- 1 - www.soha-tech.com
SH-VT200C Rev G
- NDIR CO
2
Dual sensor
- Needless calibration for
a long time
Controller has two types of
sensors, one is internal
sensor and the other is
external sensor like
SH-VT250.
Control type ;
- CO
2
, temperature and
Humidity individual control
- CO
2
+ temperature
control(OR)
- three-step fan control
- CO
2
proportional contol
This product can be
changed for quality
Improvement without
notification
CO2, Temperature, Humidity Controller
3 Relay electrical contacts output(SH-
VT200C,CNS internal relay type)
5 Relay electrical contacts output(SH-
VT200C,CNS outerl relay type)
Applications
Indoor ventilation control
Heat Ventilation Air Conditioning
System
Wine storage,distillery control
Mushroom farming greenhouse
Pig & poultry farming
Corps greenhouse and humid storage
.
SOHA TECH Co., Ltd.
Suite 104, Hagye technotown A,250-3,
Hagye-dong,Nowon-gu,Seoul, Korea
TEL : +82 -2-978-0461~2 FAX : +82-2-978-0463
http://www.soha-tech.com
- 2 - www.soha-tech.com
SH-VT200C Rev G
SPECIFICATIONS
Specification of sensor
CO
2
sensor
List
Contents
Remarks
Measuring method
NDIR
Measuring Range
0~3000ppm, 0~5000ppm,0~10000ppm
option
Display Range
0~3000ppm, 0~5000ppm,0~9999ppm
Accuracy
±60 ppm, ±3% measured value
@0~50
Response time
0 ~ 80% < 30 sec
Signal update term
Every 2.0 Seconds
Warm-up Time
@25 < 90 sec
Working Temp
-10 ~ 50
Working Humidity
0 ~ 99.5% RH
Non
condensing
temperature sensor
List
Contents
Remarks
Measuring Range
-25 ~ 85
Display Range
-19.9 ~ 99.9
Resolution
±0.3
Response time
(Min) 5 ~ (Max) 30 sec
Humidity sensor
List
Contents
Remarks
Measuring Range
0 ~ 99.9 %RH
Display Range
0 ~ 99.9 %RH
Resolution
±2 %RH
Response time
8 sec
- 3 - www.soha-tech.com
SH-VT200C Rev G
Power supply : DC 12 ~ 24V, over 250mA
Output : Relay spec.
Internal type CO
2
= From A 250V, 5A
Temp. (heater /cooler) = From A, 250V 5A
Humidity = From A 250V 5A
External type CO
2
= From A 250V 5A
Temp.(cooler) = From A 250V 5A
Temp.(heater) = From A 250V 5A
Humidity = From A 250V 5A
- 4 - www.soha-tech.com
SH-VT200C Rev G
Features
CO
2
, temperature and humidity controller
3 Relay electrical contacts output type
CO
2
= ventilation Fan, CO
2
generator
Temp. = cooler, heater
Humidity = ventilation fan, humidifier
4 Relay electronic contacts output type
(With external Relay instrument)
CO
2
= ventilation Fan, CO
2
generator
Temp. = cooler
Temp. = heater
Humidity = ventilation fan, humidifier
Three-step fan speed control by CO
2
and temperature.
We have both models which can be distinguished by internal
and external sensor, SH-VT250, transmits is our external
sensor type that can be communicated with RS-485
communication protocol.
Wall mounted type
CO
2
sensor warming-up time is about 1 minute after the
first power supplied.
During this warming-up time, device will keep OFF mode.
- 5 - www.soha-tech.com
SH-VT200C Rev G
Initial LCD
display
Selection of
control mode
(select mode
1~3)
1. Plug in the power supply and Push the [MENU] button for 2
seconds, then existing value will be displayed on LCD.
<Mode 1: individual mode>
2. Above example is no.1 mode and if you push [SET] button,
the numbers will flashes, then you can set up the mode
from 1 to 3 by [, ] button.
After you select the mode, push [SET] button for save you
selected mode and push [ESC] button to return run mode.
Then the controller will run with the mode that you set-
up.
Product name
Model name(C,CNS,CNSR)
Program version
CO2 value
Temp. value
Humidity value
Program Running
- 6 - www.soha-tech.com
SH-VT200C Rev G
Environment
control method
=Individual
control setting
CO
2
=ventilation
fan,CO
2
generator
Temp.=
cooler/heater
Humidity=
Ventilation fan,
humidifier
3. Input / Output mode
Notice : You should be careful to set up
the mode whether your device is internal
or external sensor type.
1. CO
2
ON/OFF setting(Mode = 1,2)
A. If you push [MENU] button, CO
2
setting value
and [1, On] will be displayed.
In this screen, if you push [SET] button, device
will wait for your setting with flickering related
value.
B. When numeral flashes shows number, you can modify the
value by [, ] button, In every pushing, 10ppm CO2
value will be increased or decreased
Then push [SET] button again in order to finish the
setting.
Mode
Sensor
communication
Relay output
1
Internal
Type
(SH-VT200C)
X
Individual control
2
OR control
3
3-step fan control
4
External
Type
(SH-VT200CNS)
Individual control
5
RS-485
OR control
6
3-step fan control
- 7 - www.soha-tech.com
SH-VT200C Rev G
C. If you push [] button, CO
2
OFF setting value
and [1, OF] will be displayed on LCD screen
Push [SET] button to set up.
According to OFF setting value, device will turn off
related relay for Co2.
D. When numeral flashes shows number, you can modify
the value by [, ] button and push [SET] button
again.
E. Push [ESC] button to cancel the setting value.
F. If ON setting value < OFF setting value
= CO
2
generator control
If ON setting value > OFF setting value
= ventilation fan control
G. At proportional mode [1, OF] is setting value and
[1, ON] is proportional control range.
2. Temperature ON/OFF setting (Mode = 1,2)
A. At the CO
2
setting mode if you push [] button,
You will enter temperature setting mode.
temperature
ON setting value and [2 On]
will be displayed. In this mode, push [SET] bottom
then temperature value will flicker and wait for your
setting.
- 8 - www.soha-tech.com
SH-VT200C Rev G
B. You can set the value by [, ] button and push
[SET] button again.
C. If you push [] button again, you will enter
temperature
OFF setting mode.
Exist value and [2 OF] will be displayed on the
LCD screen then push [SET] button to set up.
D. If you put [, ] button shortly, setting value
will be increased by 0.1%, but keep pushing the
button, setting value will be increased by 1%
E. In accordance with internal or external relay, Output
value will be distinguished.
i. Internal relay model for temp. control
(SH-VT250, CNS)
Heater on : ON setting value < Off setting value
Cooler on : ON setting value > Off setting value
ii. External relay mode for temp. control
(SH-VT200CNSR)
Depending on On settingandOff setting
If recent ambient temperature is higher than On
Setting, Cooler will run.
Inversely, if ambient temperature is lower than
OFF setting, Cooler will run.
- 9 - www.soha-tech.com
SH-VT200C Rev G
[SH-VT200CNSR with using external relay]
F. In the proportional control mode, value of [2,
OF] will be setting value and value of [2, ON]
will be bandwidth of proportional control range.
3. Humidity ON/OFF setting mode = 1,2,4,5)
A. In the temperature setting mode, if you push []
button, humidity
ON setting value and [3, On ]
will be displayed on the Top of LCD and
push [SET] button to set up.
B. If you put [, ] button shortly, setting value
will be increased by 0.1%, but keep pushing the
button, setting value will be increased by 1%
And push [SET] button for setting.
- 10 - www.soha-tech.com
SH-VT200C Rev G
Environment control
method
CO
2
, Temperature,
Humidity
proportional
control
If setting value is
0,its ON/OFF
individual control
and if not 0,
its proportional
control.
C. If you push [] button, humidity OFF setting value
and [3 OF ] will be displayed on the Top of LCD and
push [SET] button to set up.
D. If you put [, ] button shortly, setting value
will be increased by 0.1%, but keep pushing the
button, setting value will be increased by 1%
And push [SET] button for setting.
E. Push [ESC] button to escape the setting mode,
and device will run with set values at the same
time .
1. If you push [] button again, ventilation (CO
2
)
proportional control setting value and [4, ]
will be displayed on the bottom of LCD and
push [SET] button to set up.
[Example of 60secound setting in proportional control]
2. The numeral flashes and you can set the value by
[, ] button and push [SET] button again.
- 11 - www.soha-tech.com
SH-VT200C Rev G
3. If you push [] button, temperature proportional
control setting value and [4, ] will be
displayed on the Top of LCD and push [SET]
button to set up.
[Example of 30secound setting in proportional
temperature control]
4. The numeral flashes and you can set the value by
[, ] button and push [SET] button again.
5. If you push [] button, humidity proportional
control setting value and [4, ] will be
displayed on the top of LCD and push [SET]
button to set up.
[Example of 50secound setting in proportional
humidity control]
6. The numeral flashes and you can set the value by
[, ] button and push [SET] button again.
7. Push [ESC] button to escape the setting mode,
and device will run with set values at the same time
- 12 - www.soha-tech.com
SH-VT200C Rev G
Environment
control method
= three-step fan
control setting
method for CO
2
and
temperature.
(Humidity is only
for display, not for
control.)
CO
2
Low, Middle, High setting(Mode = 3,6)
1. If you push [] button, CO
2
low setting value and
[1, Lo] will be displayed on the bottom of LCD and
push [SET] button to set up.
2. The numeral flashes and you can set the value by
[, ] button and push [SET] button again.
3. Middle, High setting method is same as Low.
CO
2
Low setting picture CO
2
Middle setting picture
CO
2
High setting picture
Temperature Low, Middle, High setting(Mode = 3,6)
1. If you push [] button, Temperature
low setting value
and [2, Lo] will be displayed on the bottom of LCD and
push [SET] button to set up.
2. The numeral flashes and you can set the value by
[, ] button and push [SET] button again.
3. Middle, High setting method is same as Low.
Temp. Low setting picture Temp. Middle setting picture
- 13 - www.soha-tech.com
SH-VT200C Rev G
OR control
method
Relay output
= two-step
CO
2
+ Temp. => FAN
Humidity=>humidifier
(ventilation
control method)
Temp. High setting picture
4. After set all setting, push [ESC] button to escape the
setting mode, and device will display run mode with
running with set values at the same time.
1. CO
2
output relay will be used, and setting method
is same.
Control : CO
2
Temp. Output
ON OFF = ON
OFF ON = ON
ON ON = ON
OFF OFF = OFF
2. Humidity controls humidifier or ventilation fan
separately.
3. If you set the ON value of CO
2
or temperature 0, the
item will be excluded from control setting. For example,
If you set CO
2
ON value 0, it controls by the
detected value from the CO
2
sensor.
- 14 - www.soha-tech.com
SH-VT200C Rev G
Three-step FAN
control method
Relay output
CO
2
+ Temperature
integrated
control type
Proportional
control
CO
2
=> FAN
Temp.=> heater
Humidity=>humidifier
1. CO
2
+ Temperature setting : 3-step FAN control.
(internal electrical contacts type)
CO
2
Relay electrical contact : Low Speed
Temp. Relay electrical contact : Middle Speed
Humidity Relay electrical contact : High Speed
2. CO
2
+ Temperature setting : 3-step FAN control.
(External electrical contacts type)
CO
2
Relay /electrical contact : Low Speed
Temp. cooler Relay /electrical contact :
: Middle Speed
Temp. Heater Relay/ electrical contact
: High Speed
3. At the 3-step FAN control, ON/OFF gap is as below
CO
2
: setting value 50ppm,
Temperature : setting value 0.5
4. Humidity only can be displayed in the 3-step FAN control
mode.
1. Ventilation proportional control (CO2) :
[1, OF] value = setting value
[1, ON] value = proportional bandwidth.
According to setting time of proportional control mode,
Device will control the output comparing with detected
value.
Ex) CO
2
ON = 1500, CO
2
OFF = 1000, Time = 60 seconds,
CO
2
relay output time will be 0”at 1000ppm.
and CO2 relay output time will be 60 seconds at
1500ppm.
If detected value of CO
2
is 1300ppm, then the FAN
will be ON for 36 seconds(60% of60 seconds) and OFF
for 24seconds repeatedly.
- 15 - www.soha-tech.com
SH-VT200C Rev G
ON/OFF time will be changed by the detected value
of CO
2
.
2. Temperature proportional control mode:
This control mode is distinguished by using external
relay.
A. In case of using internal relay for temperature
output ( SH-VT200C, CNS)
[1, OF] value = setting value
[1, ON] value = proportional bandwidth.
According to setting time of proportional control mode,
Device will control the output comparing with detected
value.
Ex) Temp.ON = 25, Temp.OFF = 20, Time = 60 seconds,
If detected value of Temp.
is 23, heater relay output
time will be 36seconds(60%)ONand 24seconds0FF
because detected temp.23 is 60% position between 20
and 25.
So the heater will be ON for 36 seconds (60% of 60
seconds) and OFF for 24 seconds repeatedly.
ON/OFF time will be changed automatically in accordance
with the detected value of temperature.
B. In case of using internal relay for temperature
output ( SH-VT200CNSR),
Gap between [2, OF] and [2, ON] will be reference
bandwidth for proportional control.
If detected value is higher than setting value, output
of cooler will be applied to proportional control,
inversely if detected value is lower than OFF value,
output of heater will be applied to proportional control.
- 16 - www.soha-tech.com
SH-VT200C Rev G
Ex) Temp.ON = 25, Temp.OFF = 20, Time = 120 seconds,
If detected value of Temp.
is 29, relay output of
cooler will turn ON.
Since reference bandwidth is 5 (from 20 to 25),
reference high temperature will be 30.
In this case, detected Temp.29 is 80% position,
Therefore, relay output will turn on for 96second(80%)
and turn off for 24second repeatedly.
ON/OFF time will be changed automatically in accordance
with the detected value of temperature.
And with this same setting, if detected value of Temp.
is 18, relay output of heater will turn ON.
Since reference bandwidth is 5 (from 20 to 25),
reference low temperature will be 15.
In this case, detected Temp.18 is 40% position,
Therefore, relay output will turn on for 48second(40%)
and turn off for 72second repeatedly.
ON/OFF time will be changed automatically in accordance
with the detected value of temperature.
3. Humidity proportional control :
[2, OF] value = setting value
[2, ON] value = proportional bandwidth
According to setting time of proportional control mode,
Device will control the output comparing with detected
value.
Ex) Humidity ON = 90.0%, Humidity OFF = 95.0%,
Time = 60 seconds,
If detected value of humidity
is 92%, humidity relay
Output(humidifier) time will be 36seconds(60%)ONand
24seconds0FF
- 17 - www.soha-tech.com
SH-VT200C Rev G
Sensor
Compensation
CO
2
compensation
Temp. compensation
Humidity
compensation
because detected humidity,92% is 60% position between
90% toward 95%.
ON/OFF time will be changed automatically in accordance
with the detected value of humidity
Display of CO
2
sensor compensation
Display of Temperature sensor compensation
Display of Humidity sensor compensation
1.Keep pushing [SET+ ] buttons for 3 seconds at the same
time to enter compensate mode from normal working mode.
and push [SET] button to set up. Then value will show
flickering in order to get the new value.
after setting the value by [, ] button, push [ESC]
button to exit.
If set value is higher or lower than detected value,
compensate the value as much as its gap.
2. Initial value is 0(zero).
3. push [ESC] button to return normal working mode.
- 18 - www.soha-tech.com
SH-VT200C Rev G
VT250 ID Setting
( This setting is
for only external
sensor model)
Keep pushing [SET+ ] buttons for 3 seconds at the same
time to enter compensate mode from normal working mode.
and push [] button again at humidity compensation mode
in order to enter ID setting mode.
[ID setting mode]
1. If you push [] button at humidity compensation mode,
[6 ID] will be displayed and top of the LCD screen
show the communication ID of VT250(sensor) which is
connected with VT200CNS, CNSR.
2. Then push [SET]button, device will enter ID setting
mode. And you can set the value with [, ] buttons.
3. . Initial ID is set as0(zero)
Caution.
When you change the ID, number of ID should be same as
Dip switch in the VT250, if it is not, device will not
work properly.
Caution.
Once you set the ID, VT250 will work with requested
transmit mode automatically so you need to be careful.
- 19 - www.soha-tech.com
SH-VT200C Rev G
Individual control time chart
- 20 - www.soha-tech.com
SH-VT200C Rev G
CO
2
+ Temp. ventilation FAN control,
Humidity(Humidifier & FAN control) time chart
- 21 - www.soha-tech.com
SH-VT200C Rev G
Proportional control time chart
Similar to individual(ON/OFF) control but its applied to ventilation fan and
heater only.
If ON time is longer since big capacity of heater / fan / humidifier, widen
the gap of ON/OFF setting value, and ON time will be reduced proportionally.
Oppositely in the case of ON time is short, narrow the ON/OFF gap and ON
time will take a long time.
You can widen the time to prevent working of frequent but in the case of
ventilation fan, it might be a little hard to ventilate properly.
- 22 - www.soha-tech.com
SH-VT200C Rev G
3-step ventilation FAN control(Low, Middle, High) time chart
- 23 - www.soha-tech.com
SH-VT200C Rev G
Wiring diagram(Internal type Relay output) SH-VT200C
- 24 - www.soha-tech.com
SH-VT200C Rev G
Wiring diagram(Internal Relay output with external sensor ) SH-VT200CNS
- 25 - www.soha-tech.com
SH-VT200C Rev G
Wiring diagram(External type Relay output) SH-VT200CNSR
- 26 - www.soha-tech.com
SH-VT200C Rev G
6

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Sohatech SH-VT200C bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Sohatech SH-VT200C in de taal/talen: Engels als bijlage per email.

De handleiding is 2,75 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info