593152
12
Verklein
Vergroot
Pagina terug
1/43
Pagina verder
- 22 - - 23 -
Technical Specifications
Dimensions (W x H x D): 120 x 120 x 68 mm DualTech
120 x 120 x 73 mm Single US
120 x 120 x 68 mm US 360
120 x 120 x 73 mm Dual US
Power supply: 230 – 240 V, 50 Hz / 60 Hz
Capacity, switching output 1: Relay, 230 V
(COM 1/COM 2) 2000 W max. resistive load (cos φ = 1)
1000 VA max. (cos φ = 0.5)
Electronic ballasts: Max. ON current 800 A/200 μs
(COM 1/COM 1 AP/COM 2/DIM) 30 x (1 x 18 W), 25 x (2 x 18 W)
25 x (1 x 36 W), 15 x (2 x 36 W)
20 x (1 x 58 W), 10 x (2 x 58 W)
Pay attention to specific ON currents of electronic ballasts!
A relay or contactor must be provided on line side for
higher switching capacities
Capacity, switching output 2: Presence
(COM 2 only) 230 W/230 V
1A max. (cos φ = 1) for HVAC (heating/ventilation/air-conditioning)
Detection ranges: US 360/DualTech SingleUS/Dual US
(Detection Tangential/presence (m): Ø 6 m max. (28 m
2
)
at 2.5 m / mounting Ø 2 m min. (12 m
2
)
height 2.5 m) Radial: Reach up to Ø 10 m 3 x 10 m / 3 x 20 m (30 / 60 m²) max.
3 x 2.5 m / 3 x 5 m (7.5 / 15 m²) min.
Light-level setting: 10 – 1000 lux, ∞ / daylight /
DIM 100 – 1000 lux control threshold
Switching output 1: 30 sec. – 30 min., pulse mode (approx. 2 sec.),
Time setting IQ mode (automatic adjustment to the usage profile)
Switching output 2: COM2 only, for HVAC
Time setting 0 sec. – 10 min. switch-ON delay
1 min. – 2 hrs. stay-ON time
Automatic room surveillance
DIM: 30 sec. – 30 min.,
Time setting IQ mode (automatic adjustment to the usage profile)
Control output: 1 – 10 V / 50 electronic ballasts max., 100 mA max.
Mounting height: 2.5 m – 3.5 m
(mounted to ceiling)
Point of installation: Indoors
Sensor technology:
DualTech PIR (Passive Infrared), single pyro, 11 detection levels,
520 switching zones. Ultrasonic 40 kHz
US 360 / Single US / DualTech Ultrasonic 40 kHz
IP rating: IP 20
Protection class: II
Temperature range: - 25 °C - +55 °C
DIP 4
In the ON-OFF setting, the light
can be switched ON and OFF
manually at any time (except in
pulse mode: no manual OFF).
In the ON setting, light can no
longer be switched OFF manual-
ly. The stay-ON time starts from
the beginning again each time
the button is pressed.
ON/ON-OFF button
DIP 1
Functions – Settings by DIP switch
Test mode has priority over all
other settings on the presence
detector and serves the purpose
of checking for proper working
order as well for testing the de-
tection zone. Irrespective of
ambient light level, the presence
detector activates the light to
stay ON for approx. 8 sec. in
response to movement in the
room. (blue LED flashes when
movement is detected).
All user-selected potentiometer
settings apply in normal mode.
The presence detector can also
be set by means of the blue LED
without any load connected.
Normal mode / Test mode (NORM / TEST)
DIP 2
The light automatically switches
ON and OFF in relation to light
level when someone is present.
Light can be switched ON and
OFF manually at any time. This
temporarily interrupts the auto-
matic switching function. Irre-
spective of the settings selected,
light stays ON for 4 hours after
manually pressing the button
twice or switches OFF after man-
ually pressing the button once.
Pressing the button before the
4 hours elapse returns the pres-
ence detectors to the normal
operating mode.
Semi-automatic mode (MAN) / fully automatic mode (AUTO)
Fully automatic mode: (AUTO)
Semi-automatic mode: (MAN)
The light now only switches
OFF automatically. Light is
switched ON manually.
Light must be requested using
the button and stays ON for the
time set at the potentiometer
(pressing twice switches ON for
4 hours).
DIP 3
Tells the sensor how to interpret
the incoming signal. Assigning
external buttons/switches allows
you to operate the detector as a
semi-automatic unit and over-
ride it manually at any time.
n Operation either by button or
switch
n Several buttons possible on
one control input
n Only use illuminated pushbut-
ton with neutral conductor
connected
nCable length between sensor
and switch < 50 m
Button/switch
COM 1 + COM 2
DIP 5
Provides a constant level of
brightness. Detector measures
the prevailing level of daylight
and activates sufficient artificial
light to achieve the required lev-
el of brightness. As daylight
changes, the switched-in artifi-
cial lighting component is ad-
justed accordingly. In addition to
the daylight component, artificial
light is also switched ON and OFF
in relation to whether or not per-
sons are present.
Constant light ON/OFF
DIM
d
GB
12

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Steinel US 360 bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Steinel US 360 in de taal/talen: Nederlands, Duits, Engels, Frans, Italiaans, Pools, Zweeds als bijlage per email.

De handleiding is 4,64 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info