49509
3
Verklein
Vergroot
Pagina terug
1/5
Pagina verder
Dimmer outputs
LUXOR 405 (D1 and D2) 2 x 300 VA
D1 only 1 x 500 VA
Info:
The outputs are adjacent and isolated for
the supply.
Any external wire/phase can be connected!
• Semi-conductor switch outputs
Operating Manual
Dimmer module
LUXOR 405
1.0 Designated use
2.0 Brief description
4.1 Description of input terminals
3.0. Safety notes
4.0 Description of control level
4.2 Description of output terminals
5.0 Connecting upgrade devices
LUXOR 405
The LUXOR dimmer module expands the existing LUXOR seriesof devices. It is
suitable for installation in single-family and multiple family houses, offices, etc.
The device is intended for designated installation in control and distribution
cabinets. It is suitable for use in dry rooms with a normal amount of dirt.
In order to eliminate danger of fire and danger of an electric shock,
the device may only be connected and installed by an electrician in
accordance with the national regulations and the valid safety provi-
sions. Tampering with or making modifications to the device will invalidate
the guarantee.
Do not connect dimmers in series or in parallel!
Do not bridge the dimmer!
Do not install an isolation or adjustable transformer before the dimmer!
Only use transformers (Tronic transformers) that are suitable or approved
for operation with a dimmer!
Operation with differing load types is not permitted. Only the combina-
tion of R and C loads (incandescent lamps and Tronic transformers) is
permitted.
Electronic transformers (Tronic transformers) that can be operated with
reverse phase control (C load) and phase control (L load) must not be
combined with other load types.
The voltage supply (at the control cabinet or distribution cabinet) must
be switched off for a load change and when replacing lamps!
Transformers (Tronic transformers) may be operated only with the mini-
mum load specified by the manufacturer. Correct, automatic load detection
is only possible with minimum load. If no data are known, the transformer
(Tronic transformer) must be operated at a minimum nominal load of 80 %.
Non-compliance can result in radio interference and dimmers or transfor-
mers can be destroyed. The lamps have a reduced service life.
Should a switch be series-connected with the dimmer and the load is on,
a time delay will result when switching on.
The LUXOR dimmer module functions as an independent unit. It is connected
to the LUXOR system via the 2-wire COM interface and is therefore involved
in all comfort functions such as panic function, central ON, central OFF and
presence simulation.
Only keys can be connected to inputs I 1 to I 2.
In principle, various external wires/phases can be applied to the control in-
puts and the switching outputs.
Various dimming responses can be selected using program selector switches
P1 to P4.
Key actuation differs as follows:
- short keystroke on the control button = switching
- long keystroke on the control button = dimming
- very long keystroke (> 3 sec.) on
the control button (in P3 and P4 only) = continuous light
and/or continu-
ous OFF
SS
p
Connection terminal
for movement sensor
D1
Connection terminal for
movement sensor D2
2-channel operation D1 and D2
rated at 300 VA each
1-channel operation D1 rated at 500
VA (channel 2 does not function)
When the selector switch on LUXOR 400
is in position
the LED set indicates the program status.
CLEAR key for resetting the dimmer in
the event of malfunction and on indication
of overflow/over-temperature
Channel key D1 (D2) for manual ON/OFFS
switching (manual key) and programming of
central functions
LED illuminates when a contact signal is
present at the input I .
LED illuminates when a malfunction,
overflow or over-temperature is present.
LED illuminates when the
output is switched on.
Program selector switch for
programs P1 to P4
Info: The overall length of communication connection cables
(COM/low function voltage) may be up to 100 m.
• Upgrades up to max. 16 devices inc. basic device
The central connection is via the COM interface.
All devices connected to the COM interface on the
LUXOR 400 basic device can be switched centrally.
Key inputs I 1, I 2
Control voltage 230 V~
Any external wire/phase can be connected!
Operating voltage
230 V ~,
+10 %/ -15 %
Ensure correct
polarity!
Input for 3 light
settings
310 410 03
7.0 Selection programs P1, P2, P3 and P4
S1 S2
For the 2 key dimmer
One brief keystroke on the (bright) key switches on the light on.
One brief keystroke on the (dark) key switches on the light off.
One long keystroke on the (bright) key slowly increases brightness
to 100 %.
If the key is previously released, the value that has been reached is main
tained.
A further long keystroke increases brightness to 100 %.
One long keystroke on the (dark) key reduces the brightness to
10 % and/or the minimum value (if a value has been previously set).
Program P2
Program P2 corresponds to P1, except
when switched on. In this case, the light
does not switch to 100% brightness but
to the last brightness value prior to
switching off.
After the 1st short keystroke, the (bright)
key (with 2-keys dimmer) dims to the set
value and then down to 100 % brightness
after the 2nd keystroke.
“Teaching-in” a brightness value (upper reduction value for P3)
The upper reduction value can be “taught-in“ here (in position P2), see
Section 8.
Hall
Living area
Child 1
Kitchen
Child 2
Parents
floor
Dark
For the 1 key dimmer
One brief keystroke switches on the light
to 100 %.
Pressing it again switches the light
off again.
A long keystroke dims the light.
The light is dimmed up to 100%, for exam-
ple, for as long as the key is depressed.
It is then dimmed down again. The entire process is repeated until the key
is released again.
“Teaching-in” a brightness value (minimum value in P1 to P4)
The smallest value to which the dimmer is to be set can be “taught in“ (in
P1 position), see Section 8.
4 programs P1 to P4 can be selected using the program selector switch.
Program P1
Program P1 is the standard dimming program with the following sequences:
Channel 1
Channel 2
Channel 1
Channel 2
Diode module
Light
Program P3 (stairwell function with continuous light)
Program P3 behaves like an automatic stairwell light and is identical on 1
and 2 switch dimmers. P3 runs as follows:
One keystroke switches the light on
to 100 %.
The light is maintained at 100% for 1, 2, 4
or 8 min. periods (see “Teaching-in” the
stairwell light time, Section 8).
The value is then reduced to between 40 %
and 80 %. This value is maintained for 40 sec.
P3 then switches to 30 % or the pro
grammed minimum value.
This value is maintained for 10 sec.
Program P3 switches off.
If during this process the key is pressed briefly, the
“stairwell light function” starts from the beginning.
If during this process the key is pressed for longer than 3 sec., the pro-
gram switches to continuous light (100%) and confirmation is signaled
by flashing briefly.
Channel 1
Channel 2
6.0 Connection and installation
Connecting the inputs
Input I 1 acts on output D1.
Input I 2 acts on output D2.
Input S 1 acts on output D1.
Input S 2 acts on output D2.
Important: In 1-channel operation,I 2 and S 2 do not function.
Input LS can trigger 3 independent light settings.
Ensure correct polarity!
Make the 2-wire connection between the COM interfaces.
Do not connect the inputs in parallel.
11.0 Central function
Each channel can be assigned either panic, central OFF, central ON or presen-
ce simulation as a central function. The function is possible only in combina-
tion with LUXOR 400 (see Operating Manual for LUXOR 400).
Panic
The assigned channels are switched on. They cannot be operated again until
panic is cleared.
Central OFF
The assigned channels are switched off. No further operation is possible.
Central ON
The assigned channels are switched on. Operation is now possible again.
You have the option of setting or “teaching-in” various bright-
ness values in positions P1 to P4:
1)Brightness (minimum values) in position P1
Press the manual key D1 and/or D2 for longer than 3 secs. All LEDs
illuminate; the lamp illuminates up to the previously set light value.
Set the brightness value (10 % - 40 %) with the key (not with the manual
key).
Confirm briefly with the manual key D1 and/or D2. The set value is
accepted. The LED illuminates for the output illuminates.
2)Brightness (top reduction value at 40 % - 80 %) in position P2
For operation, see description under 1)
3)Stairwell light time (1, 2, 4 or mins.) in position P3
Press the manual key D1 and/or D2 for longer than 3 secs. All LEDs illuminate.
Select the stairwell light time using the program selector switch:
P1 = 1 mind., P2 = 2 mind., P3 = 4 mind., P4 = 8 mind.
Confirm briefly with the manual key D1 and/or D2. The selected time
will be accepted. The LED illuminates for the output illuminates.
If necessary, set the program selector switch back to P3.
4)Night and/or security light (1, 2, 4 or 8 mins.) in position P4
For operation, see description under 3)
Also select the time using the program selector switch: P1 = 1 mind.,
P2 = 2 mins., P3 = 4 mins., P4 = 8 mins., as described above.
If necessary, set the program selector switch back to P4.
8.0 “Teaching-in” various brightness values
9.0 “Light setting” function (LS)
Important:
3 light settings can be “taught-in” and set; this is only possible, however, in
programs P1 and P2.
“Teaching-in” a light setting
Enter the required brightness values.
Press one of the 3 setting keys (additional keys for other light settings)
for longer than 3 sec.
The brightness values will be saved and confirmation is signaled by
flashing briefly.
Running a light setting
Briefly press one of the 3 setting keys. The channels switch to the
“taught-in” light value.
Pressing the setting key again switches the channels off.
Switch-off
in P1 => switches to 0 %.
in P2 => If 100 % was set, the last brightness value is achieved.
If no brightness value was set, the program switches to
0 %.
in P3 => starts the stairwell light function.
in P4 => starts the “timer function”.
10.0 “Movement sensor” function (S)
Switch-on
in P1, P3, P4 => switches to 100 %.
in P2 => If the light is already switched on, the brightness is in-
creased to 100 %. If the light is not switched on, the
last brightness value is achieved.
p
p
LS 1
LS 2
LS 3
Program P4
Program P4 contains a night and7or security
light.
One short keystroke increases the light to
100 % brightness.
The light is maintained at 100% for 1, 2, 4 or
8 min. periods.
A further keystroke slowly reduces the light to
10 % or to the entered minimumvalue. This value is maintained
(night and/or security light).
A further keystroke increases the brightness to 100 % again.
If while the minimum value is maintained, the key is pressed for longer
than 3 sec. the light switches off.
If - with the light switched on (100 %) - the key is pressed for longer than
3 sec. the program switches to continuous light (100 %) and confirmation
is signaled by flashing briefly.
A further brief keystroke reduces the light to the minimum value.
A “timer function” starts the switching at 100 % . When this expires, the
light is automatically reduced to the minimum value.
“Teaching-in” the timer function (in position P4), see Section 8.
Channel 1
Channel 2
The continuous light can be switched off by one short keystroke.
“Teaching-in” the stairwell light time (in position P3), see Section 8.
LS
Presence simulation (AWS)
The assigned channels are switched. Operation is now possible again.
During operation, the current brightness values of the channels are
checked and where applicable saved with the time information.
The values thus collated are saved in the device every 24 hours.
After 7 days, the old values are overwritten and resaved.
After start-up, no further values are saved; a presence simulation
sequence cannot be started until a week has lapsed.
After a RESET and/or power is restored, the presence simulation values are
maintained in the device .
12.0 Function in timer module LUXOR 414
Info:
The dimmer module LUXOR 405 can be taught-into all 8 channels of the
timer module (see Operating Manual LUXOR 414, Section 13).
Behaviour with switching time/astronomical time
The percentage value set in the timer module UXOR 414 is output.
Behaviour with switching time/astronomical time
If the sensor is taught into a channel in addition to the timer, the night-
time interruption (i.e. the idle period) acts on the dimming function rather
than on the astronomical time. Astronomical times are always used.
Central functions
- Panic function
If this function is active during a timer command, the timer command
is not used until the function is terminated.
- Presence simulation (AWS)
If this function is active during a timer command, the does not react to the
AWS taught-in channel.
Astronomical time/nighttime interruption (idle period) (see Table)
Switching time
With normal switching times, the nighttime interruption (idle time)
has no function. The switching time is always used.
Astro -
evenings
Sunset
Nighttime
interruption
Start
Nighttime
interruption
End
Astro mor-
nings
Sun
rise
Explanation
Times
Switching
16:10
ON
20:00
OFF
6:00
ON
8:10
OFF
Winter
Normal
sequence
Times
Switching
21:30
20:00
OFF
6:00
4:50
OFF
Summer
remains OFF
Times
Switching
19:30
ON
20:00
OFF
6:00
5:55
OFF
evenings only
ON
Times
Switching
20:30
20:00
OFF
6:00
ON
6:55
OFF
mornings only
ON
13.0 Function in combination with sensor modu-
Info:
The dimmer module LUXOR 405 can be taught-into the dimming channel
on the sensor module LUXOR 411 module (see Operating Manual
LUXOR 411_412 Section 10).
The dimmer module LUXOR 405 reacts only to twilight (80 secs. delay).
When the set Twilight function is underrun, the channels assigned to the
Twilight function are switched to 100 % (for programmes P1, P2 and P4,
but not P3).
When the set Twilight function is exceeded, the channels assigned to the
Twilight function are switched to 0 % (for programmes P1, P2 and P4, but
not P3).
In programme P3, the dimmer module does not react to the sensor module.
If the panic function, a motion sensor, a light setting or presence
simulation are active, the dimming module will not react to the sensor
module.
Relationship between twilight, idle time and output status
(see Table)
Twilight
Idle period
% value
(LUXOR 414)
Sensor
Channel
(LUXOR 405)
getting dark 0 % was present is disabled unchanged
getting dark >0 % was present is enabled 100 %
it is dark 0 % approaching being disabled 0 %
it is dark >0 % approaching being enabled 100 %
getting bright 0 % was present remains disabled unchanged
getting bright >0 % was present remains enabled 0 %
it is bright 0 % approaching being disabled unchanged
it is bright >0 % approaching being enabled unchanged
14.0 Technical data
Operating voltage: 230 V~, +10 % to -15 %
Mains frequency: 50 Hz
Power consumption: 3 VA
Key / switch connecting cable: 230 V phase-independent
Key / switch cable length: up to 100 m (NYM, H05/H07, NYIF)
Dimmer load cable length: up to 100 m
2-wire connection for COM: Any cross-section / max. length 100 m
Permitted ambient temperature: –10 °C ... +50 °C
Protection class: II subject to correct installation
Degree of protection: IP 20 in accordance with EN 60529
Dimmer outputs: per channel 20 ... 300 VA
for one channel: 20 ... 500 VA
Load type: Automatic detection of R, C and L load
Short circuit: the outputs are short-circuit proof (indicator )
Overtemperature: monitored with cut-out (indicator )
automatic detection of R, C loads (reverse phase control) and L load
(reverse phase control)
15.0 Dimmable loads
Load type Dimmable Load type / Dimming type Comment
Halogen lights and incandescent lamps for 230 V~ YES Reverse phase control
Low-voltage halogen lights with electronic transformer YES Reverse phase control
*
Low-voltage halogen lights with laminated core transformer YES Phase control *
(toroidal core transformers and transformers from
Block and ABB except for type series... Lv) are unsuitable
Combined operation of low-volt halogen lights with YES Reverse phase control
*
Electronic transformer and 230 V~ incandescent lamps
Toroidal transformers NO X
Metal halide lamps NO X
Energy saving lamps NO X
Fluorescent lamps NO X
Lamps with own dimmer NO X
Lamps with other electronic ballasts NO X
* Only use transformers (Tronic transformers) that are suitable or approved and are operated at the minimum load.
Theben AG
Hohenbergstr. 32
D-72401 Haigerloch
Phone +49 (0) 74 74/6 92-0
Fax: +49 (0) 74 74/6 92-150
Service
Phone +49 (0) 90 01 84 32 36
Fax: +49 (0) 74 74/6 92-207
hotline@theben.de
Addresses, telephone numbers etc. at
www.theben.de
Please note!
The 3 stars on the top of the LUXOR 405 denote
a 3rd generation device.
This means that only these devices with LUXOR
411 (sensor module) and LUXOR 414 (timer
module) can be controlled.
S1 S2
16.0 Positive list of conventional transformers
tested
Type Supplier / Power [W]
Manufacturer
mind max
LDT 60 Bürklin 45 60
LTV 250/96 TB Reichelt 180 250
LTV 300/96 Reichelt 200 300
Type 120/500 Reichelt 300 500
(LTV 500/135)
Si-TR 300-230/12 Lv ABB 250* 300
* Not stated, therefore please use 80 % of maximum value.
3

Hulp nodig? Stel uw vraag in het forum

Spelregels
1

Forum

Theben-Luxor-405

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Theben Luxor 405 bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Theben Luxor 405 in de taal/talen: Engels als bijlage per email.

De handleiding is 0,45 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

Andere handleiding(en) van Theben Luxor 405

Theben Luxor 405 Gebruiksaanwijzing - Nederlands - 5 pagina's

Theben Luxor 405 Gebruiksaanwijzing - Deutsch - 5 pagina's

Theben Luxor 405 Gebruiksaanwijzing - Français - 5 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info