141Installation instructions auroMATIC 620 0020094404_00 controller
Reversal boiler sequence (only for cascades)
The aim of the reversal of boiler sequence is an equal
operating time for all connected appliances.
The boiler sequence is changed if:
1. The reversal of boiler sequence has been enabled in
the menu and
2 Reversal of boiler sequence is possible in the
selected hydraulic plan
3 Difference in the duration of activation between first
and last boiler is 100 hours.
- In this case, sorting is in rising order of activation
hours.
- An internal value for the activation hours is used;
the boiler operating hours are not read back.
Remarks:
With heaters with different outputs, it does not make
sense to reverse the boiler sequence.
Outside temperature correction
The sensor value of the outdoor sensor which is con-
nected to the controller can be changed by a value of
+/- 5 °C to compensate external influences. This means
that the measured external temperature is changed to
the set value.
Setting range: –5 K ... +5 K,
Basic setting: 0 K
Parallel charging
This function applies to all connected mixing circuits. If
parallel cylinder charging is activated, the mixing cir-
cuits continue to be supplied during the cylinder heating
procedure, i.e. the pumps in the mixing circuits are not
switched off as long as there is still a need for heating
in the respective heating circuits. HK1 is always switched
off during cylinder charging.
Phone
You can store a telephone number in the display, which
will be automatically displayed when servicing is due.
Pump blocking protection
To prevent a boiler, heating, circulation or charging
pump from seizing, those pumps which have not been
operated for the last 24 hours are actuated for about
20 seconds in sequence every day.
Pump delay time
To save electrical energy, the heating circuit pump can
be switched off for a configurable time according to
defined criteria.
The actual flow temperature is compared with the tar-
get flow temperature of the heating circuit as a crite-
rion for "Energy requirements of the heating circuit are
met". This comparison is made every 15 minutes. If the
difference is not more than 2 K and this criteria is met
three times in a row, the pump is switched off for the
set pump delay time and the mixer remains in the cur-
rent position.
Rev. Seq control
When cascading boilers, the drinking water cylinder in
hydraulic plans 5-8 can have a direct hydraulic connec-
tion with the priority switching valve or the charging
pump of the boiler with the highest eBUS address. In
this case the isolation circuit must be activated. When
there is a request for hot water via cylinder sensor TD2,
the last boiler is used for charging the cylinder: all other
boilers can continue to serve the buffer cylinder.
Selection of hydraulic plan
Nine system configurations (hydraulic plans) are already
stored in the controller. A pre-configuration is carried
out when a hydraulic plan is selected.
When the controller is put in operation, the first thing
that always ensues is a request for the required hydrau-
lic plan. The available hydraulic plans are described in
Chapter 5.
Service
You can store the next maintenance date for the system
here.
Set up heat zone
All connected heating circuits can be configured in the
Installation Assistant (Menu A6) according to how they
are used. Due to the configuration, only those values
and parameters are displayed which are relevant to the
selected type of heating circuit.
The following settings are possible for mixing circuits:
Mixing circuit (floor or radiator circuit as mixing circuit),
Fixed value (i. e. the mixing circuit is regulated to a fixed
value), Return temperature increase (for conventional
heating appliances and systems with large water capaci-
ties as protection against corrosion in the boiler due to
prolonged periods below the dew point), Cylinder
charging current and “disabled” (to suppress the para-
meters if the second mixer module is not required for a
VR 60 mixer module).
Solar-assisted heating:
Solar-assisted heating is used to extract solar heat even
for heating purposes. For this the return temperature in
the heating system is raised.
Using hydraulic plans 1-4, solar-assisted heating can be
achieved with the 3rd difference controller TD1, TD2
and MA.
- TD1 is positioned in the middle of the cylinder,
- TD2 is positioned in the return line.
Glossary
199

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Vaillant Auromatic 620 bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Vaillant Auromatic 620 in de taal/talen: Engels als bijlage per email.

De handleiding is 6,37 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Andere handleiding(en) van Vaillant Auromatic 620

Vaillant Auromatic 620 Gebruiksaanwijzing - Nederlands - 204 pagina's

Vaillant Auromatic 620 Gebruiksaanwijzing - Deutsch - 52 pagina's

Vaillant Auromatic 620 Gebruiksaanwijzing - Français - 204 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info