SERVICE MANUAL
FILE NO. DAS-SM-00-001
AIR-CONDITIONER
SUPPLEMENT
SPLIT WALL TYPE
PRINTED IN JAPAN, Nov.,1999 ToMo
RAS-07YKX
/
RAS-07YAX
RAS-10YKX
/
RAS-10YAX
RAS-11YKX
/
RAS-11YAX
RAS-07YK-E
/
RAS-07YA-E
RAS-10YK-E
/
RAS-10YA-E
RAS-07YK-ES/RAS-07YA-ES
RAS-10YK-ES
/
RAS-10YA-ES
RAS-10YK-HX
/
RAS-10YA-HX
RAS-07YKX-T
/
RAS-07YAX-T
RAS-10YKX-T
/
RAS-10YAX-T
– 2 –
CONTENTS
1. SPECIFICATIONS..................................................................................... 3
2. CONSTRUCTION VIEWS ........................................................................ 8
3. WIRING DIAGRAM ................................................................................. 10
4. SPECIFICATIONS OF ELECTRICAL PARTS ...................................... 11
5. REFRIGERANT CYCLE DIAGRAM ...................................................... 13
6. CONTROL BLOCK DIAGRAM .............................................................. 14
7. OPERATION DESCRIPTIONS................................................................. 15
8. INSTALLATION PROCEDURE ............................................................... 20
9. TROUBLESHOOTING CHART............................................................... 33
10. PART REPLACEMENT........................................................................... 46
11. EXPLODED VIEWS AND PARTS LIST ............................................... 50
– 3 –
1. SPECIFICATIONS
RAS-07YKX/07YAX, RAS-07YK-E/07YA-E, RAS-07YKX-T/07YAX-T
RAS-07YK-E/YA-E RAS-07YKX/YAX RAS-07YKX-T/YAX-T
MODEL
ITEM
Cooling
220V240V 220V
Capacity kW
*
1
2,102,20 2,10
Phase Single
V220240 220Power source
Hz 50
Power consumption kW 0,600,65 0,60
Power factor % 9694 96
V220V240V 220V
Running current
Indoor/Outdoor A 0,15/2,700,15/2,72 0,15/2,70
Starting current A 12
Moisture removal lit/h 0,8
Indoor (H/M/L) dB (A) 39 / 33 / 29
Noise
(SPL at 1 meter)
Outdoor (220240V) dB (A) 4445 44
Name of refrigerant R-22
Refrigerant
Rated volume kg 0,59
Refrigerant control Capillary tube
Gas side size mm 9,52
Connection type Flare connection
Liquid side size mm 6,35
Connection type Flare connection
Maximum length (of one way) m
*
210
Interconnection pipe
Maximum height difference
Indoor unit
Outdoor unit
m
5
Condensate drain pipe Outer diameter mm 16
INDOOR UNIT RAS-07YK-E RAS-07YKX RAS-07YKX-T
Height mm 265
Width mm 790Dimensions
Depth mm 189
Net weight kg 8
Evaporator type Finned tube
Indoor fan type Cross flow fan
High fan m³/h 550
Medium fan m³/h 490Air flow rate
Low fan m³/h 430
Fan motor output W 20
Air filter Polypropylene net filter (Washable)
OUTDOOR UNIT RAS-07YA-E RAS-07YAX RAS-07YAX-T
Height mm 530
Width mm 770Dimensions
Depth mm 200
Net weight kg 26
Condenser type
Finned tube
Outdoor fan type Propeller
Air flow rate (220240V) m³/h 15001700 1500
Fan motor output W 18 (UE6-21SJ5P) 18 (UE6-21A5P), 20 (HF-240-20A)
Model PH80T1-4C
Compressor
Output W 605
Safety device Fuse, Overload relay
Auto louver Ye s
Usable outdoor temperature range °C2143
Specifications are subject to change without notice.
4
RAS-10YKX/10YAX, RAS-11YKX/11YAX
RAS-10YK-E/10YA-E, RAS-10YK-HX/10YA-HX
Specifications are subject to change without notice.
RAS-10YKX/10YAX
RAS-10YK-E/10YA-E
RAS-10YK-HX/10YA-HX
RAS-11YKX/11YAX
MODEL
ITEM
Cooling
220V240V
Capacity kW
*
1
2,702,70
Phase Single
V220240Power source
Hz 50
Power consumption kW 0,800,85
Power factor % 9694
V220V240V
Running current
Indoor/Outdoor A 0,15/3,650,15/3,60
Starting current A 16
Moisture removal lit/h 1,2
Indoor (H/M/L) dB (A) 44 / 36 / 29
Noise
(SPL at 1 meter)
Outdoor (220240V) dB (A) 4445
Name of refrigerant R-22
Refrigerant
Rated volume kg 0,70
Refrigerant control Capillary tube
Gas side size mm 9,52
Connection type Flare connection
Liquid side size mm 6,35
Connection type Flare connection
Maximum length (of one way) m
*
210
Interconnection pipe
Maximum height difference
Indoor unit
Outdoor unit
m
5
Condensate drain pipe Outer diameter mm 16
INDOOR UNIT RAS-10YKX
RAS-10YK-E
RAS-10YK-HX
RAS-11YKX
Height mm 265
Width mm 790Dimensions
Depth mm 189
Net weight kg 8
Evaporator type Finned tube
Indoor fan type Cross flow fan
High fan m³/h 650
Medium fan m³/h 510Air flow rate
Low fan m³/h 430
Fan motor output W 20
Air filter Polypropylene net filter (Washable)
OUTDOOR UNIT RAS-10YAX
RAS-10YA-E
RAS-10YA-HX
RAS-11YAX
Height mm 530
Width mm 770Dimensions
Depth mm 200
Net weight kg 29
Condenser type Finned tube
Outdoor fan type Propeller
Air flow rate (220240V) m³/h 15001700
Fan motor output W 18 (UE6-21SJ5P) 18 (UE6-21A5P), or 20 (HF-240-20A)
Model PH102T1-4C 2PS146D5AB02
Compressor
Output W 750
Safety device Fuse, Overload relay
Air flow rate Ye s
Usable outdoor temperature range °C2143
5
RAS-10YK-ES / RAS-10YA-ES
RAS-10YKX-T / RAS-10YAX-T
Specifications are subject to change without notice.
RAS-10YK-ES/10YA-ES RAS-10YKX-T/10YAX-T
MODEL
ITEM
Cooling
220V240V 220V
Capacity kW
*
1
2,652,70 2,70
Phase Single
V220240 220
Power source
Hz 50
Power consumption kW 0,800,85 0,80
Power factor % 9694 96
V220V240V 220V
Running current
Indoor/Outdoor A 0,15/3,65
Starting current A 16 11
Moisture removal lit/h 1,2
Indoor (H/M/L) dB (A) 44 / 36 / 29
Noise
(SPL at 1 meter)
Outdoor dB (A) (220240V) 44 (220V) 46
Name of refrigerant R-410A R-22
Refrigerant
Rated volume kg 0,69 0,75
Refrigerant control Capillary tube
Gas side size mm 9,52
Connection type Flare connection
Liquid side size mm 6,35
Connection type Flare connection
Maximum length (of one way) m
*
210
Interconnection pipe
Maximum height difference
Indoor unit
Outdoor unit
m
5
Condensate drain pipe Outer diameter mm 16
INDOOR UNIT RAS-10YK-ES RAS-10YKX-T
Height mm 265
Width mm 790Dimensions
Depth mm 189
Net weight kg 8
Evaporator type Finned tube
Indoor fan type Cross flow fan
High fan m³/h 650
Medium fan m³/h 510Air flow rate
Low fan m³/h 430
Fan motor output W 20
Air filter Polypropylene net filter (Washable)
OUTDOOR UNIT RAS-10YA-ES RAS-10YAX-T
Height mm 530
Width mm 770
Dimensions
Depth mm 200
Net weight kg 29 31
Condenser type Finned tube
Outdoor fan type Propeller
Air flow rate m³/h (220240V) 1500 (220V)1700
Fan motor output W 18 (UE6-21SJ5P) 27 (UE6-31C5P) or 30 (HF-240-30A)
Model PA98X1T-4FZ RM5510GNE92
Compressor
Output W 750
Safety device Fuse, Overload relay
Auto louver Ye s
Usable outdoor temperature range °C2143
7
Note :
*
1
Capacity is based on the following temperature conditions.
CONDITION COOLING
TEMPERATURE
Indoor unit inlet air temperature
(DB) 27 °C
(WB) 19 °C
Outdoor unit inlet air temperature
(DB) 35 °C
(WB) 24 °C
Notes :
*
2 CHARGELESS
No additional refrigerant required.
This air conditioner accepts a connection piping length of up to 10m and a head of up to 5m.
There is no need to add the refrigerant as long as the total length of the connection piping is up to 10m.
Air filter
790
Heat exchanger
Air inlet
265
Air outlet
47
10
50
189
47
10
50
Knock out system
790
232 326 232
Hanger
321
Drain hose (0,54m)
Connecting pipe (0,39m)
(Flare Ø6,35)
(Flare Ø9,52)
Hanger
65965,5
326
450
65,5
For stud bolt
(Ø8~Ø10)
For stud bolt
(Ø6)
Hanger
Minimum
distance
to wall
Minimum
distance
to ceiling
265
178,5
Knock out system
Front panel
Back body
20 2037
40,5
60,5
790
12626931976
Center line
Installation
plate outline
HangerHanger
40,5
3,5
Hanger
Minimum
distance
to wall
17 20
46
120 or more 120 or more
66 or more
2,5
Connecting pipe (0,49m)
1800
07YK-E, 07YK-ES, 10YK-E
10YK-ES:
Without power cord
07YKX, 10YKX, 11YKX
07YKX-T, 10YKX-T :
With power cord
10YK-HX :
With power cord & plug
- 8 -
2.CONSTRUCTION VIEWS
2-1.Indoor Unit
600 85
36
111
Ø25 Drain hole
50
30
216
230
8-Ø6 Holes
(For fixing the outdoor unit)
4-Ø11x14 Long holes
(For anchor bolt Ø8-Ø10)
Gas side (flare Ø9,52)
Liquid side (flare Ø6,35)
111
A
600
R10
50
36
25
216
230
Ø11x14 Hole
Ø6 Hole
Handle
11
525
530
5
268
Fan guard
ø420
TOSHIBA
770 59
89
200
11
12
Electric
parts cover
Z
54 62
Access for
charging
250
Z
View
600
45 or more
Inlet port
600 or more
(Minimum distance
of the wall)
4-Ø11x14 Long holes
(For anchor bolt Ø8-Ø10)
400 or more
Outlet
port
Center
port
230
100 or more
Inlet port
Visible outline
of the product
A
Detail Drawing
Mounting dimension of anchor bolt
268
770
59
89
2-2. Outdoor Unit
- 9 -
10
3. WIRING DIAGRAM
1
2
3
456
1
2
3
456
5
3 1
1
2
1
2
1
2
1
2
L
N
FAN
MOTOR
WHI
WHI
PNK
BLK
BLK
BLK
RED
RED
RED
CAPACITOR CAPACITOR
OVER LOAD
RELAY
GRN & YEL
CHASSIS
INDOOR
OUTDOOR
BLK
WHI
GRN&YEL
GRN&YEL
P04
BLK
BRW
BLU
ORN
ORN
ORN
ORN
CN04
CN13
CN25
CN03CN10
C58
CN11 CN01
BLK
BLK
BLK
BLK
POWER
SUPPLY
CIRCUIT
C02
DC 12V
DB01
R01
C01
L01
C15
R22
F01
6,3A
250V
R21
RY01
RY02
WHI
BLK
3
4
3
4
POWER
TERMINAL
BLOCK
Datail A
INDOOR
TERMINAL
BLOCK
THERMO
SENSOR
(TA)
AC FAN MOTOR
HEAT
EXCHANGER
SENSOR
(TC)
:
:
:
:
:
:
:
:
:
:
BROWN
RED
WHITE
YELLOW
BLUE
BLACK
GRAY
PINK
ORANGE
GREEN &
YELLOW
BRW
RED
WHI
YEL
BLU
BLK
GRY
PNK
ORN
GRN&YEL
COLOR IDENTIFICATION
VARISTOR
1
9
8
7
6
54321
9
8
7
6
5
9
8
7
6
5
4
4
3
3
2
2
1
1
2
2
1
SG01
DSA
1
23
5
3 1
1
23
YEL
BLK
BLK
BRW
PNK
WHI
1
2
1
2
COMPRESSOR
BLU
PNK
BLK
WHI
BLU
BLU
BLU
BLU
BLU
OUTDOOR
TERMINAL
BLOCK
RAS-10YK-HX
RAS-07YK-E
RAS-10YK-E
RAS-07YK-ES
RAS-10YK-ES
RAS-07YK-E/10YK-E
RAS-07YK-ES/10YK-ES
RAS-07YKX
RAS-10YKX
RAS-11YKX
RAS-07YKX-T
RAS-10YKX-T
RAS-07YKX/10YKX/11YKX
RAS-07YKX-T/10YKX-T/10YK-HX
L
N
THERMAL
FUSE
77°C x 1
THERMAL
FUSE
77°C x 2
Power cord with plug
LOUVER MOTOR
1
2
3
4
6
5
PNK
YEL
ORN
RED
BRW
BLU
CN07
1
2
3
4
6
5
DC 5V
CR03 IC 03
INFRARED RAYS RECEIVE
AND INDICATION PARTS
FAN MOTOR
RAS-10YAX-T
COMPRESSOR
RAS-10YA-ES
only
only
A
MCC-798
VARISTOR
11
4. SPECIFICATIONS OF ELECTRICAL PARTS
4-1. Indoor Unit
No. PARTS NAME TYPE SPECIFICATIONS
Output (Rated) 20W, 6poles, 1phase, 220240V, 50Hz
Red-Black White-Black1
Fan motor
(for indoor) MMF-240-20-4A
Winding resistance (
W
)
(at 20°C)
220,8 324,3
2 Thermo. sensor (TA-sensor) (Microprocessor) 10k
W
at 25°C
3 Switching transformer SWT-47
4 Microcomputer TMP87CK40AN
5 Power relay, Common relay DI1U Coil : DC 12V 75mA, Rated AC 250V 20A
6 Heat exchanger sensor (TC-sensor) (Microprocessor) 10k
W
at 25°C
7 Line filter SS11V-06180 18mH, AC 0,6A
8 Diode D3SBA60 4A, 600V
9 Capacitor ECEC2GA470BL 47
m
F, 400V
10 Fuse TSCR T6, 3A, 250V
11 Varistor 15G561K 560V
12 Resistor 5,6
W
, 2W
13 Louver motor MP35EA12 Output (Rated) 2W, 10poles, 1phase, DC 12V
4-2. Outdoor Unit
RAS-07YAX, RAS-07YA-E, RAS-07YAX-T
No. PARTS NAME TYPE SPECIFICATIONS
Output (Rated) 605W, 2poles, 1phase, 220240V, 50Hz
C-R C-S1 Compressor PH80T1-4C
Winding resistance (W)
(at 20°C)
4,80 8,37
Output (Rated) 18W, 6poles, 1phase, 220240V, 50/60Hz
Red-Black White-Black
RAS-07YA-E
UE6-21SJ5P
Winding resistance (
W
)
(at 20°C)
370 370
Output (Rated) 18W, 6poles, 1phase, 220240V, 50/60Hz
Red-Black White-BlackUE6-21A5P
Winding resistance (W)
(at 20°C)
370 370
Output (Rated) 20W, 6poles, 1phase, 220240V, 50/60Hz
Red-Black White-Black
2
Fan motor
(for outdoor)
RAS-07YAX
RAS-07YAX-T
HF-240-20A
Winding resistance (W)
(at 20°C)
387 466
RAS-07YA-E
SK-50FMP1,5U1 AC 500V, 1,5
m
F
3
Runnin
g
capacitor
(for fan motor)
RAS-07YAX
RAS-07YAX-T
DS501155BPQA AC 500V, 1,5mF
4 Running capacitor (for compressor) SK-40CMP15U1 AC 400V, 15
m
F
5 Overload relay JMRA99208-9201 U/T 4,2A (25°C), OPEN 130 ± 5°C, CLOSE 69 ± 11°C
20
8. INSTALLATION PROCEDURE
8-1. Safety Cautions
For general public use
Power supply cord of parts of appliance for Outdoor use shall be more than polychloroprene sheathed flexible cord
(design H05 RN-F), or cord designation 245 IEC 57.
CAUTION
TO DISCONNECT THE APPLIANCE FROM THE MAINS SUPPLY.
This appliance must be connected to the mains by means of a circuit breaker or a switch with a contact separation
of at least 3 mm.
If this is not possible, a power supply plug with earth must be used. This plug must be easily accessible after
installation. The plug must be disconnected from the power supply socket in order to disconnect the appliance
completely from the mains.
DANGER
ENGAGE DEALER OR SPECIALIST FOR INSTALLATION.
` FOR ELECTRICAL WORKS THE WIRING AND CABLES MUST BE PERFORMED IN COMPLIANCE WITH
NATIONAL WIRING STANDARD OR REGULATION.
IF INCORRECT AND INCOMPLETE WIRING IS CARRIED OUT, IT WILL CAUSE AN ELECTRICAL FIRE OR
ELECTRICAL SHOCK.
` USE THE SPECIFIED CABLE (1,5 to 2,0mm²) AND CONNECT TIGHTLY FOR INDOOR/OUTDOOR
CONNECTION. CONNECT TIGHTLY AND CLAMP THE CABLE SO THAT EXTERNAL FORCE WILL BE
ACTED ON THE TERMINAL.
` WIRE ROUTING MUST BE PROPERLY ARRANGED SO THAT CONTROL BOARD COVER IS FIXED
PROPERLY.
` DO NOT DAMAGE OR SCRATCH THE CONDUCTIVE CORE AND INNER INSULATOR OF THE CABLES.
` DO NOT DEFORM OR SMASH ON THE SURFACE OF THE CABLES. DO NOT PRESS OR FIX THE CORD
AND CABLES FIRMLY WITH STAPLES, etc.
` DO NOT USE THE EXTENSION CABLE FOR POWER SUPPLY CORD OR INTER-CONNECTING CABLE.
NEVER EXECUTE THE CONNECTION OF WIRING WITH OTHER METHOD THAN THE APPROVED ONE.
OTHERWISE, OVERHEAT, SMOKE OR FIRE MAY BE GENERATED BY CONTACT ERROR.
` TURN OFF MAIN POWER SUPPLY AND BREAKER BEFORE ATTEMPTING ANY ELECTRICAL WORK.
MAKE SURE ALL POWER SWITCHES AND BREAKER TURN OFF. FAILURE TO DO SO MAY CAUSE
ELECTRIC SHOCK.
` CONNECT THE CONNECTING CABLE CORRECTLY. IF THE CONNECTING CABLE IS CONNECTED BY
WRONG WAY, ELECTRIC PARTS MAY BE DAMAGED.
` GROUNDING WIRE WORKS MUST BE CONSTRUCTED IN COMPLIANCE WITH INSTALLATION MANUAL.
` DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS VAPORS.
FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION.
` TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE HAZARD. PLACE THE UNIT WELL
AWAY (MORE THAN 2M.) FROM HEAT SOURCE SUCH AS RADIATORS, HEAT REGISTORS. FURNACE,
STOVES, etc.
` IF A REFRIGERATION GAS LEAKS DURING INSTALLATION, BE SURE TO PERFORM VENTLATION.
IF THE REFRIGERANT GAS COMES INTO CONTACT WITH FIRE, A POISONOUS GAS MAY OCCUR.
WHEN INSTALLING AN AIR CONDITIONER, DO NOT ALLOW AIR OR MOISTURE TO REMAIN IN THE
REFRIGERATION CYCLE. OTHERWISE, PRESSURE IN THE REFRIGERATION CYCLE MAY BECOME
ABNORMALLY HIGH SO THAT A RUPTURE OR PERSONAL INJURY MAY BE CAUSED.
` BE SURE TO USE THE CORD-CLAMPS AND THE ELECTRIC PARTS COVER TO THE SPECIFIED
POSITION WITH ATTACHED TO THE PRODUCT. MOUNT THE ELECTRIC PARTS COVER FOR CABLES OF
CONNECTING SECTION FIRMLY WITH THE SCREWS.
30
8-5-1. Refrigerant Piping Connection
<Flaring>
(1) Cut the pipe with a pipe cutter.
90˚
Obliquity
Roughness
Warp
Fig. 8-5-2
(2) Insert a flare nut into the pipe, and flare the pipe.
Outer
dia.
6,35mm
9,52mm
A (mm) R22/R410A
Imperial Rigid
1,0 ~ 1,5/ 0,5 ~ 1,0/
1,5 ~ 2,0 1,0 ~ 1,5
1,0 ~ 1,5/ 0,5 ~ 1,0/
1,5 ~ 2,0 1,0 ~ 1,5
Die Pipe
A
Fig. 8-5-3
Fig. 8-5-4
<Tightening connection>
Align the centers of the connecting pipes and tighten
the flare nut as far as possible with your fingers.
Then tighten the nut with a spanner and torque
wrench as shown in the figure.
CAUTION
Do not apply excess torque. Otherwise, the
nut may crack depending on the installation
conditions.
Half union or packed valve
Flare nut
Externally
threaded
side
Internally
threaded
side
Use a wrench
to secure.
Use a torque wrench
to tighten.
8-5-2. Vacuum Pumping
INFORMATION
In order to prevent any other refrigerant from being
charged accidentally, each port of the manifold has
been changed in shape.
Differences in Port Size between
Conventional R22 and R410A
Outer dia.
6,35mm
9,52mm
Tightening touque
Nm (kgfm)
16 ~ 18 (1,6 ~ 1,8)
30 ~ 42 (3,0 ~ 4,2)
Port
size
Manifold for R22 Manifold for R410A
7/16 UNF 1/2 UNF
20 threads per inch 20 threads per inch
AIR PURGE
Evacuate the air in the connecting pipes and in
the indoor unit using vacuum pump.
Do not use the refrigerant in the outdoor unit.
For details, see the manual of vacuum pump.
<Use of vacuum pump>
(1) Connect the charge hose (A) from the manifold
valve to the charge inlet of the gas side packed
valve.
(2) Connect the charge hose (B) to the port of
vacuum pump.
(3) Open fully the low pressure side handle of the
manifold valve.
(4) Operate the vacuum pump.
(5) Close the low pressure side handle of manifold
valve after vacuumizing and stop the vacuum
pump.
Continue vacuumizing more than 15 minutes and
check the pressure gage indicates 0,1MPa
(76 cmHg).
(6) Open the stems of packed valves A and B all the
way.
(7) Securely tighten the stem cap to each of the
packed valve stems.
39
9-3-5. Only Outdoor Fan does not Operate
Shut off the power supply
from AC outlet once and
turn it on after 5 seconds.
Does the OPERATION lamp blink?
Does the power turn on by
pushing the [START/STOP] button
of the remote control?
Is cable connection between indoor
and outdoor units correct?
Replace the
P.C. board.
See Power can not be turned on.
NO
NO
NO
NO
YES
YES
YES
YES
Is the outdoor fan motor winding normal?
(Check the winding resistance)
Is the capacitor for compressor normal?
Outdoor fan motor is defective.
Cables between indoor and
outdoor units are defective.
Outdoor fan motor is defective.
Correct cabling between indoor
and outdoor units.
NO
NO
NO
NO
YES
YES
YES
YES
Are all the cords for outdoor
fan motor normal?
Correct the wire or
replace the defective cords.
Capacitor for outdoor
fan motor is defective.
See Power can not be turned on.
Relays (RY01, RY02)
or IC31 or IC30 is failure.
Is the voltage across the indoor terminal
( 1 - 2 ) AC 220240V (AC 220V)
**
?
Is the voltage across the outdoor terminal
( 1 - 2 ) AC 220240V (AC 220V)
**
?
**
for model RAS-07YKX-T, RAS-10YKX-T
49
No. Part name Procedure Remarks
Q
Common
procedure
1) Stop the operation of air-conditioner, and disconnect
the power cord from the AC supply.
2) Remove Electric parts cover.
(2- ST1T Ø4 x 10
l
)
(1-ST1T Ø4 x 10
l
: 07YA-ES & 10YA-ES only)
3) Remove the cord clamp (2- ST2T Ø4 x 12
l
) and
remove the connecting cable.
4) Remove the front cabinet.
(7- ST1T Ø4 x 10
l
with nylon washer)
Pull the front lower portion toward
y
ou, and remove
it pulling out upward.
R
Capacitor for
compressor
1) Remove the fixing screw of the capacitor band.
(1- ST2T Ø4 x 8
l
)
2) Remove the cable connected to the terminal.
S
Capacitor for
fan motor
1) Remove the fixing screw of the capacitor band.
(1- ST2T Ø4 x 8
l
)
2) Remove the cable connected to the terminal.
Refer to [Specifications of Electric Parts]
in pages 10 and 11.
T
Overload
relay
(Except for
07YA-ES &
1) Perform the process
Q
above.
2) Remove terminal cover of compressor.
3) Remove overload relay holder and pull overload relay
10YA-ES) up.
4) Remove Fustons of leads.
Compressor
10-3. Outdoor Unit
Remove 7-ST1T
Ø4 x 10
2-ST1T Ø4 x10
2-ST2T Ø4 x 12 2-ST2T Ø4 x 12
50
11. EXPLODED VIEWS AND PARTS LIST
11-1. Indoor Unit (1)
RAS-07YK-E, RAS-07YK-ES, RAS-10YK-E, RAS-10YK-ES
Location
Part
Description
No. No.
402 43T60002 Base, Terminal
3P, AC 300V, 20A
403 43T69004 Sensor, Heat Exchanger
10k, 25°C
404 43T69005 Sensor, Thermostat
10k, 25°C
405 43T60061 Fuse Set, Thermal 77°C
Location
Part
Description
No. No.
406 43T69055 P.C. Board Assembly,
MCC-798 (07YK-E, 07YK-ES)
406 43T69054 P.C. Board Assembly,
MCC-798 (10YK-E, 10YK-ES)
412 43T69031 P.C. Board Assembly,
WRS-LED, MCC-766
413 43T61001 Base, E-Parts
ABS, Black, UL94-5V
402
403
405
413
412
404
406
402
49

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Toshiba RAS-10YK-HX bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Toshiba RAS-10YK-HX in de taal/talen: Engels als bijlage per email.

De handleiding is 10,23 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info