CE1B3076.1en / 02.Jun 2010 Subject to change Siemens Building Technologies
Button lock
Press operating mode button
for 7 seconds to lock or unlock the buttons if
manual button lock is configured (parameter P14 = 2).
The thermostat automatically locks the buttons 30 seconds after the last
adjustment if "Auto lock" is configured (P14 = 1).
The key symbol
indicates locked buttons.
Reminder to clean filters
External faults
Commissioning (by qualifie
d HVAC installer)
To adapt the thermostat to your system and optimize the control performance, a number
of control parameters can be adjusted. This can also be made during operation without
opening the thermostat.
Control sequence
Recalibrating the sensor
Note: Economy mode
The Economy setpoints are factory-set to 15 °C for heating and 30 °C for
cooling. Use parameters P11 and P12 to adjust the values.
Important: You can set these setpoints to OFF; the thermostat then is
inactive, i.e. no protective heating or cooling function. Risk of frost!
Control parameters
Proceed as follows to change the most important control parameters:
(Your HVAC installer can set additional parameters)
+ / -
+ / -
+ / -
+ / -
1. Set the thermostat to Protection
2. Press - and + simultaneously for a minimum of 3 seconds.
Release them and, within 2 seconds, press + again for 3 seconds. "P01" is displayed.
3. Repeatedly press the + or button to select the required parameter.
P01 P02 P08 P13
+-+
--
+
3057z03
P14
-
+
-
P12
+-
4. Press + and simultaneously, the current value of the selected parameter starts to flash, allowing you to change
the value by repeatedly pressing + or .
5. The next parameter is displayed when you press + and again simultaneously.
6. Repeat steps 3 to 5 to display and change additional parameters.
7. Press + or until "End" is displayed, and then press + and simultaneously to save the change and exit parameter
entry mode. 10 seconds after the last display or setting, all changes are saved and the thermostat will leave parame
t
entry mode.
Please record all changes you make! (All temperature settings can be made in increments of 0.5 K)
FIL
This message reminds you to clean the filter on your HVAC equipment.
It will appear after __________ "fan operating hours" and disappear when
the thermostat is set to Protection (
). This reminder must be configured by
your HVAC installer.
AL1
AL2
This alarm message tells you an external alarm has occurred:
AL1 : ______________________
AL2 : ______________________
The alarms are configured by your HVAC installer
The thermostat can be used in systems either for heating only or cooling
only, manually selection of heating or cooling, or automatic heating / cooling
changeover. Depending on the selected application, the relevant modes are
available and can be adjusted by commissioning parameter P01 if needed.
The factory setting for 2-pipe and single duct application is "Cooling only",
and for 4 pipe application "Heating and Cooling"
If the room temperature displayed by the thermo
stat does not agree with the
temperature effectively measured (after min 1 hour of operation), the tem-
perature sensor can be recalibrated. With parameter P05 the temperature can
be adjusted by + or – 0.5 °C up to a maximum of + / - 3 °C.
Para-
meter
Description
Factory setting Setting range
P01 Control sequence
2-pipe, Single duct: [0…3]
1 (Cooling only)
4-pipe:. [2…4]
4 (Heating & Cooling)
0 = Heating only
1 = Cooling only
2 = Manual H or C
3 = Auto Changeover
4 = Heating & cooling
P02 Mode selection by user via operating mode button 1 (Protection, Comfort) 1 = Protection, Comfort,
2 = Protection, Comfort,
Economy
P04 Selection of °C or °F °C °C or °F
P05 Sensor calibration 0.0 K – 3 ... +3 K
P06 Standard temperature display 0 (Room temp.) 0 = Room temperature
1 = Setpoint
P07 Additional user information 0 (no display) 0 = no display
1 = Temp in °C / °F
P08 Comfort basic setpoint 21 °C 5 ... 40 °C
P09 Minimum setpoint limitation in Comfort (WminComf) 5 °C 5 ... 40 °C
P10 Maximum setpoint limitation in Comfort (WmaxComf) 35 °C 5 ... 40 °C
P11 Setpoint of heating in Economy mode (WheatEco) 15 °C OFF, 5 °C…WcoolEco
P12 Setpoint of cooling in Economy mode (WcoolEco) 30 °C OFF, WheatEco…40°C
P13 Electric heater in cooling mode ON OFF = Disabled
ON = Enabled
P14
Button lock
(Press operating mode button for 7 seconds to lock or
unlock the buttons)
0 (Disabled) 0 = Disabled
1 = Auto lock
2 = Manual lock
2

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Siemens RDF340 bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Siemens RDF340 in de taal/talen: Engels als bijlage per email.

De handleiding is 0,32 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Andere handleiding(en) van Siemens RDF340

Siemens RDF340 Gebruiksaanwijzing - Deutsch - 2 pagina's

Siemens RDF340 Installatiehandleiding - Alle talen - 2 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info