Siemens RDF301, RDF301.50, RDF600KN Basic documentation CE1P3171en
Building Technologies Functions 2012-10-04
3.12.2 Description of communication objects
Obj Object name Function Type/ length Flags
1 System time Time and
date
19.001
8 Byte
CWU
System time for display on the room thermostat. See parameter
P07 (3 or 4)
3 Time of day Time and
date
10.001
3 Byte
CWU
Another object for receiving the time of day for display on the room
thermostat. See parameter P07 (3 or 4)
4 Fault information Alarm
Info
219.001
6 Byte
CT
Common alarm output. If an alarm occurs, the alarm number is
transmitted
5 Fault state Faulty /
normal
1.005
1 bit
CT
Common alarm output. If an alarm occurs, the alarm flag is set
6 Fault
transmission
Enable /
disable
1.003
1 bit
CWU
A supervisor alarm system can disable the broadcasting of alarms
by the devices. This has no impact on the local display of alarms.
After a timeout of 48 hours, the sending of faults will automatically
be enabled again.
7 Room operating
mode:
Preselection
Auto
Comfort
PreComf.
Economy
Protection
20.102
1 Byte
CWTU
Controls the room operating mode selection of the thermostat via
bus.
The command can also be submitted as four 1-bit communication
objects (8...11). The last interaction wins – either from local
operating mode button or via bus.
Note: The thermostat will transform Precomfort either into
Economy or Comfort (selectable via P88).
8
9
10
11
Operating mode:
Preselection
Auto
Comf
Eco
Prot
Trigger 1.017
1 bit
CW
Switch room operating mode to either Auto, Comfort, Economy or
Protection.
The last interaction wins – either from the local operating mode
button or via bus.
12 Room operating
mode: Time
switch
Comfort
Economy
PreComf.
Protection
20.102
1 Byte
CWU
This information is provided by a central time switch or a
supervisor and defines the actual HVAC operating mode.
The command can also be submitted via three 1-bit
communication objects (13...15).
Protection has the highest priority and cannot be overridden.
Note: The thermostat will transform Precomfort either into
Economy or Comfort (selectable P88).
13
14
15
Time switch
Comfort
Economy
Protection
Trigger 1.017
1 bit
CW
Switch the HVAC mode to either Comfort, Economy or Protection
mode.
Obj Object name Function Type/ length Flags
16 Room operating
mode: State
Comfort
Economy
Protection
20.102
1 Byte
CRT
Effective room operating mode used by the thermostat
(considering time switch, user selection, window contact, etc.) This
state information is available via one 8-bit enumeration or three 1-
bit communication objects (17...19). Note: The thermostat does not
support Precomfort.
17
18
19
Room operating
mode:
State Comfort
State Economy
State Protection
ON
OFF
1.002
1 bit
CT
Corresponding communication object sends "True"
20 Window state Open
Closed
1.019
1 bit
CWU
The thermostat is set to Economy mode if value “1” (open) is
received. It switches back to the previous mode when the value is
“0” (closed).
"Window state" is sent e.g by a KNX switch or a KNX presence
detector. It has the same effect as the local operating mode
switchover contact X1, X2 (parameter P38, P40).
Only one input source must be used, either local input X1/X2 or
KNX bus.
21 Room
temperature
Temp .
value
9.001
2 Bytes
CRT
The value of the room temperature measured via built-in or
external sensor is available via this communication object.
22 Room tempera-
ture: Comfort
basic setpoint
Temp .
value
9.001
2 Bytes
CWU
If function "Temporary setpoint" is enabled via parameter P69, then
after an operating mode change, the setpoint adjustments made by
the user and via communication object 23 will be dismissed and
the thermostat will be reset to the Comfort basic setpoint.
Note: Setpoints that have been changed via the local HMI may be
overwritten during a system startup from a central master
controller, e.g.RMB795.
The Comfort basic setpoint is stored in EEPROM (see section
3.3.2).
The service life of the EEPROM depends on the number
of write cycles. Never write this communication object cyclically!
23 Room
temperature:
Comfort setpoint
Temp .
value
9.001
2 Bytes
CWTU
Communication object used to shift the setpoint used by the
thermostat (see section 3.3.2). Same priority as local setpoint shift
on the ther
mostat. The last intervention wins.
Note: The Comfort basic setpoint (object 22) will not be changed.
24 Current setpoint Temp .
value
9.001
2 Bytes
CRT
Current setpoint, including shift, compensation, etc., used by the
thermostat for temperature control
25 Heating output
primary
0…100 % 5.001
8 bit
CRT
Indicates the position of the heating actuator of first stage.
E.g. 2-pipe with electric heater application: Output of heating coil.
26 Heating output
secondary
0…100% 5.001
8 bit
CRT
Indicates the position of the heating actuator of the second stage.
E.g. 2-pipe with electric heater application: Output of the electric
heater.
55

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Siemens RDF600KN bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Siemens RDF600KN in de taal/talen: Engels als bijlage per email.

De handleiding is 2,58 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Andere handleiding(en) van Siemens RDF600KN

Siemens RDF600KN Gebruiksaanwijzing - Nederlands - 2 pagina's

Siemens RDF600KN Gebruiksaanwijzing - Deutsch - 2 pagina's

Siemens RDF600KN Gebruiksaanwijzing - Français - 2 pagina's

Siemens RDF600KN Installatiehandleiding - Alle talen - 2 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info