812337
59
Verklein
Vergroot
Pagina terug
1/64
Pagina verder
Heating Controller LHCC
Heating circuit controller for heating and cooling systems
Installation and operating instructions
Read carefully before installation, commissioning and operation
CONTENT
Safety Instructions 5
EU-Conformity 5
General instructions 5
Explanation of Symbols 5
Changes to the Unit 6
Warranty and Liability 6
Disposal and Pollutants 6
Description LHCC 7
Specifications 7
About the Controller 8
Scope of Supply 8
Hydraulic Variants 9
Wall Installation 11
Installation 12
Electrical Terminals 12
Additional Information 13
External relay at signal output V(X) (0-10V / PWM) 13
Electrical Terminals 13
Electrical Connection 23
Installing the Temperature Sensors 23
Temperature Resistance Table for Pt1000 Sensors 23
Combining multiple SOREL products 23
CAN bus 23
°CALEON Room Controllers 24
RC21 Room thermostat with remote control 26
Operation 28
Display and Input 28
Commissioning help 29
1. Measurement values 29
2. Statistics 30
Today 30
28 days 30
Operating hours 30
Heat quantity 30
Graphic overview 30
Notifications 30
Reset / Clear 30
3. Periods 31
Time & Date 31
Daylight saving time 31
Heating Circuit (Day) 31
Heating Circuit Comfort 31
DHW enable 31
DHW comfort 31
4. Operating mode 32
Manual 32
Mode Circuit (X) 32
5. Settings 33
Heating Circuit (X) 33
Operating mode 33
Season switch 34
S/W Day 34
S/W Night 34
Curve 34
Day Correction 34
Night Correction 34
Comfort Temperature Boost 35
Min. Flow 35
Max. Flow 35
Reference/Actual - 35
Reference/Actual + 35
Variant 35
Heating circuit off 35
Room hysteresis 35
Buffer sensor 36
Insulation factor 36
Overload protection 36
Min. Flow cooling 36
Max. flow cooling 36
Dew Point protection 36
Dew point correction 36
Room Controller Heating Circuit (X) 36
Room Controller 38
Smart grid 1/ PV contact 38
Smart grid 2 38
Settings Domestic Hot Water (DHW) 38
Operating mode 38
Hot water minimum 38
DHW reference 38
DHW comfort 39
DHW hysteresis 39
Buffer DHW load 39
DHW priority 39
DHW sensor 39
Smart grid 1/ PV contact 39
6. Protective Functions 39
Seizing Protection 39
Frost Protection 39
Discharge Protection 40
Dew point correction 40
Pressure Monitoring 40
RPS1 / RPS2 40
RPS Min 40
RPS Max 40
Protective functions for Solar 40
System protection 40
Collector protection 40
Recooling 40
Frost Protection 41
Collector alarm 41
7. Special Functions 41
Program selection 41
Pump settings V(X) 41
Signal type 41
Profile 41
Output Signal 41
PWM / 0-10V off 41
PWM / 0-10V on 41
PWM / 0-10V max. 42
Show signal 42
Speed control 42
Variant 42
Purging time 42
Sweep time 42
Max. Speed 42
Min. Speed 42
Setpoint 42
Sensor Calibration 42
Relay functions 43
Heat quantity 43
Flow temperature sensor (X) 43
Return flow sensor 43
Glycol type 43
Glycol percentage 43
Flow rate supply flow (X) 43
Offset ∆T 43
VFS (X) 43
VFS - Position 44
Reference sensor 44
Commissioning 44
Factory Settings 44
Eco Display Mode 44
Network 44
Access Control 44
Ethernet 44
Datalogger Version 45
CAN bus ID 45
Sensor send interval 45
8. Menu Lock 46
9. Service Values 46
10. Language 46
Function overview 47
Mixer 47
Direction 47
Mixer turn time 47
Mixer off factor 47
Mixer increase 47
Mixer run time 47
Signal type 47
Cooling valve Heating circuit 1/ Heating circuit 2 47
Heating Circuit 2 47
Free Cooling 47
RFI mixer 48
Operating mode 48
Reference flow sensor 48
Tref: 48
Return flow sensor: 48
Storage sensor: 48
Direction: 48
Min off time: 48
On-time: 48
Off factor: 48
Increase: 48
Max one direction: 48
Signal type 48
Difference 48
Δ T Difference 49
DF-Source 49
Tmin Source 49
DF-Drain 49
Tmax Drain 49
Heat transfer 49
Δ T Heat transfer 49
HT Tmax 49
HT Tmin 49
Source 49
Drain 49
Thermostat 49
DHW request 50
Heating Circuit request 50
Tset 50
Hysteresis 50
Energy Saving Mode 50
Delay 50
Thermostat sensor 1 50
Thermostat sensor 2 50
Thermostat enable 50
Electric heating rod (auxiliary heating) 50
DHW request 50
HC request 50
TH Set 50
Delay 50
Hysteresis 51
Eco mode 51
Sensor 1 51
Sensor 2 51
Electric heating rod approval times 51
Anti-legionella heating rot 51
Dissipation (Cooling) 51
Tset 51
Cooling sensor 51
Delay 51
Season switch 51
Off hysteresis 51
On hysteresis 52
Cool storage 52
Buffer sensor 52
Solid fuel boiler 52
Solid fuel boiler Tmax 52
Solid fuel boiler Tmin 52
ΔT Solid fuel boiler 52
Boiler sensor of this function 52
Storage sensor 52
Solar 52
Tmin Collector 52
ΔT Solar 53
Tmax Storage 53
Starting aid 53
Purging time 53
Increase 53
Protective Functions 53
Collector 53
Solar storage 53
Solar bypass 53
Variant 53
Bypass sensor 53
Booster Pump 54
Charge time 54
Zone valve 54
Tmax storage 2 54
Solar storage 2 54
Heat exchanger 54
Heat exchanger sensor 54
Burner 54
DHW request 54
Heating Circuit request 54
Burner sensor 54
Delay 54
Burner offset 54
Eco mode (during solar charge) 54
Tmax 55
Boiler base temperature 55
Base hysteresis 55
Enable 55
Anti Legionella 55
Boiler pump 55
Boiler pump Tmin 55
Compressor 55
DHW request 55
HC request 55
Cooling request 55
Eco mode (during solar charge) 55
Heating circuit offset 55
Min heat pump runtime 56
Heat pump idle time 56
Heat pump delay 56
Storage charge pump (SLP) overshoot 56
Bivalent temperature 56
Min. outdoor temperature 56
Periods 56
Anti Legionella 56
Loading pump 56
Storage charge pump (SLP) overshoot 56
Glycol pump 56
Gylcol pump lag 56
Return flow increase 56
Return flow increase Tmin 57
Return flow increase Tmax 57
ΔT return flow 57
Return flow sensor 57
Storage sensor 57
Domestic hot water valve 57
Circulation 57
Tmin 57
Hysteresis 57
Circulation sensor 57
Circulation pause time 57
Purging time 57
Circulations periods 57
Anti Legionella 57
Error Messages 58
Error message 58
Pressure monitor 58
Pressure monitor 58
RPS-Type 58
RPS Max 58
RPS Min 58
Dehumidifier 58
Operating mode 58
Reference humidity 58
Hysteresis 58
Dehumidifier periods 59
Parallel operation 59
Parallel operation 59
Parallel to 59
Delay 59
Follow-up time 59
Remote 59
Relay status 59
Title 59
Always on 59
Anti Legionella 59
Malfunctions/Maintenance 61
Tips 62
Support Guideline 62
Appendix 62
Signal 62
Output Signal 62
PWM / 0-10V off 62
PWM / 0-10V on 62
PWM / 0-10V max. 63
Speed when „On“ 63
Example for signal settings 63
Technical data PWM and 0-10V 63
Show signal 63
Final Declaration 64
Safety Instructions
EU-Conformity
By affixing the CE mark to the unit the manufacturer declares that theLHCC conforms to the following relevant safety regulations:
lEU low voltage directive 2014/35/EU
lEU electromagnetic compatibility directive 2014/30/EU
conforms. Conformity has been verified and the corresponding documentation and the EU declaration of conformity are kept on file by the
manufacturer.
General instructions
Please read carefully!
These installation and operating instructions contain basic instructions and important information regarding safety, installation, com-
missioning, maintenance and the optimal use of the unit. Therefore these instructions must be read and understood completely by the
installation technician/specialist and by the system user before installation, commissioning and operation of the unit.
This unit is an automatic, electrical Heating circuit controller for heating and cooling systems for/inHeating system and similar applications.
Install the device only in dry rooms and under environmental conditions as described under "Technical Data".
The valid accident prevention regulations, VDE regulations, the regulations of the local power utility, the applicable DIN-EN standards and
the installation and operating instruction of the additional system components must also be observed.
Under no circumstances does the unit replace any safety devices to be provided by the customer!
Installation, electrical connection, commissioning and maintenance of the device may only be carried out by an appropriately trained spe-
cialist. Users: Make sure that the specialist gives you detailed information on the function and operation of the unit. Always keep these
instructions in the vicinity of the unit.
The manufacturer does not take over any liability for damage caused through improper usage or non-compliance of this manual!
Explanation of Symbols
Danger
Failure to observe these instructions can result in electrocution.
Danger
Failure to observe these instructions can result in serious damage to health such as scalding or life-threatening injuries.
Caution
Failure to observe these instructions can result in destruction of the unit or the system, or environmental damage.
Caution
Information which is especially importation for the function and optimal use of the unit and the system.
5
Changes to the Unit
lChanges, additions to or conversion of the unit are not permitted without written permission from the manufacturer.
lIt is likewise forbidden to install additional components that have not been tested together with the unit.
lIf it becomes clear that safe operation of the unit is no longer possible, for example because of damage to the housing, turn the Unit off
immediately.
lAny parts of the unit or accessories that are not in perfect condition must be exchanged immediately.
lUse only original spare parts and accessories from the manufacturer.
lMarkings made on the unit at the factory must not be altered, removed or made illegible.
lOnly the settings described in these instructions may be set using the Unit.
Changes to the unit can compromise the safety and function of the unit or the entire system.
Warranty and Liability
The unit has been manufactured and tested with regard to high quality and safety requirements. The unit is subject to the statutory guarantee
period of two years from the date of sale. The warranty and liability shall not include, however, any injury to persons or material damage that
is attributable to one or more of the following causes:
lFailure to observe these installation and operating instructions.
lImproper installation, commissioning, maintenance and operation.
lImproperly executed repairs.
lUnauthorised structural changes to the unit.
lUse of the device for other than its intended purpose.
lOperation above or below the limit values listed in the ‚Specifi cations‘ section.
lForce majeure.
Disposal and Pollutants
The unit conforms to the European RoHS 2011/65/EU for 2011/65/EUthe restriction of the use of certain hazardous substances in electrical
and electronic equipment.
Under no circumstances may the device be disposed of with the normal household waste. Dispose of the unit only at appropriate
collection points or ship it back to the seller or manufacturer.
6
Description LHCC
Specifications
Model LHCC Heating Controller
Temperature controller class VI
Energy efficiency 4%; When operating at min. 3 ° CALEONs or RC20
a energy efficiency of 5% is achieved
Standby loss 0,5 W
Request type heater On / off operation or modulating
Electrical specifications:
Power supply 100 - 240VAC,50 - 60 Hz
Power consumption / standby 0.5 - 2.5 W/0,5 W
Total switched power 2 A
Switched power per relay 460VA
Internal fuse 1 2 A slow 250V
Protection Class IP40
Protection class / overvoltage category II / II
Inputs/Outputs Measuring range
Sensor inputs 6 Pt1000 -40 °C ... 300 °C
Sensor inputs VFS 2Grundfos Direct Sensor 0°C-100°C (-25°C /120°C short term)
Outputs mechanical relay 4
of relay potential free R4 1
Mechanical relay R1 - R4 460VA for AC1 / 460VA for AC3
0-10V/PWM output V1 - V2 for 10 k Ω working resistance 1 kHz, level 10 V
+ Terminal/
Voltage output
+Max. load by external devices 24V/6W (e.g. power supply of 3
°CALEON room controllers)
Max. cable length
VFS/RPS sensors < 3 m
CAN < 3 m; at >= 3 m, a shielded twisted pair cable must be used. Isolate
shielding and connect it to the protective conductor of only one of the
devices. Max. cable length of the complete system 200 m.
0-10V/PWM < 3 m
24 VDC < 30 m
mechanical relay < 10 m
Interface
Fieldbus CAN
Permissible Ambient Conditions
for controller operation 0 °C - 40 °C, max. 85 % rel. humidity at 25 °C
for transport/storage 0 °C - 60 °C, no moisture condensation permitted
Other Specifications and Dimensions
Housing Design 2-part, ABS plastic
Installation Methods Wall installation, optionally panel installation
Overall dimensions 163 mm x 110 mm x 52 mm
Aperture installation dimensions 157 mm x 106 mm x 31 mm
Display Fully graphical display, 128 x 64 dots
Light diode multicolour
Real Time Clock RTC with 24 hour power reserve
Operation 4 entry keys
7
About the Controller
The Heating circuit controller for heating and cooling systems LHCC facilitates efficient use and function control of your Heating system pos-
sible while its handling is intuitive. After every input step the suitable functions are matched to the keys and explained in a text above. In the
menu 'measurement values and settings' are help text and graphics in addition to key words.
The LHCC can be used for the various system variants.
Important characteristics of the LHCC are:
lDepiction of graphics and texts using a lit display.
lSimple viewing of the current measurement values.
lStatistics and system monitoring by means of statistical graphics
lExtensive setting menus with explanations.
lMenu block can be activated to prevent unintentional setting changes.
lResetting to previously selected values or factory settings.
Scope of Supply
lHeating ControllerLHCC
l3 screws 3,5 x 35 mm and 3 plugs 6 mm for wall installation.
lLHCC Installation and operating instructions
Optionally contained depending on design/order:
lOutdoor sensor: TA55 (87005)
lEthernet connection: optionally possible via datalogger (77701)
lPt1000 temperature sensor: e.g. TR / S2 (81220)
lRoom Controller: °CALEON (70001) / °CALEON Clima (70002)
lCAN Bus Accessories: e.g. CAN Connection kit 1.00m (89211)
8
Hydraulic Variants
The following illustrations should be regarded only as schematic representations of the respective hydraulic systems and do not claim to be complete. Under no cir-
cumstances should the controller replace any safety devices. Depending on the specific application, additional system and safety components such as check
valves, non-return valves, safety temperature limiters, scalding protectors, etc., may be required.
Heating circuit and burner Mixed heating circuit Mixed PWM heating circuit
Mixed heating circuit and burner Mixed heating circuit, burner
and solar Mixed heating circuit and heat
pump
Mixed heating circuit, heat pump and
solar
mixed heating circuit and solid fuel
solid fuel boiler
Mixed heating circuit, heat pump
and cooling function
2 heating circuits, combined water
tank, DHW-valve and burner
Mixed heating circuit, unmixed heat-
ing circuit
and burner
Mixed heating circuit, DHW-valve
and burner
2 mixed PWM heating circuit Mixed PWM-Hc, DHW, solar, burner
and zone valve
Mixed heating circuit and
combination storage
9
Mixed PWM heating circuit and solid
fuel boiler
Mixed heating circuit, solid fuel boiler,
and burner
Mixed heating circuit, DHW and
Heat transfer
Mixed heating circuit, DHW and heat
transfer
Mixed PWM heating circuit, DHW, and
heat transfer
Mixed heating circuit, DHW,
heat transfer and burner
Mixed heating circuit, DHW, heat trans-
fer and heat pump
Mixed heating circuit with unmixed
heating circuit, solid fuel boiler
Heating circuit and burner
Mixed heating circuit and burner Heating circuit, burner and DHW load-
ing pump
Mixed PWM heating circuit, burner
and DHW loading pump
10
Wall Installation
1. Unscrew cover screw completely.
2. Carefully pull upper part of housing from lower part. During the
removal, the brackets are released as well.
3. Set upper part of housing aside. Do not touch the electronics.
4. Hold the lower part of the housing in the selected position and
mark the 3 mounting holes. Make sure that the wall surface is as
even as possible so that the housing does not become distorted
when screwed on.
5. Using a drill and size 6 bit, drill three holes at the points marked
on the wall and push in the plugs.
6. Insert the upper screw and screw it in lightly.
7. Fit the upper part of the housing and insert the other two screws.
8. Align the housing and tighten the three screws.
1. Open the terminal cover.
2. Strip lines a max. of 55 mm, assemble the strain reliefs, strip wire
ends 8-9 mm.
3. Open clamps with a fitting screwdriver and connect electrical sys-
tem to the controller.
4. Clip on the terminal cover again and close it with the screw.
5. Turn on mains supply and put the controller into operation.
If problems occur with the operation of the terminals, our video on our YouTube page can help you:
http://www.sorel.de/youtube
11
Installation
Electrical Terminals
Low voltages
max. 24 VAC / DC
Mains voltages
230 VAC 50 - 60 Hz
Terminal: Connection for:
- GND bridge on the lower ground terminal block
S1 Temperature Sensor 1
S2 Temperature Sensor 2
S3 Temperature Sensor 3
S4 Temperature Sensor 4
S5 Temperature Sensor 5
V1 0-10V / PWM signal output e.g. for controlling high-effi-
ciency pumps
V2 0-10V / PWM signal output e.g. for controlling high-effi-
ciency pumps
S6 Temperature Sensor 6 (outdoor)
+ Terminal/
Voltage out-
put
24V voltage output
Max. load by external devices 24V / 6W
The connection of the ground wire is made at the lower gray terminal
block.
Terminal: Connection for:
N Neutral conductor N
L Network outer conductor L
R1 Relays 1
R2 Relays 2
R3 Relays 3
R4| Relay 4 | (potential-free contact)
R4 Relay 4 (potential-free contact)
The neutral conductor N must be connected to the N terminal
block.
The PE protective conductor must be connected
to the PE metal terminal block!
For high-efficiency pumps with 0-10V / PWM sig-
nal input, the power can be provided (V1 /V2 par-
allel operation) over a free relay.
On the control board
VFS1 Grundfos Direct Sensor "Connection of PWM pumps"
PWM pumps are connected to the controller with 2 wires 1)
PWM Input (default: brown) 2) GND (default: blue). Some pumps
have a third wire (PWM Output Signal (default: black)). This is
not used for the connection!
VFS2 Grundfos Direct Sensor
CAN CAN bus connection (1=high,2=low)
CAN CAN bus connection (1=high,2=low)
12
Additional Information
External relay at signal output V(X) (0-10V / PWM)
With the help of an external relay (art. no. 77502), a 0-10V/PWM output
V(X) (V1, V2) can be used to obtain a switching capacity of 230 VAC (I)
or a potential-free change-over contact (II). The external relay is then
activated via the signal output (0V = "off" (0 VAC or open or closed), 10V
= "on" (230VAC or closed or open).
1. Connect external 0-10V relay to signal output, e.g. V1.
2. Assign additional function to signal V1. See " Relay functions " on
page 43
3. Disable the speed control for the corresponding 0-10V / PWM output
(Off). See " Variant " on page 42
Electrical Terminals
For high-efficiency pumps with 0-10V / PWM signal input, the power can be provided (V1 /V2 parallel operation) over a free
relay.
The connection of the ground wire is made at the lower gray terminal block. The neutral conductor N is connected to terminal
block N. The PE protective conductor must be connected to the PE metal terminal block!
Program 1 heating circuit and burner
Terminal: Connection: Terminal: Connection:
- GND N Neutral con-
ductor N
S2 Buffer sensor L Network outer
conductor L
S5 Flow sensor R1 Heating cir-
c.pump/ Cir-
culation pump
S6 Outdoor sensor R4| Burner
+24V 24V voltage output
Max. external devices 24V/6W
R4 Burner
13
Program 2 mixed heating circuit
Terminal: Connection: Terminal: Connection:
- GND N Neutral con-
ductor N
S2 Buffer sensor L Network outer
conductor L
S5 Flow sensor R1 Heating cir-
c.pump/ Cir-
culation pump
S6 Outdoor sensor R2 Mixer open
+24V 24V voltage output
Max. external devices 24V/6W
R3 Mixer close
Program 3 mixed PWM heating circuit
Terminal: Connection: Terminal: Connection:
- GND N Neutral con-
ductor N
S2 Buffer sensor L Network outer
conductor L
S5 Flow sensor R1 Heating cir-
c.pump/ Cir-
culation pump
V1 PWM Mixer (external power
supply)
S6 Outdoor sensor
+24V 24V voltage output
Max. external devices 24V/6W
Program 4 mixed heating circuit and burner
Terminal: Connection: Terminal: Connection:
- GND N Neutral con-
ductor N
S2 Buffer sensor L Network outer
conductor L
S5 Flow sensor R1 Heating cir-
c.pump/ Cir-
culation pump
S6 Outdoor sensor R2 Mixer open
+24V 24V voltage output
Max. external devices 24V/6W
R3 Mixer close
R4| Burner
R4 Burner
14
Program 5 mixed heating circuit, burner and solar
Terminal: Connection: Terminal: Connection:
- GND N Neutral conductor N
S1 Solar storage sensor L Network outer con-
ductor L
S2 Buffer sensor R1 Heating circ.pump/
Circulation pump
S4 Collector sensor R2 Mixer open
S5 Flow sensor R3 Mixer close
V1 Solar pump (external
power supply)
R4| Burner
S6 Outdoor sensor R4 Burner
+24V 24V voltage output
Max. external devices
24V/6W
Program 5 mixed heating circuit and heat pump
Terminal: Connection: Terminal: Connection:
- GND N Neutral con-
ductor N
S2 Buffer sensor L Network outer
conductor L
S5 Flow sensor R1 Heating cir-
c.pump/ Cir-
culation pump
S6 Outdoor sensor R2 Mixer open
+24V 24V voltage output
Max. external devices
24V/6W
R3 Mixer close
R4| Compressor
R4 Compressor
Program 7 mixed heating circuit, heat pump and solar
Terminal: Connection: Terminal: Connection:
- GND N Neutral conductor N
S1 Solar storage sensor L Network outer con-
ductor L
S2 Buffer sensor R1 Heating circ.pump/
Circulation pump
S4 Collector sensor R2 Mixer open
S5 Flow sensor R3 Mixer close
V1 Solar pump (external
power supply)
R4| Compressor
S6 Outdoor sensor R4 Compressor
+24V 24V voltage output
Max. external devices
24V/6W
15
Program 8 mixed heating circuit and solid fuel boiler
Terminal: Connection: Terminal: Connection:
- GND N Neutral con-
ductor N
S2 Buffer sensor L Network outer
conductor L
S4 Sensor solid fuel boiler R1 Pump
S5 Flow sensor R2 Mixer open
S6 Outdoor sensor R3 Mixer close
+24V 24V voltage output
Max. external devices 24V/6W
R4| Solid fuel boiler
R4 Solid fuel boiler
Program 9 mixed heating circuit, heat pump and cooling function
Terminal: Connection: Terminal: Connection:
- GND N Neutral conductor
N
S2 Buffer sensor L Network outer con-
ductor L
S4 Buffer sensor 2 R1 Heating circ.pump/
Circulation pump
S5 Flow sensor R2 Mixer open
V1 Season switch R3 Mixer close
S6 Outdoor sensor R4| Compressor
+24V 24V voltage output
Max. external devices 24V/6W
R4 Compressor
Program 10 2 heating circuits, combined storage, DHW valve and burner
Terminal: Connection: Terminal: Connection:
- GND N Neutral conductor
N
S2 Buffer sensor L Network outer con-
ductor L
S3 DHW sensor R1 Heating circ.pump/
Circulation pump
heating circuit 2
S4 Flow sensor heating circuit 2 R2 Heating circ.pump/
Circulation pump
heating circuit 1
S5 Flow sensor heating circuit 1 R3 DHW valve
S6 Outdoor sensor R4| Burner
+24V 24V voltage output
Max. external devices 24V/6W
R4 Burner
16
Program 11 mixed heating circuit, unmixed heating circuit and burner
Terminal: Connection: Terminal: Connection:
- GND N Neutral conductor
N
S2 Buffer sensor L Network outer con-
ductor L
S4 Flow sensor heating circuit 2 R1 Heating circ.pump/
Circulation pump
heating circuit 1
S5 Flow sensor heating circuit 1 R2 Mixer open
V1 Heating circ.pump/
Circulation pump heating cir-
cuit 2
R3 Mixer close
S6 Outdoor sensor R4| Burner
+24V 24V voltage output
Max. external devices 24V/6W
R4 Burner
Program 12 mixed heating circuits, DHW valve and burner
Terminal: Connection: Terminal: Connection:
- GND N Neutral conductor
N
S2 Buffer sensor L Network outer con-
ductor L
S3 DHW sensor R1 Heating cir-
c.pump/ Cir-
culation pump
S5 Flow sensor R2 Mixer open
V1 DHW valve (via external relay) R3 Mixer close
S6 Outdoor sensor R4| Burner
+24V 24V voltage output
Max. external devices 24V/6W
R4 Burner
Program 13 2 mixed PWM heating circuits
Terminal: Connection: Terminal: Connection:
- GND N Neutral conductor N
S2 Buffer sensor L Network outer con-
ductor L
S4 Flow sensor heating cir-
cuit 2
R1 Heating circ.pump/ Cir-
culation pump heating
circuit 2
S5 Flow sensor heating cir-
cuit 1
R2 Heating circ.pump/ Cir-
culation pump heating
circuit 1
V1 PWM mixer heating cir-
cuit 1 (external power sup-
ply)
V2 PWM mixer heating cir-
cuit 2 (external power sup-
ply)
S6 Outdoor sensor
+24V 24V voltage output
Max. external devices
24V/6W
17
Program 14 mixed PWM heating circuit, DHW, solar, burner and zone
valve
Terminal: Connection: Terminal: Connection:
- GND N Neutral conductor N
S1 Solar storage sensor L Network outer conductor
L
S2 Buffer sensor R1 Heating circ.pump/ Cir-
culation pump
S3 DHW sensor R2 Solar pump
S4 Collector sensor R3 DHW valve
S5 Flow sensor R4| burner
V1 PWM Mixer (external
power supply)
R4 burner
S6 Outdoor sensor
+24V 24V voltage output
Max. external devices
24V/6W
Program 15 mixed heating circuit, and combination storage
Terminal: Connection: Terminal: Connection:
- GND N Neutral conductor N
S2 Buffer sensor L Network outer con-
ductor L
S3 DHW sensor R1 Heating circ.pump/ Cir-
culation pump
S5 Flow sensor R2 Mixer open
S6 Outdoor sensor R3 Mixer close
+24V 24V voltage output
Max. external devices
24V/6W
R4| DHW-pump
R4 DHW-pump
Program 16 mixed PWM heating circuit and storage
Terminal: Connection: Terminal: Connection:
- GND N Neutral conductor N
S2 Buffer sensor L Network outer conductor
L
S3 DHW sensor R1 Heating circ.pump/ Cir-
culation pump
S5 Flow sensor R2 DHW-pump
V1 PWM mixer
S6 Outdoor sensor
+24V 24V voltage output
Max. external devices
24V/6W
18
Program 17 mixed heating circuit, storage and burner
Terminal: Connection: Terminal: Connection:
- GND N Neutral con-
ductor N
S2 Buffer sensor L Network outer
conductor L
S3 DHW sensor R1 Heating cir-
c.pump/ Cir-
culation pump
S5 Flow sensor R2 Mixer open
V1 DHW-pump R3 Mixer close
S6 Outdoor sensor R4| Burner
+24V 24V voltage output
Max. external devices 24V/6W
R4 Burner
Program 18 unmixed heating circuit, DHW and storage transfer
Terminal: Connection: Terminal: Connection:
- GND N Neutral con-
ductor N
S2 Buffer sensor L Network outer
conductor L
S3 DHW sensor R1 Heating cir-
c.pump/ Cir-
culation pump
S5 Flow sensor R2 DHW-pump
S6 Outdoor sensor
+24V 24V voltage output
Max. external devices 24V/6W
Program 19 mixed heating circuit, DHW and storage transfer
Terminal: Connection: Terminal: Connection:
- GND N Neutral con-
ductor N
S2 Buffer sensor L Network outer
conductor L
S3 DHW sensor R1 Heating cir-
c.pump/ Cir-
culation pump
S5 Flow sensor R2 Mixer open
S6 Outdoor sensor R3 Mixer close
+24V 24V voltage output
Max. external devices 24V/6W
R4| DHW-pump
R4 DHW-pump
19
Program 20 mixed PWM heating circuit, DHW and storage transfer
Terminal: Connection: Terminal: Connection:
- GND N Neutral con-
ductor N
S2 Buffer sensor L Network outer
conductor L
S3 DHW sensor R1 Heating cir-
c.pump/ Cir-
culation pump
S5 Flow sensor R2 DHW-pump
V1 PWM mixer
S6 Outdoor sensor
+24V 24V voltage output
Max. external devices 24V/6W
Program 21 mixed heating circuit, DHW, storage transfer and burner
Terminal: Connection: Terminal: Connection:
- GND N Neutral conductor
N
S2 Buffer sensor L Network outer con-
ductor L
S3 DHW sensor R1 Heating circ.pump/
Circulation pump
S5 Flow sensor R2 Mixer open
V1 DHW-pump R3 Mixer close
S6 Outdoor sensor R4| Burner
+24V 24V voltage output
Max. external devices 24V/6W
R4 Burner
Program 22 mixed heating circuit. DHW, storage transfer and heat pump
Terminal: Connection: Terminal: Connection:
- GND N Neutral conductor
N
S2 Buffer sensor L Network outer con-
ductor L
S3 DHW sensor R1 Heating circ.pump/
Circulation pump
S5 Flow sensor R2 Mixer open
V1 DHW-pump R3 Mixer close
S6 Outdoor sensor R4| Compressor
+24V 24V voltage output
Max. external devices 24V/6W
R4 Compressor
20
Program 23 mixed heating circuit, unmixed heating circuit and burner
Terminal: Connection: Terminal: Connection:
- GND N Neutral conductor
N
S2 Buffer sensor L Network outer con-
ductor L
S3 DHW sensor R1 Heating circ.pump/
Circulation pump
S4 Flow sensor R2 Boiler pump
S5 Flow sensor R3 DHW valve
V1 PWM mixer R4| Burner
S6 Outdoor sensor R4 Burner
+24V 24V voltage output
Max. external devices 24V/6W
Program 24 heating circuit and burner
Terminal: Connection: Terminal: Connection:
- GND N Neutral con-
ductor N
S5 Flow sensor L Network outer
conductor L
S6 Outdoor sensor R1 Heating cir-
c.pump/ Cir-
culation pump
+24V 24V voltage output
Max. external devices 24V/6W
R4| Burner
R4 burner
Program 25 mixed heating circuit and burner
Terminal: Connection: Terminal: Connection:
- GND N Neutral conductor
N
S5 Flow sensor L Network outer con-
ductor L
S6 Outdoor sensor R1 Heating circ.pump/
Circulation pump
+24V R3 Mixer
R4| Burner
R4 burner
21
Program 26 heating circuit, burner and DHW loading pump
Terminal: Connection: Terminal: Connection:
- GND N Neutral con-
ductor N
S3 DHW sensor L Network outer
conductor L
S5 Flow sensor R1 Heating cir-
c.pump/ Cir-
culation pump
S6 Outdoor sensor R2 DHW-pump
+24V 24V voltage output
Max. external devices 24V/6W
R4| Burner
R4 Burner
Program 27 mixed heating circuit, burner and DHW loading pump
Terminal: Connection: Terminal: Connection:
- GND N Neutral conductor
N
S3 DHW sensor L Network outer con-
ductor L
S5 Flow sensor R1 Heating circ.pump/
Circulation pump
V1 PWM mixer R2 DHW-pump
S6 Outdoor sensor R4| Burner
+24V 24V voltage output
Max. external devices 24V/6W
R4 Burner
22
Electrical Connection
Before working on the unit, switch off the power supply and secure it against being switched on again! Check that there is no
power flowing! Electrical connections may only be made by a specialist and in compliance with the applicable regulations. The
unit may not be put into operation if there is visible damage to the housing, e.g. cracks.
The unit may not be accessible from behind.
Low-voltage cables such as temperature sensor cables must be routed separately from mains voltage cables. Feed tem-
perature sensor cables only into the left-hand side of the unit, and mains voltage cables only into the right-hand side.
The customer must provide an all-pole disconnecting device, e.g. an emergency heating switch.
The cables being connected to the unit must not be stripped by more than 55 mm, and the cable jacket must reach into the hous-
ing just to the other side of the strain relief.
Installing the Temperature Sensors
The controller operates with Pt1000 temperature sensors which are accurate to 1 °C, ensuring optimal control of system functions.
If desired, the sensor cables can be extended to a maximum of 30 m using a cable with a cross-section of at least 0.75 mm².
Ensure there is no contact resistance! Position the sensor precisely in the area to be measured! Only use immersion, pipe-
mounted or flat-mounted sensors suitable for the specific area of application with the appropriate permissible temperature
range.
Low-voltage cables such as temperature sensor cables must be routed separately from mains voltage cables. Feed tem-
perature sensor cables only into the left-hand side of the unit, and mains voltage cables only into the right-hand side.
Temperature Resistance Table for Pt1000 Sensors
°C -20 -10 0 10 20 30 40 50 60 70 80 90 100
Ω 922 961 1000 1039 1077 1116 1155 1194 1232 1270 1308 1347 1385
Combining multiple SOREL products
SOREL devices with CAN Bus such as HCC controller, Datalogger or °CALEON Room Controller can be networked to communicate with
each other and intelligently control larger systems.
CAN bus
1. The CAN devices are connected in series with the CAN bus cable.
2. The first and last CAN device in this connection in series must be fitted with terminating
resistance.
The wiring of the two CAN sockets is arbitrary.
23
°CALEON Room Controllers
°CALEON is an optional accessory and is normally not included in the scope of supply.
Accessories
Each °CALEON comes with an accessory bag that contains everything (except the CAN cable) needed to connect to an HCC. The following
components are used for the electrical connection:
1. Molex adapter for the CAN connection
2. Single wire connector to easily connect the Molex adapter to the CAN cable
3. Terminating resistor for the 2nd CAN bus connection on the HCC (if it is not used).
Can cable: <3m; at >=3m a shielded, twisted-pair cable is to be used. Isolate shielding and connect it to the protective conductor
on one end. Max. cable length of the complete system 200 m.
Wiring
Cable strip off max. 55 mm, insulate all wire ends 8-9 mm and
insert shielding over the cable. Insulate the entire shielding with
tape.
Wire ferrules made of brass can be difficult to clamp due to their asymmetric crimping shape. In this case, remove the wire fer-
rule. The plug-in terminals are also suitable for flexible cables.
Any contact between protective conductor and circuit board can cause serious damage.
Wiring of a °CALEON with controller
When connecting the CAN-Bus cable, make sure that the correct pairs of wires are twisted. The assignment is identical to the
terminal pairs on the °CALEON room controller.
-> GND + 24VDC
-> CAN Low + CAN High
Wiring of several °CALEONs with controller
The 24V power supply of the LHCC is designed for a load of up to 6W. This can supply 3 °CALEON room controllers. For loads
> 6W, an external power supply must be used.
24
Configuration
First, the °CALEON must be set up directly on the room controller. The automatic start-up wizard (Overview > Operating Mode > Menu >
Expert > Factory Settings) and the °CALEON user manual will help you.
If not already done, set up the HCC now with the help of the commissioning wizard.
The setup of the room controller is done in the following menu:
5. Settings -> 5.1. Heating circuit 1 - > 5....24. Room controller
5....1. Thermostat
Here, you select the room created in °CALEON. The rooms represented by symbols in °CALEON are given written names in the HCC. The
assignment can be found in the following table.
Bathroom Children 3 Room 2
Bathroom 2 Corridor Room 3
Bathroom 3 Corridor 2 Room 4
25
Bathroom 4 Dining Room 5
Bedroom Kitchen Room 6
Bedroom 2 Living Room 7
Bedroom 3 Office Room 8
Children Office 2 Room 9
Children 2 Room 1 Room 10
5....12. Room controller
This value can be adjusted as to the amount of influence the room temperature will have on the reference flow temperature, as a percentage.
For each degree deviation between room temperature and reference temperature, the percentage of the calculated set flow temperature set
here is added to the set flow temperature or subtracted from it up to the min. or max. values set under the protective functions.
Example: Reference room temp.: e.g. 25 °C; room temp.: e.g. 20 °C ±5 °C. Calculated reference temp.: e.g. 40 °C: room controller: 10 %= 4
°C 5 X 4 °C= 20 °C. Accordingly, 20 °C are added to the reference flow temperature, giving 60 °C. If the value is higher than the one set in
"Max. flow temp", the resulting temperature will be the one set in "Max. flow temp".
The setting parameters "5....13. Room ref. day“ and "5....14. Room ref. night" have no influence, when using a °Caleon and can
be ignored.
Under "5…2. Thermostat" further °CALEONs can be set optionally as room controllers. The same system as for the first room controller
applies.
5. Settings -> 5.1. Heating circuit 1 -> 5.15. Heating circuit off
If you want the heating circuit to switch off in addition to summer-winter shutdown, even if the room temperature is reached, set "summer +
room" here.
RC21 Room thermostat with remote control
The RC21 room thermostat is an optional accessory and is normally not included in the scope of supply.
The remote control with integrated thermostat RC21 provides you with easy to use temperature controlled adjustment of the temperature
from within your living space.
Setting options
The RC21 control dial parallel shifts the heating circuit characteristic stored in the controller. The flow temperature (depending the outdoor
temperature) is increased or decreased respectively by this. When the dial is turned all the way down, the heat circuit is switched off. Frost
protection stays active to prevent damage.
Temperature Sensors
The RC21 room thermostat has a built-in temperature sensor, the values of which are registered, used and displayed in the controller. If the
settings in the controller allow it, the sensor is used to alter the flow temperature.
Operating Modes
The slider can be moved to the following operating modes.
In automatic mode, the temperature is controlled according to the set thermostat periods.
In continuous day mode, the set times are ignored and the temperature is controlled according to the day settings.
In continuous night mode, the temperature is usually reduced. This setting is suitable, for example, for periods of prolonged absence
(e.g. holidays).
Installation
Carefully remove the dial from the housing with a screwdriver. Loosen
the screw beneath. Remove the light-coloured part of the housing from
the base.
The RC21 is connected to the controller via 3 wires.
The following picture shows exemplary wiring.
26
1) Remote control -> to a free sensor input (S1-S6)
2) Temperature sensor -> to a free sensor input (S1-S6)
3) GND
The setup of the room controller is done in the following menu:
5. Settings -> 5.1. Heating circuit 1 -> 5.24. Room controller
5....1. Thermostat
Select "RC21-Local 1".
5....10. RC 1 Temp 1
Select here the sensor input that you use for the temperature sensor (Terminal 1) of the RC21.
5....11. RC 1 contr.
Select here the sensor input that you use for the remote control (Terminal 2) of the RC21.
"5....13. Room ref. day“ / "5....14. Room ref. night"
Setting the desired room temperature for day/night operation.
5....12. Room Controller
This value is used to appoint the amount of influence the room temperature has on the reference flow temperature, as a percentage. For
each degree deviation between room temperature and reference temperature, the percentage of the calculated set flow temperature set
here is added to the set flow temperature or subtracted from it up to the min. or max. values set under the protective functions.
Example: Reference room temp.: 25 °C; room temp.: 20 °C = 5 °C deviation. Calculated reference flow temp.: 40 °C: room controller: 10
%= 4 °C 5 X 4 °C= 20 °C. Accordingly, 20 °C are added to the reference flow temperature, giving 60 °C. If the value is higher than the one
set in "Max. flow temp", the resulting temperature will be the one set in "Max. flow temp".
Under "5....2. Thermostat" further °CALEONs can be set optionally as room controllers. The same system as for the first room controller
applies.
5. Settings -> 5.1. Heating circuit 1 -> 5.15. Heating circuit off
If you want the heating circuit to switch off in addition to summer-winter shutdown, even if the room temperature is reached, set "summer +
room" here.
The RC21 is suited for low voltage only!
27
Operation
Display and Input
Further symbols can be found in the special functions
Examples for key settings:
+/- Increase / decrease values
▼/▲ Scroll menu down / up
Yes/No agree / reject
About further information
Back to the previous display
Ok Confirm selection
Confirm Confirm setting
The display‘s (1), extensive text and graphical mode, enables simple,
almost self-explanatory, operation of the controller.
The LED (2) lights up green when the primary pump is switched on
(automatic mode). The LED (2) lights up red when operating mode
‚Off‘ is set. The LED (2) flashes quickly red when an error is present.
The function of the other 3 keys (4) is shown in the display right above
the keys. The right-hand key generally has a confirmation and selec-
tion function.
The graphics mode appears if not key is pressed for 2 minutes or after
exiting the main menu with ‘esc’.
The temperature overview appears when you press the.
left button. Tapping the button again leads back to
The graphic overview.
Hitting the "esc" key in the graphics mode takes you directly to the
main menu.
28
Commissioning help
1. Set language and time
2. Commissioning help / setup wizard
a) select or
b) skip.
The setup wizard guides through the necessary basic settings in the correct
order. Every parameter is explained on the display of the controller. Pressing the
„esc“ key takes you back to the previous setting.
b) With free commissioning the settings should be made in the following order:
lmenu 10. Language
lmenu 3. Time, Date and Operating Times.
lMenu 5. Settings, all values
lmenu 6. Protection Functions (if any adjustments necessary).
lmenu 7. Special Functions (if any adjustments necessary).
3. In menu operating mode "4.1. Manual”, test the witch outputs with the con-
sumers connected and check the sensor values for plausibility. Then set to auto-
matic mode.See " Manual " on page 32
The setup wizard can be accessed in menu 7.2 at any time.
Consider the explanations for the individual parameters on the following pages and check if further settings are necessary for
your application.
1. Measurement values
Serve to display the current measured temperatures.
If ‚error‘ appears on the display instead of the measurement value,
there may be a defective or incorrect temperature sensor.
If the cables are too long or the sensors are not well-placed, small devi-
ations in the measurement values may occur. In this case, the display
values can be compensated by adjustments in the controller See "
Sensor Calibration " on page 42. The selected program, connected
sensors and the specific model design determine which measurement
values are displayed.
29
2. Statistics
Serve for function control and long-term monitoring of the system.
For time-dependent functions such as circulation and anti-legionella and
the evaluation of system data, it is essential that the time is accurately set
on the controller. Please note that the clock continues to run for about 24
hours if the mains voltage is interrupted, and afterward must be reset.
Improper operation or an incorrect time may result in data being cleared,
recorded incorrectly or overwritten. The manufacturer accepts no liability
for the recorded data!
Today
Flow temperature of the last 24 hours
In the graphical overview the characteristics of the flow for the present day is shown from 0 ... 24 h. The right button changes the unit of time
(days) and the two left buttons scroll through the diagram.
28 days
Flow temperature during the last 28 days
In the graphical overview the characteristics of the flow temperature during the last 28 days is shown. The right button changes the unit of
time (days) and the two left buttons scroll through the diagram.
Operating hours
Here the operating hours of the heating circuit and other switch or signal outputs are displayed. This is the entire time the heating circuit pump
and other switch or signal outputs were active. The displayed date in this menu is the date of the last deletion. From this date on the current
count is added.
Heat quantity
Display of the consumed heat quantity form the system in kWh.
This is an indicative value.
Graphic overview
This results in a clear illustration of the data as a bar graph. Different time ranges are available for comparison. You can page through with the
two left keys.
Notifications
Display of the last 20 errors in the system with indication of date and time.
Reset / Clear
Resetting and clearing the selected statistics. Selecting ‚all statistics‘ clears everything except the messages.
30
3. Periods
Settings for time, date and operating times for the heating circuit.
The associated temperature reference values are spe-
cified in Menu 5, ‚Settings‘.
Time & Date
Serve to set the current time and date.
For time-dependent functions such as circulation and anti-legionella and the evaluation of system data, it is essential that the
time is accurately set on the controller. Please note that the clock continues to run for about 24 hours if the mains voltage is
interrupted, and afterward must be reset. Improper operation or an incorrect time may result in data being cleared, recorded
incorrectly or overwritten. The manufacturer accepts no liability for the recorded data!
Daylight saving time
If this function is activated, the controller automatically changes to winter time or summer time (DST, Daylight Savings Time).
Heating Circuit (Day)
This menu is used to select the daytime mode times for the heating circuit; three time periods can be specified for each weekday and
copied to the following days.
Unspecified times are automatically considered to be night-time mode. The set times are only taken into account in the ‚Auto-
matic‘ heating circuit operating mode.
Heating Circuit Comfort
This menu can be used to select three time ranges for each day of the week in which the heating circuit is supplied with an increased com-
fort temperature, e.g. for quick heating in the morning.
DHW enable
In this menu, the approval times for the DHW load (sensor S3) are selected, whereby for every weekday 3 periods can be determined and
copied in the following days.
In times that are not filled, the DHW load is automatically shut down by the controller.
DHW comfort
This menu can be used to select three time ranges for each day of the week in which the DHW is supplied with an increased comfort tem-
perature.
31
4. Operating mode
To specify the operating modes for the heating circuit. After an interruption of the
mains voltage, the controller automatically returns to the last operating mode selected.
Only in automatic mode does the controller use the set operating times and
the correspondingly set target flow temperatures!
Manual
The individual relay outputs, v outputs and the connected consumers can be checked for proper functioning and correct assignment.
The operating mode ‚Manual‘ may only be used by specialists for brief function tests, e.g. during commissioning! Function in
manual mode: The relays and thus the connected consumers are switched on and off by pressing a key, with no regard to the cur-
rent temperatures and set parameters. At the same time, the current measurement values of temperature sensors are also shown
in the display for the purposes of function control.
Mode Circuit (X)
Sets the heating circuit mode.
Off
"Off" switches off the heating circuit completely. The heating circuit is only switched on again by changing the operating mode directly on the
controller or via the optional internet application "SOREL Connect".
Changes to room controllers in "off" mode have no influence on the heating circuit operation.
Heating
"Heating" switches the heating circuit to normal heating mode.
Changes to room controllers or via "SOREL Connect" affect the heating circuit operation.
Cooling
If the heating circuit is in "Heating and Cooling" Mode (5. Settings -> 5.1. Heating Circuit 1 -> Operating Mode), manual seasonal change of
the heating circuit can be effected by selecting the mode "Cooling".
Changes to room controllers or via "SOREL Connect" affect the heating circuit operation.
32
5. Settings
The basic settings for the control function of the heating circuit are applied.
Basic settings applied.
By no means does the controller replace the safety appliances on site!
Heating Circuit (X)
Operating mode
Heating: automatic/normal operation taking into account operating times (day, comfort increase, night reduction).
Reference: fixed flow temperature independent of the outside temperature. The desired flow temperature must be set in Menu 5.1.5. .
Reference program: e.g. for screed heating. For the next 14 days, can be found under Menu 4. different fixed flow temperatures can be
entered. After 14 days, the reference temperature of the 14th day is used continuously until the operating mode is changed. Different tem-
perature values can be set in menu 5.4. for every individual day separately.
Set room controllers have no influence on the setpoint program!
Heating and cooling: automatic/normal operation taking into account operating times (day, comfort increase, night decrease) with
change of season.
The operating mode can be changed from heating to cooling in different ways:
1. Switching via °CALEON Clima room controller
a. Configuration "See " °CALEON Room Controllers " on page 24"
b. Main menu °CALEON Clima room controller
2. Using a sensor input for the change of season (e.g. by signal of an invertible heat pump or via an external switch). The sensor
input is monitored for short circuit (closed= cooling, open = heating).
a. menu 5. Settings - > Heating Circuit (X) - > Room Contr. heating circ. (X) -> Thermostat -> Sensor Input (e.g., S1)
b. Menu 5. Settings -> Heating Circuit (X) -> Thermostat -> Sensor Type -> Season
3. Manual switchover on the controller:
a. Menu 4. Operating Mode - > Mode Heating Circuit (X) - > Heating/Cooling
Cooling: automatic cooling operation taking into account operating times (day, comfort increase, night reduction).
The ideal addition to your cooling system is a °CALEON Clima room controller (room temperature measurement, relative
humidity measurement, dew point monitoring, simple seasonal change, and many more).
The following functions can be helpful when using the cooling function:
lDew point correction
lMin. Flow cooling
lMax. flow cooling
lCooling valve heating circuit 1/ heating circuit 2
lFree Cooling
lSeason switch
lCompressor - > Cooling Request
lDehumidifier
33
Season switch
Only appears, if "heating and cooling" mode is selected. Heating circuits separately, or switching system-wide between heating and cooling.
S/W Day
Summer / Winter changeover in daytime mode
If this value is exceeded at the outdoor sensor the controller automatically switches the heating circuit off = Summer mode. If the outdoor tem-
perature drops below this value, the heating circuit is switched on again = Winter mode.
In addition to the operating times in normal daytime operation, this setting is also valid for times with activated comfort.
S/W Night
Summer/Winter changeover in night-time mode
If this value is exceeded at outdoor sensor S1 during the nighttime mode times, the controller automatically switches the heating circuit off =
Summer mode. If the outdoor temperature drops below this value, the heating circuit is switched on again = Winter mode.
Curve
Type and slope of the heating characteristic curve
The characteristic curve is used to control the heat dissipation of the heating circuit relative to the outdoor temperature. The demand for heat
differs due to factors such as the type of building, heating, insulation and outdoor temperature. For this reason, the controller can operate with
a normal straight curve (setting ‚simple‘) or split curve (setting ‚split‘).
If ‚simple‘ is selected, the curve is adjusted using the graphic diagram. While setting the slope, the controller also shows the slope value and
the calculated target flow temperature at -12 °C as a reference point.
If ‚split is selected, the curve is set in the following steps:
1. Outdoor temperature for slope change
2. Slope over outdoor temperature for change
3. Slope below outdoor temperature for change
While setting the slope, the controller also shows the slope value and the calculated target flow temperature at -12 °C as a reference point. In
case of repeated adjustment of the split curve, the settings appear in reverse order.
The diagram shows the influence of the selected characteristic curve steepness
(standard curve) on the calculated reference flow
temperature of the heating unit. The correct characteristic curve is determined by
defining the intersection point of the maximal calculated flow temperature (=design
temperature) at minimal outdoor temperature.
Example: The design temperature of the heater 60 °C flow at lowest outdoor tem-
perature according to calculation of heat requirement
-12 °C. The intersection point renders a slope of 1.2 as the setting.
Day Correction
Parallel characteristic translation
The day correction causes a parallel shift of the heating curve during daytime operating hours, because with certain outdoor temperatures the
building might not be optimally heated with the set heating curve. With a non-optimised heating curve, the following situations frequently
occur: hot weather = room too cold/cold weather = room too hot. In this case, the slope of the curve should be reduced stepwise by 0.2 points
and increases the day correction
by 2 ... 4 °C each.
Night Correction
Parallel characteristic translation
The night correction produces a parallel translation of the heating characteristic during the nighttime operating hours. If a negative value is set
for the night correction, the reference flow temperature is lowered accordingly during the nighttime operating hours. In this manner, primarily
34
at night, but also during the day when no-one is at home, the room temperature is lowered, thus saving energy. Example: A day correction
of +5 °C and a night correction of -2 °C produces a reference flow temperature in nighttime operation that is 7 °C lower.
Comfort Temperature Boost
Parallel characteristic translation
The comfort temperature boost is added to the set day correction. In this manner it is possible to carry out quick heating and/or raise the
temperature of living spaces at a certain time each day.
Min. Flow
The minimum flow temperature is the lower limit of the heating curve, and by this, the reference flow temperature of the heating circuit. In
addition to that, the minimal flow temperature is the reference flow temperature for the frost protection function.
Max. Flow
This value is the upper limit of the reference flow temperature of the heating circuit If however, the temperature of the heating circuit
exceeds the set value, the heat circuit shuts down until the temperature falls below this value. After 55 seconds, rinse for 5 seconds.
The customer must provide an additional limiting thermostat which is connected to the pumps in series (eg underfloor heating)
for safety.
Reference/Actual -
Switch on hysteresis for additional heating
This setting determines the allowed undershoot of the heating circuit temperature below the calculated reference fl ow temperature. If the
heating circuit flow temperature and the storage temperature drop below the reference flow temperature by this value, the additional heat-
ing will start the additional heat source after a 1 minute delay.
Heat request is started when the flow temperature is continuously below reference temperature for 1 minute.
Reference/Actual +
This value determines the acceptable underflow of the heating circuit temperature beyond the calculated reference flow temperature at the
buffer sensor or flow sensor. If the temperature at the buffer sensor exceeds the reference flow temperature by the value set here, the heat-
ing request is deactivated.
The setting value reference/actual + appears only in the menu if a sensor has been set under buffer sensor.
Variant
Only appears, if the heating circuit is an unmixed heating circuit (no mixer 1).
The condition for switching off the heating circuit pump is set. In the mode flow (FL), the pump is shut down, if the reference temperature is
exceeded. In the summer/winter mode (SW), it is shut down in the winter mode at Tmax, in the summer mode the heating circuit pump is
shut down in general.
The sensor should be placed in the return line in the VL mode.
Heating circuit off
If you use a room controller, the heating circuit can also be switched off on the base of the room controller in addition to the switch-off
according to outside temperature.
Summer: Heating circuit turns off when the summer/winter time changeover (outside temperature) is exceeded.
Summer + Room: Heating circuit is turned off as soon as the summer/winter time changeover (outside temperature) or the room setpoint
temperatures are exceeded.
Room hysteresis
Only appears, if "Switch off heating circuit" has been set to "Summer+Room". If the reference room temperature + the hysteresis set here
are exceeded, the heating circuit is switched off.
35
In cooling mode, reactivation when the room temperature is exceeded.
Buffer sensor
Input of heating circuit buffer sensor.
In this menu, the sensor is set, which is used as a reference sensor for the heating circuit request. Switching on and off conditions for a heat-
ing circuit request See " Reference/Actual - " on page 35 / See " Reference/Actual + " on page 35.
The request only works if an energy source (burner, compressor, solid chamber) is activated as an additional function and if this
source is set for the heating circuit request
(see also
Thermostat: See " Heating Circuit request " on page 50,
Burner: See " Heating Circuit request " on page 54,
Compressor: See " HC request " on page 55,
Heater: See " HC request " on page 50).
Insulation factor
Depending on the selected factor, the outdoor temperature has an influence on the VL temperature calculation after the set delay.
0= Off, 1= 15 minutes, 2= 60 minutes, 3= 120 minutes, 4= 300 minutes
Better insulated buildings can increase comfort and save energy by increasing the building factor.
Overload protection
If the function is set to "On", it does not matter which state the heating circuit has. If the temperature at the buffer sensor is above Max. buffer,
the heating circuit pump switches on and the setpoint flow rate is fixed to See " Max. Flow " on page 35 -2°C or the adjusted set point. If the
set Max. If the temperature of the buffer falls below 5 Kelvin, the heating circuit switches back to the previous mode.
Min. Flow cooling
Only appears when the operating mode of the heating circuit is set to heating and cooling or cooling.
This value is the upper limit of the reference flow temperature of the cooling.
Max. flow cooling
Only appears when the operating mode of the heating circuit is set to heating and cooling or cooling.
This value is the upper limit of the reference flow temperature of the cooling.
Dew Point protection
Only appears, if the operating mode of the heating circuit is set to heating and cooling or cooling.
Is only active, if humidity is measured (e.g. via a °CALEON Clima room controller). It is calculated from which room temperature there is
unwanted condensation (precipitation) for the currently measured humidity. Dew point monitoring automatically shifts the target supply tem-
perature in cooling mode to prevent mould formation.
Dew point correction
Only appears, if the operating mode of the heating circuit is set to heating and cooling or cooling. This value moves the internal dew point
characteristic by up to 10 °C in parallel.
Example 1: You determine that there is condensation with the default value, so you increase this correction value.
Example 2: Condensation/precipitation can be ignored, but stronger cooling is required instead. You therefore decrease this correction
value.
In case of reduction of the calculated temperature with the help of dew point correction condensation / perspiration / precipitation
can occur, which, among other things, may cause the formation of mold.
Room Controller Heating Circuit (X)
Here, the settings are made for an optional room controller. The following variants can be used with different functions:
°CALEON Room Controller:
36
Influence of the room temperature, the room reference temperature as well as of room-specific time programs on the reference flow. Oper-
ating modes of the °CALEON and significance for the HCC:
Off = Heating Circuit Off,
Eco = Reference - Night reduction,
Normal = Reference + daily correction,
Comfort = Reference + daily correction + comfort increase
The selection of an operating mode (Normal, Comfort, Eco or Off) is only valid until a change to another mode is effected in the
time program of the °CALEON.
Example: The operating mode “Off” is activated on the °CALEON. The next change in the time program ends the manually set
operating mode and activates the mode set according to the time program. If a longer shutdown of the heating circuit is
desired, for example, the holiday mode can be used in the °CALEON.
If several °CALEONs are set as room controllers, the operating mode of the HCC is determined by the room with the greatest
energy demand.
RC21:
Influence of the room temperature on the reference, parallel shift of the characteristic curve by the control dial, influence on the reference
flow by the operating mode switch. Operating modes of the RC21 (Switch) and significance for the HCC:
Auto = Set reference,
Day = Reference + daily correction,
Night = Reference night reduction
For detailed instructions on how to connect °CALEON or an RC21, See " °CALEON Room Controllers " on page 24
Sensor input (S1-S6, VT1, VT2):
Use of a sensor input as room controller with different functions (see "Sensor Type").
Set room controllers have no influence on the setpoint program!
Thermostat (X)
The room controller or sensor input is selected here.
When using a °CALEON: select the room set in the °CALEON.
When using an RC21: select RC21-Local 1 and then select RC 1 Temp. 1 and RC1 Contr. sensor inputs used - See " RC21 Room ther-
mostat with remote control " on page 26.
When using an RC20 or other thermostats and seasonal switches: select the sensor input used here and then select the exact function
under "sensor type".
Sensor Type
If a sensor input is selected for "Thermostat (X)", it must be set here how exactly this input is to be used.
RC20: measurement of room temperature and influence on reference
Contact: Open = heating circuit Off, closed = heating circuit
Season: Closed= cooling, Open = heating
RC 1 Temp. 1
Only appears, if an RC21 has been set in "Thermostat (X)".
Select here the sensor input that you use for the temperature sensor (Terminal 1) of the RC21.
RC 1 contr.
Only appears, if an RC21 has been set in "Thermostat (X)".
Select here the sensor input that you use for the remote control (Terminal 2) of the RC21.
37
Room Controller
This value is used to appoint the amount of influence the room temperature has on the reference flow temperature, as a percentage. For each
degree deviation between room temperature and set point temperature, the percentage set here is added from the calculated set flow tem-
perature to the set flow temperature or subtracted from it until the min. or max flow values.
Example: Reference room temp.: e.g. 25 °C; room temp.: e.g. 20 °C ±5 °C. Calculated reference temp.: e.g. 40 °C: room controller: 10 %= 4
°C 5 X 4 °C= 20 °C. Accordingly, 20 °C are added to the reference flow temperature, giving 60 °C. If the value is higher than the one set in
max. flow temp, the resulting temperature is the one set in max. flow temp.
Room Reference Day
The desired room temperature for day mode.
In combination with the %-value set under "room controller", the difference between reference and actual room temperature influences the
reference flow temperature. If the room controller is set to 0 %, this function is deactivated.
For °CALEON room controller without influence.
Room Reference Night
The desired room temperature for night mode.
In combination with the %-value set under "room controller", the difference between reference and actual room temperature influences the
reference flow temperature. If the room controller is set to 0 %, this function is deactivated.
For °CALEON room controller without influence.
In the mode Set point program, the room controller has no influence.
Smart grid 1/ PV contact
A sensor input can be set here, which can be used as Smart grid terminal 1 for interference by the energy supplier or as a PV contact for a
photovoltaic system. This sensor is observed to "short circuit" (PV-Contact closed). If the PV-Contact is closed, the mode of this function is
changed to "comfort" and operated at the comfort temperature set for the comfort function. This also applies in the case that the mode "com-
fort" of the function currently has no time release.
Information about the operation and the connection of PV-contact, refer to the technical description of your PV system.
Smart grid 2
Smart Grid Terminal 2 for influence by the energy supplier. The inputs are checked for open and short-circuit. The combination of inputs 1
and 2 determines how the heating circuit is influenced: 1= short-circuit, 0 = open Terminal 1: Terminal 2
0:0 = Set heating circuit modes to "Off".
1:0 = Set heating circuit modes to" Eco
0:1 = Set heating circuit mode according to time and room controller settings
1:1= Set heating circuit mode to "Comfort" mode
Settings Domestic Hot Water (DHW)
By no means does the controller replace the safety appliances on site!
Operating mode
The DHW heating can be set here. “Auto” activates the DHW heating according to the time program, with “off” the DHW heating is turned off.
Hot water minimum
Minimum DHW temperature. If the set temperature at the DHW sensor is undeshot outside of the set times, the DHW charge and heat
request will be turned on.
DHW reference
Minimum DHW temperature time program. If the set temperature at the DHW sensor is undershot and the DHW charge is approved for the
time, the DHW charge and the heat request will be turned on.
38
The request only works if an energy source (burner, compressor, solid chamber) is activated as an additional function and if
this source is set for the DHW request.
DHW comfort
DHW temperature for comfort time. The set temperature considered as minimum temperature during the set comfort time. If the tem-
perature on DHW-sensor is below the value set here is during the DHW comfort periods, the DHW heating is started, until DHW comfort +
hysteresis is achieved.
DHW hysteresis
DHW hysteresis. The DHW charge and heat request are shut down if the temperature at the DHW sensor reaches the value set under “See
" Hot water minimum " on page 38“ / “See " DHW reference " on page 38“ plus the heating set here.
Buffer DHW load
DHW load from the buffer. The DHW load from the buffer storage is turned on if the temperature on the buffer sensor is at least 8 °C
warmer than at the DHW sensor. The DHW load from the buffer storage is shut down if the temperautre at the buffer sensor is only 4 °C
warmer than at the DHW sensor or if the temperature at the DHW sensor has reached the value set under See " Hot water minimum " on
page 38 or See " DHW reference " on page 38.
DHW priority
Preferred DHW charge. If this function is activated, the reference flow temperature during a DHW heating will be set to the minimum flow
temperature See " Min. Flow " on page 35 so that the mixer moves to the “closed” position.
DHW sensor
The sensor used as a domestic hot water sensor.
Smart grid 1/ PV contact
A sensor input can be set here, which can be used as Smart grid terminal 1 for interference by the energy supplier or as a PV contact for a
photovoltaic system. This sensor is observed to "short circuit" (PV-Contact closed). If the PV-Contact is closed, the mode of this function is
changed to "comfort" and operated at the comfort temperature set for the comfort function. This also applies in the case that the mode "com-
fort" of the function currently has no time release.
Information about the operation and the connection of PV-contact, refer to the technical description of your PV system.
6. Protective Functions
The 'Protective functions‘ can be used by specialists to activate and set various pro-
tective functions.
By no means does the controller replace the safety appliances on site!
Seizing Protection
If the anti-seizing protection is activated (daily, weekly, off), the controller switches the outputs on/off at 12:00 noon for 5 seconds to prevent
seizing of the pump/valve after long periods of inactivity.
Frost Protection
If the external temperature on sensor S1 goes below 1 °C and the heating circuit is turned off, the heating circuit will automatically be turned
on if the frost protection is activated and the reference flow temperature is set at the minimum flow temperature set under See " Min. Flow "
on page 35. As soon as the outdoor temperature exceeds 1 ° C, the heat circuit is switched off again.
Switching the frost protection function off or setting the minimum flow temperature too low can lead to severe damage to the sys-
tem.
39
Discharge Protection
With activated buffer discharge protection, the heating circuit is switched off as soon as the buffer temperature undershoots the min. flow tem-
perature. flow temperature. Every 5 minutes, the system checks if the flow temperature has been reached.
Dew point correction
Activate or deactivate. Activated dew point correction corrects the heating circuit flow temperature in cooling mode and switches off the heat-
ing circuit when the temperature falls below the dew point in order to prevent condensation.
Pressure Monitoring
In this menu, the system pressure monitoring can be activated through a direct sensor. A message is displayed and the LED flashes red
when the pressure drops below minimum or exceeds the maximum.
RPS1 / RPS2
In this menu, you can adjust which pressure sensor model is being used. Please note: If e.g. VFS1
is connected, RPS1 will be hidden
RPS Min
Minimum pressure. If this pressure is not met, the controller emits an error notification and the red LED flashes.
RPS Max
Maximum pressure in the system. If this pressure is exceeded, the controller emits an error message and the red LED flashes.
Protective functions for Solar
The protection functions for Solar are not displayed in the “Protective functions” menu, but rather as a sub-menu in the settings
from the solar function, See " Solar " on page 52.
System protection
Priority protection function
The system protection should prevent an overheating of the components installed in the system through the forced shut down of the solar cir-
culation pump. If the value “AS Ton” on the collector has been exceeded for 1 Min. the pump will be turned off and not turn on again in order to
protect the collector, for example, from steam. The pump will only be switched on again, when the collector temperature falls below “SP Toff”.
With the system protection (on), there are increased standstill temperatures in the solar collector and therefore an increased pres-
sure in the system. The operating manuals from the system components must be observed.
Collector protection
Priority protection function
The collector protection prevents the collector from overheating. A forced switching of the pump makes sure that the collector is cooled
through the storage. If the value “KS Ton” is exceeded on the collector, the pump will be turned on in order to cool the collector. The pump is
shut down if the value “KS Toff” on the collector is not met or the value “KS Tmax Sp.” on the storage is exceeded.
System protection has priority over collector protection! Even if the switch requirements for the collector protection are present,
the solar circulation pump is turned off once “AS T on” is reached. Normally the values from the system protection (depending on
the maximum temperature of the storage or other components) are higher than the collector protection.
Recooling
In the system hydraulics with solar, excess energy is guided from the storage back to the collector with an activated return cooling function.
This only occurs if the temperature in the storage is greater than the value “Return cooling Tref” and the collector is at least 20 °C colder than
the storage and until the storage temperature has fallen below the value “Return cooling Tref”. For muti-storage systems, the return cooling
applies to all storage.
Energy is lost through the collector through this function! The recooling should only be activated in cases of exception, with low
heat acceptance, for example, during vacation.
40
Frost Protection
A 2-level frost protection function can be activated. In level 1, the controller turns on the pump every hour for 1 minute if the collector tem-
perature is below the set value “Frost Level 1”. If the collector temperature continues to decrease to the set value “Frost Level 2”, the con-
troller will turn on the pump without disruption. If the collector temperature exceeds the value “Frost level 2” by 2 °C, the pump will turn off
again.
Energy is lost through the collector through this function! It is normally not activated for solar systems with antifreeze. The oper-
ating manuals from the other system components must be observed.
Collector alarm
If this temperature at the collector sensor is exceeded when the solar pump is turned on, a warning or error notification is triggered. There is
a corresponding warning in the display.
7. Special Functions
Used to set basic items and expanded functions.
The settings in this menu should only be changed by a specialist.
Program selection
Here the hydraulic variation fitting to the respective use case is selected and set.
The program selection normally occurs only once during the first entry into service by a specialist. An incorrect program selec-
tion may lead to unpredictable errors.
Pump settings V(X)
Settings from the 0-10V or the PWM pump can be made in this menu.
When this menu is selected, you may receive a request to save the speed settings.
Signal type
Only available, if the function is used on one of the V-outputs. The type of device to be controlled is set here.
0-10V: Control by 0-10V signal.
PWM: Control by means of a PWM signal.
Profile
In this menu, the preset profiles for actuators can be selected or under “manual” all settings can be done personally. The settings can still
be changed after a profile has been selected.
Output Signal
In this menu the type of actors are set: heating pumps have the greatest output with a small input signal, solar pumps in contrast have very
little output with a small input signal. Solar = normal, heating = inverted.
PWM / 0-10V off
This signal / this voltage is emitted if the actor is turned off (actor with cable break detection require a minimum voltage / a minimum signal).
PWM / 0-10V on
This voltage / this signal requires the pump in order to turn on and to run at a minimum speed.
41
PWM / 0-10V max.
With this value, the maximum signal / maximum voltage level can be specified for the highest speed of the energy saving valve, which is
used, for example, during the purging or manual operation.
Show signal
Represents the set signal in a graphic and text overview.
Speed control
If the speed control is activated, it LHCC offers the possibility through a special internal electronic system to change the speed of pumps
depending on the process. The PWM and 0-10V outputs can work speed-controlled.
Variant
The following speed variants are available here:
Off: There is no speed regulation. The connected pump is only turned on or off with full speed.
Mode M1: The controller changes to the set max. speed after the purging time. If the temperature difference ∆T between the reference
sensors is below the set switch on temperature difference ∆T R1, the speed will be reduced. If the temperature difference between the ref-
erence sensors is above the set switch on temperature difference ∆T R1, the speed will be increased. If the controller has decreased the
speed of the pump to the smallest level and the ∆T between the reference sensors is still only ∆Toff, the pump will be turned off.
Mode M2: The controller changes to the set min. speed after the Speed. If the temperature difference ∆T between the reference sensors is
above the set switch on temperature difference ∆T R1, the speed will be increased. If the temperature difference ∆T between the reference
sensors is below the set switch on temperature difference ∆T R1, the speed will be reduced. If the controller has decreased the speed of the
pump to the smallest level and the ∆T between the reference sensors is still only ∆Toff, the pump will be turned off.
Mode M3: The controller changes to the set min. speed after the Speed. If the temperature on the reference sensors is above the set value to
be set in the following, the speed will be increased. If the temperature on the reference sensors is below the set value to be set in the fol-
lowing, the speed will be reduced.
Purging time
For this time, the pump runs with its full speed (100%) in order to guarantee a secure start-up. Only after expiration of this purging time will the
pump have a controlled speed and will switch, depending on the set variant, to the max. or min. speed. Speed.
Sweep time
With the control time, the inertia of the speed control is determined in order to prevent strong temperature deviations as much as possible.
The timespan is entered here, which is needed for a complete cycle from minimum speed to maximum speed.
Max. Speed
The maximum speed of the pump is determined here in %. During the setting, the pump runs in the respective speed and the flow can be
determined.
The specified percentages are variables, which may deviate more or less strongly depending on the system, pump and pump
level. 100% is the maximum possible power of the controller.
Min. Speed
The minimum speed of the pump is determined here. During the setting, the pump runs in the respective speed and the flow can be determ-
ined.
The specified percentages are variables, which may deviate more or less strongly depending on the system, pump and pump
level. 100% is the maximum possible power of the controller.
Setpoint
This value is the control setpoint. If this value is below at the sensor, the speed is reduced. When it is exceeded, the speed is increased.
Sensor Calibration
Deviations in the temperature values displayed, for example. due to cables which are too long or sensors which are not positioned optimally
can be compensated for manually here. The settings can be made for each individual sensor in steps of 0.5 °C.
Settings are only necessary in special cases at the time of initial commissioning by the specialist. Incorrect measurement values
42
can lead to unpredictable errors.
Relay functions
Free relays, i.e. relays not used in a basic scheme, can be assigned to various additional functions. Every additional function can only be
assigned once. Preset functions can be deselected. See " Function overview " on page 47
When assigning relays with functions, the activated function for already used relays must first be deactivated before a new
function can be selected.
R1 to R3: mechanical relay 230V
R1 to R4: mechanical relay 230V
V1 and V2: PWM and 0-10 V outputs See " External relay at signal output V(X) (0-10V / PWM) " on page 13
Please pay special attention to the relay’s technical information (see "Specifications“).
The symbols shown here are displayed on the main overview screen when the special function is activated.
Heat quantity
Constant flow
If “Constant flow” is activated as the type of heat quantity metering, the approximate heat from the manually entered values for antifreeze,
its concentration and the flow from the system and the measured sensor values from the collector and storage are calculated. Additional
information about antifreeze, its concentration and the flow of the system is required. Additionally through the setting offset ∆T, a correction
factor can be set for the heat quantity collection. Since the collector temperature and the storage temperature can be used for the heat
quantity metering, depending on the system, there may be deviations from the displayed collected temperature to the actual previous tem-
perature or the displayed storage temperature to the actual return temperature. Through the setting Offset ∆T, this deviation can be cor-
rected.
Example: displayed collector temperature 40°C, read previous temperature 39°C, displayed storage temperature 30°C, read return tem-
perature 31° means a setting of -20% (displayed ∆T 10K, actual ∆T 8K => -20% correction value)
The heat quantity data in the “Constant flow” mode only consists of calculated values for the functional inspection of the system.
Flow temperature sensor (X)
In this menu, it is set which sensor is used to measure the flow temperature.
Return flow sensor
In this menu, you can set which sensor is used to measure the return flow temperature.
Glycol type
In this menu, the antifreeze used is set. If none is used, please set glycol proportion to 0.
Glycol percentage
The percentage of antifreeze in the medium.
Flow rate supply flow (X)
Nominal system flow.
The flow of the system in liters per minute, which is used as calculation basis for heat metering.
Offset ∆T
Correction factor for the temperature difference for heat metering
Since the collector temperature and the storage temperature can be used for the heat quantity metering, depending on the system, there
may be deviations from the displayed collected temperature to the actual previous temperature or the displayed storage temperature to the
actual return temperature. This deviation can be corrected with the adjustment value Offset ΔT
Example: displayed collector temperature 40°C, read previous temperature 39°C, displayed storage temperature 30°C, read return tem-
perature 31° means a setting of -20% (displayed ∆T 10K, actual ∆T 8K => -20% correction value)
VFS (X)
The type used of direct sensor is set in this menu.
43
VFS - Position
This menu is used to set whether the direct sensor was mounted in supply or return flow.
To prevent damage to the Vortex Flow sensor it is highly recommended to place it in the return flow. If contrary to this recom-
mendation it is used in the supply line, the maximum temperature has to be considered. (0 ° C to 100 ° C continuous operation
and short term -25 ° C to 120 ° C)
Reference sensor
The sensor to be used for heat metering is set here.
Commissioning
Starting commissioning help guides you in the correct order through the basic settings necessary for commissioning, and provides brief
descriptions of each parameter in the display. Pressing the ‚esc‘ key takes you back to the previous value so you can look at the selected set-
ting again or adjust it if desired. Pressing ‚esc‘ more than once takes you back to the selection mode, thus cancelling the commissioning help
(See " Commissioning help " on page 29).
May only be started by a specialist during commissioning! Observe the explanations for the individual parameters in these instruc-
tions, and check whether further settings are necessary for your application.
Factory Settings
All settings can be reset, returning the controller to its delivery state.
All of the controller‘s parametrization, statistics, etc. will be lost irrevocably. The controller must then be commissioned once
again.
Eco Display Mode
In Eco Display Mode the backlight of the display is switched off if no buttons are pushed for 2 minutes.
If a message exists, the backlight does not switch off until the message has been scanned by the user.
Network
If necessary, the network settings of the connected data logger must be set.
Access Control
This menu lets you give up to 4 users access to the data logger. The users that are registered then have access to the controller or respect-
ively the data logger.
To add a user in the list, select <add user>. Leave the now visible menu open und connect to the address of the connector or respectively the
data logger. Your user name is going to appear in this menu and can be selected and confirmed with ‘OK’.
Note
You can find the address of the connector or respectively the data logger on the address sticker on the outside of the casing. Pointers and
help on how to establish a connection you can find in the enclosed SOREL Connect instructions or the instructions of the data logger.
Select a user with ‚OK‘ to grant access.
To revoke access again, choose one of the users from your list and choose <remove user>.
Ethernet
The data logger‘s Ethernet connection settings can be set using this menu.
MAC Address
Displays the individual MAC address of the data logger.
Auto-Configuration (DHCP)
If auto-configuration is activated, the data logger requests IP addresses and network parameters from a DHCP server that assigns an IP
address, subnet mask, gateway IP and DNS server IP. If you deactivate the auto configuration (DHCP), you will have to make the
required network settings manually!
44
IP-Address
Please refer to the router configuration for the IP address to be set.
Subnet Mask
Please refer to the router configuration for the subnetz mask to be set.
Gateway
Please refer to the router configuration for the gateway to be set.
DNS-Server
Please refer to the router configuration for the DNS server to be set.
Datalogger Version
Shows software version of the datalogger.
CAN bus ID
Here you can see the ID of the controller on the CAN bus.
Sensor send interval
The send interval determines how often the sensor and output values of the controller may be send via CAN. If a value changes, it is sent
and starts the interval. The next values are not sent until the interval has expired. If no value changes, nothing is sent.
If there are several controllers in the CAN network, a too short send interval can lead to an overload of the CAN network.
45
8. Menu Lock
Secure the controller against unintentional changing and compromise of basic func-
tions.
Menu lock active = "On"
Menu lock off = "Off"
In addition, the "Simple" menu view can be used to hide menu items that are not neces-
sary for the daily use of the controller after commissioning. The menu item "Menu lock
on/off" is also hidden when the "Simple" menu view is selected!
The menus listed below remain completely accessible despite the menu lock being
activated, and can be used to make adjustments if necessary:
1. Measurement values
2. Statistics
4. Settings
6. Special Functions
7. Menu lock
9. Language
9. Service Values
Serve for remote diagnosis by a specialist or the manufacturer in the event of errors,
etc.
Enter the values into the table when an error occurs.
10. Language
To select the menu language. During initial commissioning and longer power inter-
ruptions, the query is made automatically. The choice of languages may differ depend-
ing on the model. Language selection is not available for every model.
46
Function overview
When assigning relays with functions, the activated function for already used relays must first be deactivated before a new
function can be selected.
Mixer
This menu contains all settings relating to the mixer of the heating circuit.
Direction
Direction of the mixing valve can be set here.
Mixer turn time
The mixer is switched on i.e. is opening or closing for the time span set here, then the temperature is measured to control the flow tem-
perature
Mixer off factor
The calculated pause time of the mixer is multiplied with the value set here. If the pause factor is ‚1‘, the normal pause time is used, ‚0.5‘ will
use half the normal pause time. Setting the pause factor to ‚4‘ would quadruple the pause time.
Mixer increase
If the temperature rises very fast, this value is added to the measured flow temperature so that the mixer’s reaction is stronger. If the meas-
ured temperature does not rise any more, the measured value is used again. The measurement occurs once every minute.
Mixer run time
Mixer-specific setting of the running time required by the mixer for a full ride.
Signal type
Only available, if the function is used on one of the V-outputs. The type of device to be controlled is set here.
0-10V: Control by 0-10V signal.
PWM: Control by means of a PWM signal.
Cooling valve Heating circuit 1/ Heating circuit 2
If the heating circuit is in heating-off, cooling-off, heating-eco, heating-normal or heating-comfort mode, the relay is switched off or switched
to the heating circuit buffer.
If the heating circuit is in cooling-Eco, cooling-normal or cooling-Comfort mode, the relay is switched on or the valve switches to the cooling
circuit.
The additional function cooling valve heating circuit 1 / heating circuit 2 is only visible if heating circuit 1 / 2 has been activated
on an output.
Heating Circuit 2
See " Heating Circuit (X) " on page 33
Free Cooling
If the function is activated, the output switches a pump or fan and supplies the heating system with "free cooling". This pump supplies e.g.
heating circuits whose cooling valve is switched on and must therefore run as soon as cooling is required in at least one heating circuit.
Switch-on condition: a heating circuit is set to Cooling-Eco, Cooling-Normal or Cooling-Turbo.
Switch-off condition: no heating circuit cools.
47
RFI mixer
The RLA-mixer function (return flow increase mixer) can be used to control a motorized return flow increase for a solid fuel boiler or a return
flow buffer/buffer admixture. The RFI mixer requires either 2 relay switch outputs (230) or alternatively may be controlled via a 0-10V / PWM
output (PWM mixer).
Operating mode
The RFI mixer can be operated in "SF increase" (solid fuel boiler), "setpoint" or "heating circuit automatic" mode.
SF increase: motorized return flow increase for a solid fuel boiler.
Heating circuit automatic: the setpoint temperature, which is provided by the RFI mixer at the flow sensor, is specified by the heating circuit
1. In addition, a target flow offset can be set.
Setpoint: The setpoint temperature, which is provided by the RFI mixer at the flow sensor, will be set fixed under see "Tsoll".
Reference flow sensor
Sensor for monitoring the reference variable of the RFI function. The mixed temperature of the RFI mixer is measured at this sensor and com-
pared with the current setpoint value. If the flow rate falls below or exceeds this limit, the mixer is controlled or controlled accordingly.
Tref:
Temperature controlled by the mixer.
For operating mode solid fuel boiler
When using a motorised return temperature control for a solid fuel boiler, the minimum temperature of
it should not fall below the return (Tref) of the solid fuel boiler. Please refer to the boiler manufacturer's
instructions.
Return flow sensor:
Sensor in return
Storage sensor:
Sensor in storage
Direction:
See " Direction " on page 47
Min off time:
Minimum timeout setting of the function
On-time:
See " Mixer turn time " on page 47
Off factor:
See " Mixer off factor " on page 47
Increase:
See " Mixer increase " on page 47
Max one direction:
Maximum cycle time until the mixer is fully clocked on/off.
Signal type
Only available, if the function is used on one of the V-outputs. The type of device to be controlled is set here.
0-10V: Control by 0-10V signal.
PWM: Control by means of a PWM signal.
Difference
The assigned relay is activated as soon as there is a preset temperature difference (ΔT on/off) between the source and target sensors.
48
Δ T Difference
Switch on - difference:
If this temperature difference is reached, the relay will switch on.
Switch off difference:
If this temperature difference is reached, the relay will switch off.
DF-Source
Heat source sensor/heat supplier for differential function
Adjusts the sensor from the heat source.
Tmin Source
Minimum temperature on the source sensor for approval of the difference relay.
If the temperature on the source sensor is below this value, the difference function will not be switched on.
DF-Drain
Heat decreasing sensor / heat customer for the different functions
Sets the sensor of the heat customer.
Tmax Drain
Maximum temperature on the target sensor for approval of the difference relay.
If the temperature at the target sensor exceeds this value, the difference function will not be turned on.
Heat transfer
With this function, energy from one storage can be loaded in another.
Δ T Heat transfer
Temperature difference for the transfer. If the temperature difference between the sensors ∆T transfer On is reached, the relay is switched
on. As soon as the difference on ∆T Transfer off falls, the relay is turned off again.
HT Tmax
Target temperature of the target storage
If this temperature is measured on the sensor in the target storage, the Heat Transfer will be shut down.
HT Tmin
Minimum temperature in the source storage for the approval of the Heat Transfer.
Source
In this menu, the sensor is set, which is placed in the storage from which the energy is extracted.
Drain
In this menu, the sensor is set that is placed in the storage in which it is loaded.
Thermostat
Through the thermostat function, additional energy can be added to the system while being time and temperature controlled. The ther-
mostat function can be used in 2 modes.
"On" = the relay is switched on when all switching conditions are reached
"Inverted" = the relay is switched off when all switching conditions are reached and is otherwise switched on.
Temperature values which are set too high can lead to scalding or damage to the system. Scalding protection must be provided
by the customer!
49
Other values, for example, Teco, apply in economy mode.
DHW request
Thermostat is started for a DHW - heat request.
Heating Circuit request
Thermostat is started with a heating circuit - heat request.
Tset
The target temperature of the thermostat sensor 1. Below this temperature, the thermostat turns on until Tset+ Hysteresis is reached.
Hysteresis
Hysteresis of set point temperature.
Energy Saving Mode
The Energy Saving Mode switches the heating on when “T Eco on” is undershot and heats up to “T Eco” + hysteresis when solar charge or
solid fuel boiler is active.
Delay
Delay for this function.
The function first turns on after this time span if the switch conditions were reached and are still present. This delay is intended to prevent
unnecessary switching operations caused by temperature fluctuations or to
Give another energy source time to provide the necessary energy.
Thermostat sensor 1
TH Set is measured at thermostat sensor 1. With a connected thermostat sensor 2, the relay switches on if “TH Ref” at thermostat sensor 1 is
undershot and off if “TH Ref” + hysteresis is exceeded at thermostat sensor 2.
Thermostat sensor 2
Optional switch off sensor
If “TH target” + hysteresis is exceeded on thermostat sensor 2, the relay will be shut down.
Thermostat enable
Thermostat activity times
Here the desired periods are set in which the thermostat function is approved. For each weekday, three times can be specified, furthermore,
you can copy individual day to other days. The thermostat function is shut down outside of the set times.
Electric heating rod (auxiliary heating)
An electric heating rod that heats up the storage water heater if needed. The heating rod function can be used in 2 modes. "On" = the relay is
switched on when all switching conditions are reached.
"Inverted" = the relay is switched off when all switching conditions are reached and is otherwise switched on.
Temperature values which are set too high can lead to scalding or damage to the system. Scalding protection must be provided
by the customer!
DHW request
Electric heating rod is started for a DHW - heat request.
HC request
Electric heating rod is started with a heating circuit - heat request.
TH Set
The target temperature of the thermostat sensor 1. Below this temperature, the eat turns on until TH Set + Hysteresis is reached.
Delay
After reaching the switching conditions, the time set here will be waited until the heating rod is actually turned on in order to give another heat
source time to heat up.
50
Hysteresis
Hysteresis of set point temperature.
Eco mode
The Energy Saving Mode switches the heating on when “T Eco on” is undershot and heats up to “T Eco” + hysteresis when solar charge or
solid fuel boiler is active.
Sensor 1
TH Reference is measured at the thermostat sensor 1. With a connected thermostat sensor 2, the relay switches on if “TH Ref” at ther-
mostat sensor 1 is undershot and off if “TH Ref” + hysteresis is exceeded at thermostat sensor 2.
Sensor 2
Optional switch off sensor
If “TH target” + hysteresis is exceeded on thermostat sensor 2, the relay will be shut down.
Electric heating rod approval times
Release time for the electric heating rod
Here the desired periods are set in which the electric heating rod is approved. For each weekday, three times can be specified, fur-
thermore, you can copy individual day to other days. The electric heating rod is shut down outside of the set times.
Anti-legionella heating rot
See " Anti Legionella " on page 59.
Dissipation (Cooling)
The dissipation function is a simple cooling function.
The relay of this function switches "on" as soon as the set Tsoll temperature at the assigned cooling sensor is exceeded and the set time
delay has elapsed.
If the temperature at the cooling sensor reaches Tsoll hysteresis, the function switches "off" without a time delay.
Tset
The target temperature at the set sensor for the function cooling (dissipation).
Cooling sensor
The corresponding cooling sensor for the dissipation function is set here.
Delay
Switch delay of the heat and cooling request. In order to prevent the heat or cooling request to be activated if there are heat deviations, the
corresponding relay is switched up ot 5 minutes before the switch conditions occur.
Season switch
1. 2.
1. Mode "Heating" -> output of the season switch is not active
2. Mode "Cooling" -> output of the season switch active
The seasonal switch function switches for change of season (from heating to cooling or vice versa) in combination with the energy request.
For example, for inverting a heat pump suitable for reversible operation. If the request for domestic water is activated for the heat pump in
the controller, the operating mode of the heat pump automatically switches to the "heating" mode in case of domestic water request, i.e. the
output of the seasonal switch is switched off.
Off hysteresis
If the controller has changed the season from cooling to heating and flow <reference flow + Off hysteresis, the seasonal switch will be
switched off (output not switched).
Example 1:
Flow = 28 °C; target flow = 30 °C; off-hysteresis = - 3 °C
28 °C < 30 °C - 3 °C -> 28 °C < 27 °C -> wrong! -> Do not switch off the season change
51
Example 2:
Flow = 28 °C; target flow = 30 °C; off-hysteresis = + 3 °C
28 °C < 30 °C + 3 °C -> 28 °C < 33 °C -> correct! -> Switch off the season change
On hysteresis
If the controller has changed the season from heating to cooling and flow <reference flow + On hysteresis, the seasonal switch will be
switched on (output switched).
Cool storage
The storage can be cooled through this function.
Yes: The flow and buffer storage are cooled down to the reference flow temperature + hysteresis.
No: It is cooled down to the reference flow temperature + hysteresis, the temperature in the buffer storage is ignored.
Buffer sensor
If the buffer tank is to be cooled in the cooling mode, the corresponding sensor can be set here.
Solid fuel boiler
In solid-fuel boiler function, a pump is controlled with a assigned relay, which loads the heat energy from a solid-fuel boiler into a storage tank.
The solid-fuel boiler function controls the charge pump of a solid-fuel boiler based on the temperature difference between the solid-fuel boiler
sensor and the storage tank sensor.
If a control output (V1 or V2, ...) is used with this function, a speed control with a PWM / 0-10V HE pump is possible.
Solid fuel boiler Tmax
Maximum temperature in storage tank. If this is exceeded, the relay is switched off.
Solid fuel boiler Tmin
Minimum temperature in the solid fuel boiler to start the pump.
If the temperature at the solid fuel boiler sensor exceeds the temperature set here, the relay switches on the pump, if the other starting con-
ditions are met.
Below the solids boiler Tmin temperature, the solids boiler function is deactivated.
ΔT Solid fuel boiler
Switch-on and switch-off difference between solid fuel boiler (SFB) and storage tank.
If the temperature difference between the sensors defined for this function exceeds the value set here (ΔT SF On), the function switches on
the assigned output (relay or signal output).
If the set temperature difference (ΔT SF Off) between the solids boiler and the storage tank is below, the function switches off the assigned
output (relay or signal output).
Boiler sensor of this function
Sensor used as a solids boiler sensor. Considered for SF Tmin and ΔTon/off.
Storage sensor
Sensor used as a storage tank sensor. Considered for FS Tmax and ΔTon/off.
Solar
This function is used to control a solar pump.
Tmin Collector
Enable/start temperature at sensor X:
If this value on the specified sensor is exceeded and the other conditions are fulfilled, the controller will turn on the affiliated pump or the
valve. If the temperature on the sensor falls 5 °C below this value, the pump or the valve will be turned off again.
52
ΔT Solar
Switch on/switch off temperature difference for sensor X:
If the temperature difference ΔT Solar between the reference sensors is exceeded and the other conditions are fulfilled, the controller will
turn on the pump/valve on the corresponding relay. If the temperature difference falls to ΔT Off, the pump/valve will be turned off again.
Tmax Storage
Switch off temperature at sensor X:
If this value is exceeded at the specified sensor, the controller turn off the affiliated pump or the valve. If this value on the sensor is under-
shot and the other conditions are fulfilled, the controller will turn on the pump or the valve.
Temperature values which are set too high can lead to scalding or damage to the system. Scalding protection must be provided
by the customer!
Starting aid
For some solar systems, in particular for vacuum tube collectors, the measurement recording on the collector sensors may be too slow or
imprecise, because the sensor is often not on the warmest spot. With an activated starting aid, the following procedure occurs: If the tem-
perature on the collector sensor increases within a minute by the value defined under “increase”, the solar circulation pump will be turned
on for the set “purging time” so that the medium to be measured is transported to the collector sensor. If there is still no normal switching
condition through this, there will be a 5 minute block time for the start wizard function.
This function should only be activated by a technician if problems occur with the measurement recording. Observe in particular
the instructions from the collector manufacturer.
The menus "Purging time" and "Increase" are only displayed when the starting aid function is set to "On".
Purging time
If the temperature on the collector sensor increases within a minute by the value defined under “increase”, the solar circulation pump will be
turned on for the set “purging time” so that the medium to be measured is transported to the collector sensor. If the set ΔT is not reached, a
5-minute circulation pause time for the starting aid function will apply.
Increase
If the temperature at the collector reaches within a minute the value defined, the solar pump is turned on for the duration of the purging
time.
Protective Functions
See " Protective functions for Solar " on page 40
Collector
Collector sensor
The collector sensor can be determined or changed here. The collector sensor set here is used for solar function ( Tmin collector, ∆T
Solar,....) as well as all protection functions Solar (collector protection, system protection, ...).
Solar storage
The solar storage sensor can be determined or changed here. The solar storage sensor determined here is used for the solar function (
Tmax storage, ∆T Solar,....).
Solar bypass
Use a relay to switch a bypass valve or a bypass pump. With this function, the flow can be guided past the storage if the flow temperature at
the bypass sensor is less than in the storage to be filled.
Variant
In this menu, you can set if the flow is guided through the bypass with a pump or a valve.
Bypass sensor
The reference sensor for the bypass function to be placed in the flow is selected in this menu.
53
Booster Pump
An additional booster pump can be activated with this function if the primary pump is no longer sufficient.
Charge time
When solar charging begins, the connected booster pump fills the system for the time set here.
Zone valve
This feature can control a solar accumulator charging valve. This enables charging of a second tank or second tank zone. The number on the
left next to the zone valve indicates which tank / zone is being charged by the system.
Tmax storage 2
Maximum temperature storage 2. Up to this temperature, store 2 or the 2nd store zone will be charged.
Solar storage 2
In this menu, the storage tank sensor 2 must be set.
Heat exchanger
Adds a heat exchanger and a secondary pump to the solar circuit. Function is only visible if the additional funciton Solar is activated.
Heat exchanger sensor
The sensor that is used to turn on the secondary pump. It must be on the primary side on the heat exchanger.
Burner
This function requests a burner when a request of a heating circuit or the DHW function is present. Depending on the request, the burner will
turn on in a more economic manner in the Eco-Mode if the solar circulation pump is running.
DHW request
The burner is started for a DHW - heat request.
Heating Circuit request
The burner is started for a heating circuit heat request.
Burner sensor
Reference sensor for burner function. If this temperature at the set sensor is exceeded, the burner is shut down.
Delay
Switch delay, valid for cooling and heat request. The burner first turns on after this time span if the switch conditions were reached and are
still present. This feature prevents unnecessary switching by temperature fluctuations or gives time for a renewable energy source to gen-
erate energy.
Burner offset
When using the 0-10V outputs V1 or V2 for the burner function, the requested temperature is emitted through a corresponding voltage. This
offset increases the requested temperature.
Eco mode (during solar charge)
The economy mode for this function can be operated in 2 different variants:
54
Turn off: The function is not started with an active solar charge.
Decrease:
For a heating request the function first turns on when the conditions and an additional offset were not met.
For a DHW request the function only activates when Teco is not met and de-activates when Teco + DHW-heating is achieved.
Tmax
Maximum temperature at the burner sensor. If this temperature at the set sensor is exceeded, the burner is shut down.
Boiler base temperature
Minimum temperature to avoid condensation and corrosion in the burner. Requires an assigned burner sensor. As soon as the temperature
at the burner sensor falls below the set temperature and the heating circuit is not in summer shutdown, the burner is switched on.
Base hysteresis
Only visible when the boiler base temperature is set. Switch-off hysteresis for the boiler base temperature. If the burner has been switched
on by the boiler base temperature, it runs until the boiler base temperature + base hysteresis at the burner sensor are reached.
Enable
(temporal) enable for this function
Here, the desired periods can be set in which the function is enabled.
For each weekday, three times can be specified, furthermore, you can copy individual day to other days.
Outside the set times the function is disabled.
Anti Legionella
See " Anti Legionella " on page 59.
Boiler pump
A boiler pump is turned on and off together with the burner. Function is only visible if the additional function Burner is activated.
Boiler pump Tmin
Minimum temperature at the burner sensor for enabling of the boiler pump. If this temperature is exceeded at the burner sensor, the burner
pump is activated.
Compressor
The function switches on the compressor from a heat pump if a heat request from the heating circuit or DHW sensor is present.
DHW request
The compressor is started with a DHW - heat request.
HC request
The compressor is started with a heating circuit - heat request.
Cooling request
The compressor is started when cooling is requested.
Eco mode (during solar charge)
The economy mode for this function can be operated in 2 different variants:
Turn off: The function is not started with an active solar charge.
Decrease:
For a heating request the function first turns on when the conditions and an additional offset were not met.
For a DHW request the function only activates when Teco is not met and de-activates when Teco + DHW-heating is achieved.
Heating circuit offset
The temperature offset setting for the eco operaing mode “Lower” (see above).
55
Min heat pump runtime
The compressor turns on at least for the set time.
Heat pump idle time
The compressor is blocked for this time after it is shut down.
Heat pump delay
Delay for this function.The function first turns on after this time span if the switch conditions were reached and are still present. This delay is
intended to prevent unnecessary switching operations caused by temperature fluctuations or toGive another energy source time to provide
the necessary energy.
Storage charge pump (SLP) overshoot
The pump turns off after the compressor delayed by this time.
Bivalent temperature
Below the temperature set here, the next energy source is added. If the outside temperature falls below the value set here, when using
another energy source (thermostat, electric heating rod, burner), the switch-on delay is cancelled and this is switched on immediately when
heat is required. If several additional energy sources are used, they switch on one after the other, prioritized according to the switch-on
delays.
Min. outdoor temperature
When the outdoor temperature set here is undershot, the heat pump switches off.
Periods
Approval time for the compressor function
Here the desired periods are set in which the compressor is approved. For each weekday, three times can be specified, furthermore, you can
copy individual day to other days. The compressor is shut down outside of the set times.
Anti Legionella
See " Anti Legionella " on page 59.
Loading pump
The function switches on the charge pump of a heat pump if a heat request from the heating circuit or DHW sensor is present. This function
can only be selected if a compressor was activated on a different relay.
Storage charge pump (SLP) overshoot
The pump turns off after the compressor delayed by this time.
Glycol pump
The glycol pump is turned on and off together with the compressor. Function is only visible if the additional function Compressor is activated.
Gylcol pump lag
After shutting down the compressor, the pump remains on for the time set here.
Return flow increase
With this function, for example, the return temperature of a heating circuit is increased through the storage.
56
Return flow increase Tmin
Minimum temperature at storage sensor to enable the return flow increase. As soon as this temperature at the set storage sensor is
exceeded and adequate ΔT is present, the relay is turned on.
Return flow increase Tmax
Maximum temperature set on the storage sensor set for this function If this temperature is exceeded at the RL storage sensor, the function
is deactivated again.
ΔT return flow
Switch on temperature difference:
The relay is turned on if this temperature difference is exceeded between the storage sensor and the recooling sensor.
Switch off temperature difference:
The relay is turned off if this temperature difference is undershot between the storage sensor and the recooling sensor.
Return flow sensor
Selection of the return flow sensor.
Storage sensor
Selection of the storage sensor.
Domestic hot water valve
This function activates a DHW-valve or -pump, if a DHW heat request is present.
Circulation
Depending on the temperature and time approval, a circulation pump is turned on for the DHW storage.
Tmin
If this value at the circulation sensor is undershot and the circulation is approved or there is a request through a tapping process, the cir-
culation pump is started.
Hysteresis
If the circulation Tmin value is exceeded by the value set here, the circulation pump will be shut down.
Circulation sensor
Select the temperature sensor for the circulation.
Circulation pause time
In order to prevent an excessive switching on of the circulation pump, a block time can additionally be set up here to prevent
it from being turned on again. If the circulation pump has turned off, it can first go into operation again after the expiration of the time set
here.
Purging time
If during the operation of the circulation pump, also after expiration of the optional purging time, the previously selected temperature at the
circulation sensor is not reached, the pump will turn off. This function should protect against unnecessarily long operation of the circulation
pump, for example, if the warm water storage is too cold.
Circulations periods
Operating times of the circulation
Here the desired periods are set in which the circulation is approved. For each weekday, three times can be specified, furthermore, you can
copy individual day to other days. The circulation is shut down outside of the set times.
Anti Legionella
See " Anti Legionella " on page 59.
57
Error Messages
The relay is switched on if one or several of the set protective functions are activated. This function can be inverted so that the relay is turned
on (Duration on) and then turned off again if a protective function is activated.
Error message
Activate or deactivate function
The additional function error message activates the relay for certain events and only deactivates again when the information message to
each event was read.
The following messages are available:
Collector protection
System protection
Frost Protection
Recooling
Anti Legionella
Message
Sensor error VFS1
Sensor error VFS2
Pressure monitor
In this menu, the system pressure monitoring can be activated through a direct sensor. As soon as the set pressure conditions are undershot
or exceeded, the set relay will switch on.
Pressure monitor
Relay turns on if the pressure goes below the minimum or exceeds the maximum.
RPS-Type
Type of pressure sensor
In this menu, you can adjust which pressure sensor is being used. Please note: If e.g. VFS1 is connected, RPS1 option is not shown.
RPS Max
Maximum pressure in the system. If this pressure is exceeded, the controller emits an error notification and the relay switches.
RPS Min
Minimum pressure. If this pressure is not met, the controller emits an error notification and the relay switches.
Dehumidifier
Operating mode
The operating mode of the dehumidifier function can be set here.
Cooling : In the cooling operating mode, the dehumidifier turns on when the target humidity is exceeded, if the S/W day temperature is
exceeded and the function is approved.
Cooling +Circ.: In the cooling +circulation operating mode, the dehumidifier turns on when the target humidity is exceeded, if the S/W day
temperature is exceeded and the heating circuit pump is running and the function is approved.
Year round: In the year round operating mode, the dehumidifier turns on when the target humidity is exceeded if the function is approved.
Reference humidity
Reference value for the humidity in the room.
If the value set here is exceeded, the relay will turn on the dehumidifier if this is approved for the time. The dehumidifier is turned off if the ref-
erence value hysteresis is not met.
Hysteresis
Hysteresis of setpoint for the humidity.
58
Dehumidifier periods
Approval time for the dehumidifier
Here the desired periods are set in which the dehumidifier is approved. For each weekday, three times can be specified, furthermore, you
can copy individual day to other days. The dehumidifier is shut down outside of the set times.
Parallel operation
The relay runs simultaneously with the set relay.
Parallel operation
Here you can additionally set the switch mode.
On : The function switches parallel to the set signal output.
Inverted : The function switches contrary to the set signal output.
Parallel to
Here, the output can be selected, which this function should be activated parallel to. Every available signal output can be selected.
Delay
In this menu, it is set how long to wait after switching the signal output until the parallel operated relay switches as well.
Follow-up time
In this menu, it is set how long the parallel-operated relay continues to operate after the set signal output has been deactivated.
Remote
Relay status
The relay status determines if the condition of the relay is in sleep mode, and it also applies if the controller is restarted.
Title
Here you can assign a name for the selected relay. This name also appears on the Sorel-Connect page to simplify the assignment.
Always on
Relay is permanently switched on.
Anti Legionella
The anti-legionella function is an additional function for certain relay functions such as: electric heating rod, burner, circulation,
compressor.
With the help of the anti legionella function (hereinafter referred to as: AL), the system can be heated up at selected times in order to free it
of legionella.
In the delivery state, the anti legionella function is switched off.
As soon as it has heated up with “AL” turned on, information with the date will be shown in the display.
This anti legionella function does not offer any secure protection against legionella, because the controller requires an
59
adequate added amount of energy and the temperatures cannot be monitored in the entire storage area and the connected
pipe system.
During the operation of the anti legionella function, if applicable, the storage is heated above the set value “Tmax”, which may
lead to scalding and system damage.
AL Tset
For a successful heating, this temperature has to be reached at the AL sensor(s) for the exposure time period.
AL residence time
For this period of time the AL Tsettemperatures at the activated AL-sensors have to be reached for a successful heating.
Last AL heat
This displays when the last successful heating has occurred.
AL sensor 1
On this sensor, the temperature of the AL function is measured.
AL Sensor 2
Optional AL sensor
If this sensor is set for a successful heating Tset AL have to be achieved at this sensor too for the action time.
60
Malfunctions/Maintenance
Replacing the Fuse
Repairs and maintenance may only be performed by a specialist. Before working on the unit, switch off the power supply and
secure it against being switched on again! Check that there is no power flowing!
Only use the included safeguard or a similar safeguard with the following
specifications: T2A / 250 V.
If the mains voltage is switched on and the controller still does not function or display anything,
then the internal device fuse may be defective. First find the external fault source (e.g. pump),
replace it and then check the device fuse.
To replace the device fuse, open the device as described under "See " Wall Installation " on page
11", remove the old fuse, check it and replace if necessary.
Then first recommission the controller and check the function of the switch outputs in manual mode
as described in Section 4.1.
Maintenance
In the course of the general annual maintenance of your heating system, the functions of the controller should also checked by
a specialist and the settings should be optimized if necessary.
Performing maintenance:
lCheck the date and time See " Time & Date " on page 31
lAssess/check plausibility of statistics See " Statistics " on page 30
lCheck the error memory See " Notifications " on page 30
lVerify/check plausibility of the current measurement values See " Measurement values " on page 29
lCheck the switch outputs/consumers in manual mode See " Manual " on page 32
lPossible optimization of the parameters setting (only on customers request)
Possible error messages
Possible error messages Notes for the specialist
Sensor x defective Means that either the sensor, sensor entrance on the controller or the connecting wire was defective
(See " Temperature Resistance Table for Pt1000 Sensors " on page 23).
Collector alarm Means that the temperature on the collector set under “Collector protection" was exceeded.
Restart Means that the controller was restarted, for example, due to a power outage. Check date & time!
Time & Date This display appears automatically after a longer network disruption, because the time & date must
be examined and, if applicable, adjusted.
No flow If ΔT between store and collector is 50 ° C or more for 5 minutes, this message is displayed.
Frequent on / off A relay was switched on and off more than 5 times within 5 minutes.
61
Tips
The service values include not only current measurement values and operating states, but also all of the settings for the controller.
Write the service values down just once after commissioning has been successfully completed.
In the event of uncertainty as to the control response or malfunctions the service values are a proven and successful method for
remote diagnosis. Write the service values down at the time that the suspected malfunction occurs. Send the service value table by
fax or e-mail with a brief description of the error to the specialist or manufacturer.
To protect against loss of data, record any statistics and data of particular importance at regular intervals.
Support Guideline
If there are errors with your device, please proceed as follows:
1. Read user manual
2. Check FAQ
3. Watch help-video on YouTube
4. Talk to an installation technician/tradesman
5. Contact SOREL Support - provide the following information:
What is the Problem? lInstallation problem
lNew problem
lChange request
Controller Type/Controller Name (9.1.)
Software Version (9.2.)
Program (7.1.)
Additional function (7.7. - 7.12.)
Accessories (e.g. room thermostats + Software Version)
Sensor values of the sensors (1.1. - 1.10.)
Error messages/frequency of error/error description
Further Information
Appendix
Signal
In this menu, the preset profiles for the signal can be selected or under “manual” all settings can be done personally. The settings can still be
changed after a profile has been selected.
Output Signal
In this menu the type of actors are set: heating pumps have the greatest output with a small input signal, solar pumps in contrast have very
little output with a small input signal. Solar = normal, heating = inverted. For 0-10 V pump always choose the "Normal" setting
PWM / 0-10V off
This voltage / this signal is emitted if the actor is turned off (actor with cable break detection require a minimum voltage / a minimum signal).
PWM / 0-10V on
This voltage / signal is required the actuator to switch on and run at minimum speed.
62
PWM / 0-10V max.
With this value, the maximum voltage level / maximum signal can be specified for the highest speed of the actuator, which is used, for
example, during the purging or manual operation.
Speed when „On“
In this menu, the calculation basis of the displayed speed is changed. If, for example, 30% is specified here, the signal/voltage set under
“PWM On” / “0-10V On” will be displayed during creation so that a 30% speed is present. When creating the signal/voltage of PWM Max / 0-
10V Max, 100% speed is displayed. Temporary values are calculated correspondingly.
This function does not influence the rule, but rather only the display on the status screen.
Example for signal settings
Technical data PWM and 0-10V
Show signal
Represents the set signal in a graphic and text overview.
63
Final Declaration
Although these instruction have been created with the greatest possible care, the possibility of incorrect or incomplete information cannot be excluded. Subject
as a basic principle to errors and technical changes.
Date and time of installation:
Name of installation company:
Space for notes:
Your specialist dealer: Manufacturer:
SOREL GmbH Mikroelektronik
Reme-Str. 12
D - 58300 Wetter (Ruhr)
+49 (0)2335 682 77 0
+49 (0)2335 682 77 10
info@sorel.de
www.sorel.de
Version: 13.05.2022
SOREL
64
59

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Sorel LHCC 24V bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Sorel LHCC 24V in de taal/talen: Engels als bijlage per email.

De handleiding is 4.53 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

Andere handleiding(en) van Sorel LHCC 24V

Sorel LHCC 24V Gebruiksaanwijzing - Deutsch - 65 pagina's

Sorel LHCC 24V Gebruiksaanwijzing - Français - 64 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info