Building Technologies 74 319 0614 0 c 20.05.2008 4/26
- If it flashes, the detector wiring may be faulty
- If it is lit, the controller is overridden by a remote operation
facility (room unit or changeover switch). Set room unit to
operating mode
or open the external switch)
4. Set operating mode selector to
.
5. Set heating curve potentiometer
to 4 and setting knob
to +8 °C:
- Flow temperature must rise: burner on, valve open, heat-
ing circuit pump on (electro-thermal actuators respond with
a certain delay!)
- If not: check wiring of the detectors (flow/boiler, outside de-
tector), actuator/burner and heating circuit pump
6. Set operating mode selector to
.
7. Set heating curve to 0.25 and setting knob
to –8 °C:
- Burner must switch off (observe minimum running time of
4 minutes), valve must travel toward "colder", and heating
circuit pump must remain activated
- If not: check wiring of the detectors (flow/boiler, outside de-
tector), actuator/burner and heating circuit pump
Commissioning the remote operation facility
1. Set the controller's operating mode selector to one of the two
Auto positions
2. If a room unit is present: select operating mode
on the
room unit
- Check the "Override" LED on the controller: must be lit
- If not: check wiring of the room unit
3. If a changeover switch is present: close it (gives operating
mode
on the controller).
- Check the "Override" LED on the controller: must be lit.
- If not: check wiring of the changeover switch
Commissioning of D.h.w. heating
(only RVP211)
1. The D.h.w. temperature must be around 30 °C (check by
touching or use a measuring instrument).
2. Set the controller's operating mode selector to
.
3. Set setting knob
to 60 °C.
- D.h.w. temperature must rise: charging pump on or
changeover valve open
- If not: check wiring of the d.h.w. temperature detector and
the heating circuit pump, or the changeover valve
4. Set setting knob
to 10 °C (observe overrun time)
- Charging pump or changeover valve must switch off
- If not: check wiring of d.h.w. temperature detector
5. Reset setting knob
to 55 °C (factory-setting).
Setting elements
Refer to figure
3
on page 24
1 Opening for time switch
2 LED for "Override"
3 Operating mode selector
4 Setting knob for heating curve
5 Setting knob for setback
6 Setting knob for d.h.w. temperature (only RVP211)
7 Setting knob for normal room temperature
8 Coding switches
9 Setting potentiometer for authority of room temperature
and quick setback active / inactive
10 Setting potentiometer for max. limitation of flow or boiler
temperature
11 Setting potentiometer for ECO heating limit
12 Setting potentiometer for switching differential
Coding switches
Function Switch position on the left Symbol Symbol Switch position on the right
Type of regulating unit Control of a motorized valve
Control of a atmospheric or
forced draught burner
Type of control Three-position (modulating)
Two-position (on/off)
Frost protection Yes, frost protection
No, no frost protection
D.h.w. priority (only RVP211)
With priority (absolute). Underfloor
heating systems and boiler opera-
tions: always set to abs.!
No priority (parallel)
RVP211 with boiler temperature control:
Regulating unit for d.h.w. heating Changeover valve
Charging pump
Setting potentiometers
Settings must be determined during the planning phase.
If missing, the following guide values can be used.
Potentiometer Function Setting range Guide value Notes
Switching differential
with two-position
control
1…20 K Burner control: 6 K
Authority of room
temperature on flow
temperature control
0…100 % authority
Off = quick setback is
inactive
50 % (quick setback
is active)
Plants with no room unit: setting is inactive
Plants with no outside detector:
Setting 0…100 % = quick setback is active
Setting Off = quick setback is inactive
Heating limit for ECO
automatic energy
saver
–10…+8 K (referred to
the room temperature
set value)
–3 K (gives a heat-
ing limit of 17 °C at a
room temperature
set value of 20 °C)
Off = function disabled
Max. limitation of flow
or boiler temperature
10…100 °C Guide value for un-
derfloor and ceiling
heating systems:
55 °C max.
Off = function disabled
Settings on the controller
Seal the transparent cover, if required.
Heating curve diagram: Refer to figure
4
on page 24
T
A
Outside temperature [°C]
1. Set heating curve as specified in the planning documen-
tation or in compliance with local practices.
2. Reset setting knob
to 0 (factory-setting, corresponds
to 20 °C room temperature).
3. Leave setting knob
to –6 °C (factory-setting).
4. Set operating mode selector to one of the two
Auto posi-
tions.
5. Set time switch as indicated in the operating instructions.
T
V
Flow temperature [°C]
4

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Siemens RVP201 bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Siemens RVP201 in de taal/talen: Nederlands, Duits, Engels, Frans, Italiaans, Spaans, Deens, Zweeds, Fins als bijlage per email.

De handleiding is 0,49 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Andere handleiding(en) van Siemens RVP201

Siemens RVP201 Gebruiksaanwijzing - English - 46 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info