavigation area
Buttons and symbols in navigation area B
Calls up the main menu.
Or
Takes you back to the home screen.
Scrolls through the menu or adjusts values.
"OK" You confirm the operation.
Buttons and symbols in function area A
Note
What buttons and symbols are available depends on
the operating mode: Weather-compensated opera-
tion, constant operation, room temperature-depend-
ent operation
These symbols are not always displayed, but appear
subject to the system version and the operating sta-
tus.
Symbols
Heating circuit 1
Heating circuit 2
DHW temperature
System pressure
DHW ECO function
Service menu active
Fault display active
Burner status active
WiFi connection
Reduced temperature level active
Emissions test mode
Burner reset
Overview of main menu
In the main menu, you can check and adjust all of the
settings for the appliance's range of functions.
Available menus:
" . " Temperature level
" . " Information
" . " Heating curve
" . " Time program for central heating and DHW
heating
" . " Display brightness
" . " Display standby mode
" . " Internet access and information
" . " Low power radio access and information
" . " Lightguide
" . " Date
" . " Time
Operation
Displays (cont.)
6167584
16
Calling up the main menu
Tap the following buttons:
1. to call up the main menu.
2. for the required menu
3. "OK" to confirm
Operating programs for central heating and DHW heating
Note
The operating programs for central heating and DHW
heating can be set separately or all together for the
entire system.
Operating program Function
Room heating
Heating circuit 1 and/or heating circuit 2
is active.
The rooms of the selected heating circuit are heated in accordance
with the specified room temperature or flow temperature and the
time program: See chapter "Central heating".
Note
In room temperature-dependent operation, a time program for cen-
tral heating can only be set at the room temperature controller or
OpenTherm controller: See the operating instructions for the room
temperature controller or OpenTherm controller.
Heating circuit 1 and/or heating circuit 2
is not active.
No room heating
Frost protection for the heat generator is active.
DHW heating
DHW is active. DHW is heated in accordance with the specified DHW temperature
and time program: See chapter "DHW heating".
DHW is not active. No DHW heating
Frost protection for the DHW cylinder is active.
System
The entire system is switched on. The rooms are heated in accordance with the specified room
temperature or flow temperature and the time program: See
chapter "Central heating".
Note
In room temperature-dependent operation, a time program for
central heating can only be set at the room temperature control-
ler: See the operating instructions for the room temperature con-
troller.
DHW is heated in accordance with the specified DHW tempera-
ture and time program: See chapter "DHW heating".
The entire system is switched off. No room heating
No DHW heating
Frost protection for the heat generator and the DHW cylinder is
active.
Operation
Overview of main menu (cont.)
6167584
17
Note
In room temperature-controlled operation, you set the
time programs via the room temperature controller or
OpenTherm controller.
Operating instructions for the room temperature
controller or OpenTherm controller
In the time programs you determine what your heating
system should do at what time. To do so, divide the
day into sections. These are called time phases. Dif-
ferent temperature levels are active within and outside
these time phases.
You can set up a time program for the following functions:
Function Temperature level
Within the time phase Outside the time phase
Room heating Weather-compensated operation:
Your rooms are heated with standard room
temperature or comfort room temperature.
Your rooms are heated with reduced room
temperature.
Constant operation:
Your rooms are heated with standard flow
temperature or comfort flow temperature.
Your rooms are heated with reduced flow
temperature.
Room temperature-dependent operation:
A time program for central heating can only be set at the room temperature controller.
Operating instructions for room temperature controller
DHW heating DHW heating is switched on.
The water in the DHW cylinder is heated to
the set DHW temperature.
DHW heating is switched off.
Procedure for setting a time program
The following explains how to input the settings for a
time program. The specifics of the individual time pro-
grams can be found in the relevant chapters.
In the time programs you determine what your heating
system should do at what time. To do so, divide the
day into sections. These are called time phases. Dif-
ferent temperature levels are active within and outside
these time phases.
Note
In operating modes "constant operation with room tem-
perature controller" and "OpenTherm controller", it is
not possible to adjust a time program for central heat-
ing and DHW heating.
Time programs
Time programs and time phases
6167584
18
Fig. 2
Adjusting a time program for central heating .
The time program for central heating is adjusted under
. .
The time phase for central heating is factory-set to
06:00 to 22:00.
Tap the following buttons:
1. for 4 s to enter the main menu.
2. / . should be selected.
3. "OK" to confirm
4. / or should be selected.
5. "OK" to confirm
6. / for the required period
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
7. "OK" to confirm
8. confirm with "OK" to add time phases
and/or .
or
/ and confirm with "OK" to edit the time of
the respective time phase.
9. and confirm with "OK" to modify the time
of the time phase.
or
and confirm with "OK" to delete the time
phase.
10. / to select the start time.
11. "OK" to confirm
12. / to select the end time.
13. "OK" to confirm
Time programs
Procedure for setting a time program (cont.)
6167584
19
14. and confirm with "OK" to set the "Stand-
ard" temperature level.
or
and confirm with "OK" to set the "Com-
fort" temperature level.
15. repeatedly to exit the menu.
Note
Outside the time program with temperature level or
, the reduced temperature level is active. The
reduced temperature level is shown as on the
home screen.
Adjusting a time program for DHW heating .
The time phase for DHW heating is factory-set to
05:00 to 22:00.
Adjust the time program to suit your needs.
Tap the following buttons:
1. for 4 s to enter the main menu.
2. / . should be selected.
3. "OK" to confirm
4. / should be selected.
5. "OK" to confirm
6. / for a time period
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
7. "OK" to confirm
8. Confirm with "OK" to add time phase .
or
Confirm with "OK" to edit the time of the
time phase.
9. and confirm with "OK" to modify the time
of the time phase.
or
and confirm with "OK" to delete the time
phase.
10. / to select the start time
11. "OK" to confirm
12. / to select the end time
13. "OK" to confirm
14. repeatedly to exit the menu.
Time programs
Adjusting a time program for central heating . (cont.)
6167584
20
Weather-compensated operation
Standard room temperature: 20 °C
Reduced room temperature: 3 °C
Comfort room temperature: 20 °C
Constant operation and room temperature-depend-
ent operation
Standard flow temperature: 60 °C
Reduced flow temperature: 20 °C
Only for constant operation
Comfort flow temperature: 70 °C
Constant operation and room temperature-depend-
ent operation with room temperature controller
Only change the set values for the flow temperature if
the heat supply for central heating is insufficient.
Room temperature-dependent operation with
OpenTherm controller
In this operating mode, it is not possible to adjust tem-
peratures via the control unit.
See the OpenTherm controller operating instructions.
Switching on the central heating
Tap the following buttons:
1. repeatedly to switch between the default dis-
plays until appears.
2. until the set temperature appears.
3. "OK" to confirm.
4. to exit the menu.
Adjusting the temperature level for central heating .
Adjust the temperature level for central heating to suit
your needs.
Note
With room temperature-dependent operation, you
adjust the set room temperature on your room temper-
ature controller.
Fig. 3
Tap the following buttons:
1. for 4 s to enter the main menu.
2. / . should be selected.
3. "OK" to confirm
4. / or should be selected.
5. "OK" to confirm
6. / Select the temperature level:
Reduced level
Standard level
Comfort level
7. "OK" to confirm
8. / to select the set value.
9. "OK" to confirm
10. repeatedly to exit the menu.
Note
The set value for the current temperature level and the
set flow temperature can be set directly via the home
screen for the respective heating circuit with .
Adjusting the heating curve .
The heating curve can only be adjusted in weather-
compensated operation.
By setting the heating curve, you influence the flow
temperature provided by the heat generator.
So that your rooms are heated optimally at any outside
temperature, you can adjust the heating curve slope
and level.
Central heating
Factory settings for the temperature levels
6167584
21
Factory setting:
Slope: 1
Level: 3
Fig. 4
Tap the following buttons:
1. for 4 s to enter the main menu.
2. / . should be selected.
3. "OK" to confirm
4. / or should be selected.
5. "OK" to confirm
6. / to set the value for the slope.
7. "OK" to confirm
8. / to set the value for the level.
9. "OK" to confirm
10. repeatedly to exit the menu.
Adjusting the room temperature for longer periods at home
If you are continuously at home for one or more days
but do not want to change the time program, select the
"holiday at home" function, e.g. for public holidays or
when the children are on school holidays.
The "holiday at home" function has the following
effects:
The room temperature during the periods between
the set time phases is raised to the set value of the
first time phase of the day: From reduced room tem-
perature to standard room temperature or comfort
room temperature
If no time phase is active before 00:00, your rooms
are heated to the reduced room temperature until the
next time phase becomes active.
DHW heating is active.
The "holiday at home" function starts and ends
according to the set times for the start date and end
date.
As long as the "holiday at home" function is switched
on, the default display shows "E 3".
Switching the holiday at home function on/off
You can switch the "holiday at home" function on and
off via the ViCare app.
While the function is switched on, "E 3" is shown on
the display.
Saving energy during long absences
To save energy during long periods of absence, select
the "holiday program".
The holiday program has the following effects:
Room heating:
For heating circuits in the heating operating pro-
gram:
The rooms are heated to the set reduced room
temperature.
For heating circuits in standby mode:
No room heating: Frost protection for the heat gen-
erator and the DHW cylinder is active.
DHW heating:
No DHW heating: Frost protection for the DHW cylin-
der is active.
Central heating
Adjusting the heating curve . (cont.)
6167584
22
The holiday program starts at 00:00 on the first day
of your holiday and ends at 23:59 on the final day.
As long as the "holiday program" function is switched
on, the default display shows "E 3".
Switching the holiday program on/off
The "holiday program" function is switched on and off
via the ViCare app.
While the function is switched on, the display shows
"E 3".
Turning off central heating
You do not want to heat your rooms but you want to
have DHW available (summer mode).
Note
If heating circuit 2 was configured on the heat gen-
erator and you want to switch it off, move through the
default display until is illuminated.
Tap the following buttons:
1. repeatedly to switch between the default dis-
plays until appears.
2. until appears.
3. "OK" to confirm.
4. to exit the menu.
Note
To prevent the circulation pump from seizing, it
briefly starts every 24 hours.
Boiler frost protection is enabled.
Central heating
Saving energy during long absences (cont.)
6167584
23
You want to have DHW available.
Tap the following buttons:
1. repeatedly to switch between the default dis-
plays until appears.
2. for 4 s until appears.
3. "OK" to confirm.
4. to exit the menu.
Adjusting the temperature for DHW heating .
Factory settings: 50 °C
Adjust the DHW temperature to suit your needs.
Note
For reasons of good hygiene, you should not set the
DHW temperature lower than 50 °C.
Tap the following buttons:
1. for 4 s to enter the main menu.
2. . should be selected
3. "OK" to confirm
4. / should be selected.
5. "OK" to confirm
6. / Set a value.
7. "OK" to confirm
8. repeatedly to exit the menu.
Setting the Eco function for DHW heating
Note
This function is only possible in conjunction with an
instantaneous water heater (combi boiler).
The ECO function does not provide you with instant
hot water; the water is not heated until it is drawn off.
You can set the Eco function via default display .
Tap the following buttons:
1. repeatedly to switch between the default
displays until appears.
2. /
3. "OK" to confirm
If is illuminated on the far left, you have
successfully switched on the Eco func-
tion.
Switching off DHW heating
You do not want to have DHW available.
Tap the following buttons:
1. repeatedly to switch between the default dis-
plays until appears.
2. for 4 s until appears.
3. "OK" to confirm.
4. to exit the menu.
DHW heating
Switching on DHW heating
6167584
24
Set the right brightness for your display.
Tap the following buttons:
1. for 4 s to enter the main menu.
2. / . should be selected.
3. "OK" to confirm
4. / Set a value.
5. "OK" to confirm
6. repeatedly to exit the menu.
Setting standby for the display .
Activate or deactivate standby.
Tap the following buttons:
1. for 4 s to enter the main menu.
2. / . should be selected.
3. "OK" to confirm
4. / or should be selected.
The display is always on.
The display enters standby mode
after 2 minutes.
5. "OK" to confirm
6. repeatedly to exit the menu.
Switching the "Lightguide" on and off .
Depending on the heat generator, a white spot (Light-
guide) is shown on the display during operation.
In the delivered condition, the Lightguide is switched
on. You can switch off the Lightguide.
Tap the following buttons:
1. for 4 s to enter the main menu.
2. / . should be selected.
3. "OK" to confirm
4. / or should be selected.
Confirm your selection with "OK".
5. repeatedly to exit the menu.
Meaning of the display:
Lightguide pulsates slowly:
Display is in standby mode.
Lightguide flashes quickly:
There is a fault in the system.
Note
Faults are shown by flashing lights even if the Light-
guide is switched off.
Setting the date .
The date is preset by the heating contractor. Change
the date if necessary.
Tap the following buttons:
1. for 4 s to enter the main menu.
2. / . . should be selected.
3. "OK" to confirm
4. / to select the day.
5. "OK" to confirm
6. / to select the month.
7. "OK" to confirm
8. / to select the year.
9. "OK" to confirm
Further settings
Adjusting the display brightness .
6167584
25
10. repeatedly to exit the menu.
Setting the time .
The time is preset by the heating contractor. Change
the time if necessary.
Tap the following buttons:
1. for 4 s to enter the main menu.
2. / . . should be selected.
3. "OK" to confirm
4. / to select the hour.
5. "OK" to confirm
6. / to select the minutes.
7. "OK" to confirm
8. repeatedly to exit the menu.
Switching internet access on or off
You can control your system remotely via the internet
using an app. To do this, establish an internet connec-
tion via WiFi (2.4 gigahertz): See the following chapter.
The required credentials for internet access to the con-
trol unit via app can be found on the adjacent label:
Establishing a WiFi connection
You will need the ViCare app on your mobile device to
establish an internet connection with the heat genera-
tor.
Tap the following buttons:
1. "OK" for 4 s. The display will show a rotating bar
until the WiFi symbol is illuminated on the far left.
2. Start the ViCare app and follow the instructions in
the app.
flashes. The connection to the local
network is being estab-
lished.
is dimly illuminated. The connection to the local
network has been estab-
lished.
is brightly illuminated. The connection to the server
has been established.
Fault while establishing the connection
"E10" Connection to the home network cannot be
established.
Note
If "E10" appears on the display, check the con-
nection to the router and whether the network
password is correct.
"E12" Connection to the server cannot be estab-
lished.
Note
If "E12" appears on the display, re-establish
the connection at a later time.
Switching the WiFi connection on or off
Switch the WiFi connection on and off as required.
Further settings
Setting the date . (cont.)
6167584
26
Tap the following buttons:
1. repeatedly to access the main menu.
2. + "OK" Press and hold for 4 s to switch the
WiFi connection on or off.
In the display you will see:
to indicate the WiFi connection is
switched on
or
to indicate the WiFi connection is
switched off
3. repeatedly to exit the menu.
Switching the wireless connection for the remote control on or off
With weather-compensated operation, you can con-
nect your remote control to the control unit for wireless
data transfer via low power radio.
Fig. 5
Tap the following buttons:
1. for 4 s to enter the main menu.
2. / . should be selected.
Note
Menu point P.8 is not shown if a low
power radio component is already con-
nected to the appliance.
3. "OK" to confirm
4. / Switch low power radio on with or off
with .
5. "OK" to confirm
6. repeatedly to exit the menu.
Further settings
Switching internet access on or off (cont.)
6167584
27
Depending on the system equipment level and the set-
tings made, you can check current system data, e.g.
temperatures.
Fig. 6
Tap the following buttons:
1. for 4 s to enter the main menu.
2. / . should be selected.
3. "OK" to confirm
4. / . ... . should be selected.
. Outside temperature
. Heat generator flow temperature
. Primary circuit pump speed in %
. Flue gas temperature
. Burner hours run
. Burner output
. 3-way valve position
Heating
Middle position (if installed)
DHW
. Serial number of heat generator
As only 3 digits can be displayed at
one time, tap on / to see
more digits.
. Heating circuit 1 flow temperature
. Heating circuit 2 flow temperature
. DHW temperature
5. "OK" to confirm
6. repeatedly to exit the menu.
Checking licences for the integrated communication module
Switch on the WiFi to call up online legal information,
such as open source licences:
On the home screen, press OK for approx. 4 s.
Calling up the license information for third party components
Requirement: Access point must be switched on.
Tap the following buttons:
1. Call up the WiFi settings on your mobile device.
2. Connect your mobile device to the WiFi
"Viessmann-<xxxx>".
A password prompt will be displayed.
3. Enter the WPA2 network key as the password for
the "Viessmann-<xxxx>" WiFi.
Note
The WPA2 network key can be found on the label:
See chapter "Switching internet access on or off".
4. With your connected mobile device, open http://
192.168.0.1 in your internet browser.
Checks
Checking operating data .
6167584
28
5. Follow the link "Third party Components Licen-
ces".
Third Party Software
1 Overview
This product contains third party software, including
open source software. You are entitled to use this third
party software in compliance with the respective
license conditions as provided in this document.
A list of used third party software components and of
license texts can be accessed by connecting your
boiler, like it is mentioned in the manual.
2 Acknowledgements
Linux® is the registered trademark of Linus Torvalds in
the U.S. and other countries. This product includes
software developed by the OpenSSL Project for use in
the OpenSSL Toolkit (http://www.openssl.org/). This
product includes cryptographic software written by Eric
Young (eay@cryptsoft.com) and software written by
Tim Hudson (tjh@cryptsoft.com).
3 Disclaimer
The open source software contained in this product is
distributed WITHOUT ANY WARRANTY; without even
the implied warranty of MERCHANTABILITY or FIT-
NESS FOR A PARTICULAR PURPOSE. The single
licenses may contain more details on a limitation of
warranty or liability.
4 How to Obtain Source Code
The software included in this product may contain
copyrighted software that is licensed under a license
requiring us to provide the source code of that soft-
ware, such as the GPL or LGPL. To obtain the com-
plete corresponding source code for such copyrighted
software please contact us via the contact information
provided in section 5 below indicating the built number
you will find in the licensing information section, which
can be accessed as outlined in this document. This
offer is not limited in time and valid to anyone in receipt
of this information.
5 Contact Information
Viessmann Climate Solutions SE
35108 Allendorf
Germany
Fax +49 64 52 70-27 80
Phone +49 64 52 70-0
open-source-software-support@viessmann.com
www.viessmann.de
Checking WiFi information .
You can check the current status of your WiFi connec-
tion, such as the signal strength.
Tap the following buttons:
1. for 4 s to enter the main menu.
2. / . should be selected.
Checks
Checking licences for the integrated… (cont.)
6167584
29
3. "OK" to confirm
One of the following statuses is dis-
played:
WiFi off
Signal strength very weak
Signal strength weak
Signal strength good
Signal strength very good
Connection is established.
No data transfer
Communication error
Offline
Access point mode; the heat gener-
ator can be connected to ViCare,
for example.
4. "OK" to confirm
5. repeatedly to exit the menu.
Checking fault messages
If your heating system has a fault, and the fault
code will be displayed.
Danger
If faults are not rectified, they can have life
threatening consequences.
Do not acknowledge fault messages several
times in quick succession. Please notify your
contractor if a fault occurs. Your contractor will
be able to analyse the cause and rectify the
fault.
If a fault is active and is shown on the display, you can
confirm with OK and return to the home screen.
To call up this fault later, follow the steps below.
Note
If you have connected a message facility to alert you
to fault messages (e.g. a buzzer), this is deactivated
when the fault message is acknowledged.
If troubleshooting cannot be carried out until a later
date, the fault message will be displayed again the
following day at 07:00. The message facility is
switched on again.
Tap the following buttons:
1. for 4 s to enter the main menu.
2. / should be selected.
3. "OK" to confirm
4. / to select fault message to .
5. "OK" to confirm
6. / to call up further details about the fault
code.
Note
Up to 5 fault messages can be displayed.
7. repeatedly to exit the menu.
If flashes and appears on the display, the burner
is locked out. To reset the burner, see next chapter
"Burner fault".
Burner fault
The display shows and flashes.
A fault has caused the burner to lock out. You can
reset it.
Note
The burner fault display can be closed for the time
being by pressing for 4 s. You can open the fault
later by pressing simultaneously.
Tap the following buttons:
1. / to see the fault number.
2. Make a note of the fault number.
This enables the contractor to be better prepared
and may save you unnecessary travelling costs.
Checks
Checking WiFi information . (cont.)
6167584
30
3. Press and for approx. 4 s.
A rotating bar will appear on the display. This indi-
cates that the resetting process has been started.
If the fault no longer exists, the home screen will
appear.
Notify your heating contractor if the fault
recurs.
Checks
Checking fault messages (cont.)
6167584
31
Emissions test mode for testing flue gas must only be
activated by your flue gas inspector during the annual
inspection.
If possible, have the emissions test carried out during
the heating season.
Tap the following buttons:
and for 4 s.
A rotating bar is shown on the display. The process
has been started. A check runs in the background to
determine whether there is sufficient heat transfer.
As soon as emissions test mode is active, the heat
generator flow temperature appears on the display.
Note
If "- - -" flashes on the display 3 times and then the
home screen is shown, emissions test mode is not
possible due to a low flow rate or low heat draw-off.
Note
Emissions test mode ends automatically after
30 minutes.
Press to manually end emissions test mode.
Emissions test mode
Switching emissions test mode on and off
6167584
32
With frost protection monitoring
If you do not wish to use your heat generator for sev-
eral days you can switch it off.
Set the operating mode to OFF.
Frost protection monitoring is active for the heat gener-
ator and the DHW cylinder.
Note
For frost protection for the entire heating system, see
the operating instructions for the room temperature
controller.
Without frost protection monitoring
Shut down your heating system completely if it will not
be needed for long periods of time (several months).
We recommend you contact your local heating con-
tractor if you are planning to take your heating system
out of use for long periods. Your heating contractor can
then take suitable steps such as frost protection for the
system or heating surface preservation as required.
1. Close the gas shut-off valve. Secure to prevent
unauthorised opening.
2. Turn off the ON/OFF switch.
The power to the system is now at zero volt.
Note that the system is no longer protected
against frost.
Switching on the system
Ask your contractor about the following:
Required system pressure
Position of ventilation apertures in the installation
room, if applicable
1. Open the gas shut-off valve.
2. Check whether the power supply to your system is
switched on, e.g. at a separate MCB/fuse or mains
isolator.
Note
The power supply to the system was switched on
by your heating contractor during commissioning. If
possible, do not interrupt the power supply, even
when the system is in standby mode.
3. Turn on the ON/OFF switch.
After a short while, the home screen is shown on
the display.
The Lightguide is illuminated constantly.
Your system and, if installed, remote control units
are ready for operation.
4. Check the system pressure:
until the pressure gauge symbol lights up.
If the pressure shown is below 1.0 bar:
Please top up with water or notify your heating
contractor.
Switching on and off
Switching the system off
6167584
33
Cause Remedy
The heating system is off. Turn on the ON/OFF switch.
Switch ON the mains isolator if installed (outside the
boiler room).
Reset the MCB in the power distribution board (main
domestic MCB).
Control unit or room temperature controller is not set
correctly.
Operation with room temperature controller:
Set a higher flow temperature.
Weather-compensated operation:
Set a higher room temperature.
Only when operating with DHW heating:
Priority for DHW heating is active (" " is displayed).
Wait until the DHW cylinder has been heated up (" "
disappears).
In the case of operation with an instantaneous water
heater, stop DHW draw-off.
No fuel. With LPG:
Check the fuel reserves and re-order if required.
With natural gas:
Open the gas shut-off valve. If necessary, check with
your gas supply utility.
" " is shown on the display. Notify your heating contractor of the fault code shown.
" " and the fault code flash on the display. The burner
does not start.
Reset the burner.
Notify your heating contractor if the fault recurs.
Danger
If faults are not rectified, they can have life
threatening consequences.
Do not reset the burner several times in quick
succession. Notify your heating contractor if a
fault recurs. Your heating contractor will be able
to analyse the cause and rectify the fault.
Air in the heating system Bleed radiators.
The burner is switched off. Blockage in the ventilation
air supply or flue system
Notify your local heating contractor.
The "holiday program" function is switched on via the
ViCare app.
"E 3" is shown on the display.
Use the ViCare app to check whether the "holiday pro-
gram" function is switched on, change it if necessary, or
switch it off.
Rooms are too hot
Cause Remedy
Control unit or room temperature controller is not set
correctly.
Check and correct the room temperature or flow tem-
perature.
Operating instructions for room temperature con-
troller
" " is shown on the display. Notify your heating contractor of the fault code.
The "holiday at home" function is switched on via the
ViCare app.
"E 3" is shown on the display.
Use the ViCare app to check whether the "holiday at
home" function is switched on, change it if necessary,
or switch it off.
What to do if...
Rooms are too cold
6167584
34
Cause Remedy
The heating system is switched off. Turn on the ON/OFF switch.
Switch ON the mains isolator if installed (outside the
boiler room).
Reset the MCB in the power distribution board (main
domestic MCB).
Control unit is not set correctly. Check and correct the DHW temperature.
No fuel. With LPG:
Check the fuel reserves and re-order if required.
With natural gas:
Open the gas shut-off valve. If necessary, check with
your gas supply utility.
" " is shown on the display. Notify your heating contractor of the fault code shown.
" " and the fault code flash on the display. The burner
does not start.
Reset the burner fault: See page 29.
Notify your heating contractor if the fault recurs.
Danger
If faults are not rectified, they can have life
threatening consequences.
Do not reset the burner fault several times in
quick succession. Notify your heating contractor
if a fault recurs. Your heating contractor will be
able to analyse the cause and rectify the fault.
"Filter strainer" dirty
(Gas condensing combi boilers only).
Have the filter strainer checked/replaced by your con-
tractor.
The DHW is too hot
Cause Remedy
The control unit is not set correctly. Check and correct the DHW temperature.
" " and the fault code are flashing
Cause Remedy
The burner does not start. Reset the burner fault: See page 29.
Notify your heating contractor if the fault recurs.
Danger
If faults are not rectified, they can have life
threatening consequences.
Do not reset the burner fault several times in
quick succession. Notify your heating contractor
if a fault recurs. Your heating contractor will be
able to analyse the cause and rectify the fault.
" " is shown
Cause Remedy
Heating system fault Notify your heating contractor of the fault code.
What to do if...
There is no hot water
6167584
35
The appliances can be cleaned with a commercially
available domestic cleaning agent (non-scouring).
Clean the surface of the programming unit with a
microfibre cloth.
Inspection and maintenance
The inspection and maintenance of a heating system
is prescribed by the Buildings Energy Act [Germany]
and the DIN 4755, DVGW-TRGI 2018 and
DIN EN 806-5 standards.
Regular maintenance ensures trouble-free, energy effi-
cient, environmentally responsible and safe heating
operation. Your heating system must be serviced by an
authorised contractor at least every 2 years. For this, it
is best to arrange an inspection and maintenance con-
tract with your local contractor.
Appliance
Increased contamination raises the flue gas tempera-
ture and thereby increases energy losses. We recom-
mend the appliance is cleaned annually.
DHW cylinder
Standard EN 806-5 specifies that maintenance and
cleaning should be carried out no later than 2 years
after commissioning and as required thereafter.
Only a qualified contractor should clean the inside of
the DHW cylinder and the DHW connections.
If any water treatment equipment (e.g. a sluice or
injection system) is installed in the cold water supply of
the DHW cylinder, ensure this is refilled in good time.
For this, observe the manufacturer's instructions.
Safety valve (DHW cylinder)
The function of the safety valve must be checked
every six months by the user or a contractor through
venting (see valve manufacturer's instructions). The
valve seat may become contaminated.
Water may drip from the safety valve during a heat-up
process. The outlet is open to the atmosphere.
!Please note
Overpressure can cause damage.
Do not close the safety valve.
Potable water filter (if installed)
To maintain high hygienic standards, proceed as fol-
lows:
Replace filter element on non-back flushing filters
every six months (visual inspection every
two months).
On back flushing filters, back flush every
two months.
Damaged cables / lines
If there is damage to the connecting cables or lines of
the appliance or externally installed accessories, these
must be replaced with Viessmann cables or lines. For
this, contact your qualified contractor.
Maintenance
Cleaning
6167584
36
Operating program
The operating program enables you to define the fol-
lowing, for example:
How you heat your rooms
Whether you heat DHW
Heating curve
Heating curves illustrate the relationship between the
outside temperature, the set room temperature and the
flow temperature. The lower the outside temperature,
the higher the flow temperature.
In order to guarantee sufficient heat with minimum
energy consumption at any outside temperature, the
conditions of your building and system must be taken
into consideration. The heating curve is adjusted by
your contractor for this purpose.
3.2
3.4
Flow temperature in °C
Outside temperature in °C
Heating curve slope
3.0
2.8
2.2
2.4
2.0
1.6
1.4
1.2
1.0
0.8
0.6
0.4
0.2
90
80
70
60
50
40
30
20
1.8
2.6
1020 -30-20-100
Fig. 7
Setting the slope and level, taking the heating curve as an example
Factory settings:
Slope = 1
Level = 3
The heating curves shown apply with the following set-
tings:
Heating curve level = 0
Standard room temperature (set room temperature)
= 20 °C
0.2
Outside temperature in °C
Slope
2.4
2.62.8
3.03.2
3.4
90
80
70
60
50
40
30
0 -10 -2010
2.0
2.2
Set room
temperature in °C
35 30 25 20 15 10 5
0.4
0.6
0.8
1.0
1.2
1.4
-30
1.8
1.6
-14
C
B
A
Flow temperature in °C
Fig. 8
Appendix
Terminology
6167584
37
For an outside temperature of 14 °C:
AUnderfloor heating system: Slope 0.2 to 0.8
BLow temperature heating system: Slope 0.8 to 1.6
CSystem with a flow temperature in excess of 75 °C, slope 1.6 to 2.0
AB
Flow temperature
in °C
110
Outside temperature
in °C
3.5
1.4
0.2
-20
C
Set room temperature in °C
35 30 25 20 15 10 5
Fig. 9
AIf you change the slope:
The steepness of the heating curves changes.
BIf you change the level:
The heating curves are shifted in parallel in a verti-
cal direction.
CIf you change the standard room temperature (set
room temperature):
The heating curves are shifted along the "Set room
temperature" axis.
Note
Setting the slope or level too high or too low will not
cause any damage to your heating system.
Both settings affect the level of the flow temperature,
which may then be too low or unnecessarily high.
Heating circuit
A heating circuit is a sealed unvented circuit connect-
ing the heat generator and the radiators, in which the
heating water circulates.
A system may comprise several heating circuits.
For example, one heating circuit for the rooms occu-
pied by you and one heating circuit for the rooms of a
separate apartment.
Heating circuit pump
Circulation pump for circulating the heating water in
the heating circuit
Appendix
Terminology (cont.)
6167584
38
Room temperature
Standard room temperature or comfort room temper-
ature:
Set the standard room temperature or comfort room
temperature for periods when you are at home dur-
ing the day.
Reduced room temperature:
For periods when you will be absent or during the
night, set the reduced room temperature; see "Heat-
ing mode".
Safety valve
Safety equipment that must be installed in the cold
water pipe by your contractor. The safety valve opens
automatically to prevent excess pressure in the DHW
cylinder.
The heating circuits are also equipped with safety
valves.
Temperature level
You can specify set values for 3 different temperature
levels:
"Standard"
"Reduced"
"Comfort"
Set temperature
Specific temperature that should be reached, e.g. set
DHW temperature for example.
Drinking water filter
A device that removes solids from the drinking water.
The drinking water filter is built into the cold water
pipework to the DHW cylinder.
Flow temperature
The flow temperature is the temperature at which the
heating water enters a system component such as a
heating circuit.
Time program
In the time programs you determine what your heating
system should do at what time.
Information on disposal
Disposal of packaging
Your contractor will dispose of the packaging from your
Viessmann product.
Appendix
Terminology (cont.)
6167584
39
Final decommissioning and disposal of the heating system
Viessmann products can be recycled. Components
and fluids from your heating system do not belong in
ordinary domestic waste.
Please speak to your contractor about the correct dis-
posal of your old system.
Appendix
Information on disposal (cont.)
6167584
40
A
Ambient temperatures................................................ 11
B
Brightness adjustment................................................24
Burner reset............................................................... 29
Buttons....................................................................... 15
C
Central heating
Factory settings.......................................................12
Central heating, switching on..................................... 20
Checks
Fault messages.......................................................29
Information.............................................................. 27
WiFi information...................................................... 28
Cleaning..................................................................... 35
Cleaning information.................................................. 35
Cold rooms.................................................................33
Comfort (tips)............................................................. 13
Commissioning.....................................................11, 32
D
Date/time, factory setting........................................... 12
Default displays..........................................................14
Default setting............................................................ 12
DHW heating
Comfort................................................................... 13
Energy saving......................................................... 13
Factory setting.........................................................12
DHW heating, switching off........................................ 23
DHW heating, switching on........................................ 23
DHW temperature adjustment....................................23
Display illumination.................................................... 24
Drinking water filter.................................................... 38
E
Emissions test mode.................................................. 31
Energy saving (tips)................................................... 13
Energy saving function...............................................21
F
Factory setting............................................................12
Fault............................................................... 29, 33, 34
Filter (drinking water)................................................. 38
Flow temperature....................................................... 38
Frost protection.................................................... 12, 22
Frost protection monitoring........................................ 12
G
Gas shut-off valve...................................................... 32
Glossary..................................................................... 36
H
Heat generator, switching on......................................32
Heating circuit............................................................ 37
Heating circuit pump.................................................. 37
Heating curve
Explanation............................................................. 36
Heating curve adjustment.......................................... 20
Holiday....................................................................... 21
Holiday at home......................................................... 21
Holiday program...................................................21, 22
Home screen..............................................................14
Hot rooms...................................................................33
Hot water....................................................................34
I
Information................................................................. 10
Inspection...................................................................35
Installation room......................................................... 11
Intended use.............................................................. 10
Internet access, switching on..................................... 25
L
Legal information........................................................27
Level of heating curve................................................ 36
Liability......................................................................... 8
Licences............................................................... 11, 27
Lightguide.............................................................14, 24
Low power radio on/off...............................................26
M
Main menu................................................................. 15
Maintenance...............................................................35
Maintenance contract.................................................35
N
No hot water...............................................................34
Notice of completion...................................................11
O
ON/OFF switch...........................................................32
Open source licences.................................................27
Operating data, checking........................................... 27
Operating program
Terminology.............................................................36
Operating programs................................................... 16
Operation................................................................... 14
P
Power failure.............................................................. 12
Pressure gauge..........................................................32
Pressure indicator...................................................... 32
Product information.................................................... 10
Pump
Heating circuit......................................................... 37
R
Reduced heating mode.............................................. 12
Reduced heating operation........................................ 12
Rooms are too cold.................................................... 33
Rooms too hot............................................................33
Room temperature
Adjusting for longer periods at home...................... 21
S
Safety valve................................................................38
Screensaver............................................................... 14
Set temperature......................................................... 38
Keyword index
Keyword index
6167584
41
Setting a time program...............................................17
Setting the date.......................................................... 24
Shutdown
With frost protection................................................ 32
Without frost protection........................................... 32
Slope of heating curve............................................... 36
Standard heating operation........................................12
Standby...................................................................... 14
Standby mode............................................................ 36
Standby mode for display...........................................24
Status display.............................................................14
Summer mode............................................................36
Summertime changeover........................................... 12
Switching off
DHW heating...........................................................23
Heat generator........................................................ 32
Switching on...............................................................32
Central heating........................................................20
DHW heating...........................................................23
Symbols....................................................................... 9
System
Switching on............................................................32
T
Temperature
Set temperature...................................................... 38
Temperature level.......................................................38
Temperature level adjustment.................................... 20
Terminology................................................................36
Test mode...................................................................31
Third Party Software.................................................. 28
Time/date, factory setting........................................... 12
Time program....................................................... 13, 38
Comfort................................................................... 13
Time program adjustment
Central heating........................................................18
DHW........................................................................19
Time setting................................................................25
Turning off
Central heating........................................................22
Turning off central heating..........................................22
V
ViCare app................................................................. 14
W
Water too cold............................................................ 34
Water too hot..............................................................34
What to do if...?.......................................................... 33
WiFi............................................................................ 25
WiFi connection..........................................................25
WiFi connection, establishing.....................................25
Winter mode...............................................................36
Wintertime changeover.............................................. 12
Wireless connection, switching on............................. 26
Keyword index
Keyword index (cont.)
6167584
42
6167584
43
6167584
44
Your contact
Contact your local contractor if you have any questions about your system or wish to arrange maintenance or
repair work. You can find local contractors on the internet at www.viessmann.de.
Viessmann Limited
Hortonwood 30, Telford
Shropshire, TF1 7YP, GB
Telephone: +44 1952 675000
Fax: +44 1952 675040
E-mail: info-uk@viessmann.com
Viessmann Climate Solutions SE
35108 Allendorf / Germany
Telephone: +49 6452 70-0
Fax: +49 6452 70-2780
www.viessmann.com
6167584 Subject to technical modifications.
11

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Viessmann VITODENS 100-W - 2023 bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Viessmann VITODENS 100-W - 2023 in de taal/talen: Engels als bijlage per email.

De handleiding is 1.96 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

Andere handleiding(en) van Viessmann VITODENS 100-W - 2023

Viessmann VITODENS 100-W - 2023 Gebruiksaanwijzing - Nederlands - 44 pagina's

Viessmann VITODENS 100-W - 2023 Gebruiksaanwijzing - Deutsch - 44 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info