Operating and display functions 8
0020237057_00 Installation instructions 21
8.9.14 Activating parallel cylinder charging
(domestic hot water cylinder and mixer
circuit)
Menu Installer level System configuration [DHW cir-
cuit ----] Parallel cyl. charging
You can use this function to define, for the connected
mixer circuit, that the mixer circuit should continue to be
heated during charging of the domestic hot water cylin-
der.
If the Parallel cyl. charging function is activated, the mixer
circuits continue to be supplied while the cylinder is being
charged. Provided there is an energy demand in the mixer
circuit, the controller does not deactivate the heating pump
in the mixer circuit. The non-mixed heating circuit is always
switched off during cylinder charging.
8.10 Buffer cylinder
8.10.1 Reading the top cylinder temperature in the
buffer cylinder
Menu Installer level System configuration [Buffer
cylinder ----] Cyl. temp.: top
You can use this function to read the current temperature
in the upper section of the buffer cylinder.
8.10.2 Reading the bottom cylinder temperature in
the buffer cylinder
Menu Installer level System configuration [Buffer
cylinder ----] Cyl. temp.: Bottom
You can use this function to read the current temperature
in the lower section of the buffer cylinder.
8.10.3 Reading the top cylinder temperature for
hot water in the buffer cylinder
Menu Installer level System configuration [Buffer
cylinder ----] DHW temp. sensor, top
You can use this function to read the current temperat-
ure in the upper section of the buffer cylinder's hot water
component.
8.10.4 Reading the bottom cylinder temperature
for hot water in the buffer cylinder
Menu Installer level System configuration [Buffer
cylinder ----] DHW tmp. sensor, bot.
You can use this function to read the current temperat-
ure in the lower section of the buffer cylinder's hot water
component.
8.10.5 Reading the top cylinder temperature for
heating in the buffer cylinder
Menu Installer level System configuration [Buffer
cylinder ----] Heat. temp. sens., top
You can use this function to read the current temperature
in the upper section of the buffer cylinder's heating com-
ponent.
8.10.6 Reading the bottom cylinder temperature
for heating in the buffer cylinder
Menu Installer level System configuration [Buffer
cylinder ----] Heat. temp. sens., bot.
You can use this function to read the current temperature
in the lower section of the buffer cylinder's heating com-
ponent.
8.10.7 Setting the max. target flow temperature in
the buffer cylinder
Menu Installer level System configuration [Buffer
cylinder ----] Max.DHW fl.targ.temp.
You can use this function to set the buffer cylinder's max-
imum target flow temperature for the domestic hot wa-
ter unit. The max. target flow temperature that is to be
set must be lower than the max. flow temperature for the
heat generator. While the cylinder's set target temperat-
ure is not reached, the controller does not allow the heat
generator to go into heating mode.
You can find the maximum target flow temperature that the
heat generator can achieve in the installation instructions for
the heat generator.
If the max. target flow temperature that is set is too low, the
domestic hot water unit cannot provide the required hot wa-
ter temperature for the cylinder.
8.11 Solar circuit
8.11.1 Reading the collector temperature
Menu Installer level System configuration [Solar
circuit ----] Collector temp.
You can use this function to read the current temperature
on the collector temperature sensor.
8.11.2 Reading the status of the solar pump
Menu Installer level System configuration [Solar
circuit ----] Solar pump status
You can use this function to read the current status of the
solar pump (On, off).
8.11.3 Reading the running time of the solar pump
Menu Installer level System configuration [Solar
circuit ----] Solar pump runtime
This function allows you to read the measured operating
hours of the solar pump since start-up or since the last
reset.
8.11.4 Resetting the solar pump running time
Menu Installer level System configuration [Solar
circuit ----] Reset runtime
You can use this function to reset the total operating
hours of the solar pump to zero.
8.11.5 Reading the value of the solar yield sensor
Menu Installer level System configuration [Solar
circuit ----] Solar yield sensor
You can use this function to read the current value for the
solar yield sensor.
21

Hulp nodig? Stel uw vraag in het forum

Spelregels
1

Forum

Vaillant-VRC-700F-4

Zoeken resetten

  • Beste,
    Ik kan mijn temperatuur niet regelen voor de nacht, wel inde dag met de tijdsprogramma's.
    Hoe kan ik dat verhelpen Gesteld op 10-1-2024 om 11:32

    Reageer op deze vraag Misbruik melden

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Vaillant VRC 700F-4 bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Vaillant VRC 700F-4 in de taal/talen: Engels als bijlage per email.

De handleiding is 1,3 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info