Siemens Building Technologies CM2N3204E / 1.1999
Landis & Staefa Division 17/20
47 Fan overrun time
3)
00.00...30.00 mm.ss 05.00 mm.ss
48 Min. heating circulator running time
11)
00.00...30.00 mm.ss 05.00 mm.ss
49 Heating circulator kick interval
10)
00.00...24.00 hh.mm/
Auto/Cont Auto
50 Alarm delay air flow start
12)
00.00...10.00 mm.ss 00.20 mm.ss
51 Alarm delay air flow operation
12)
00.00...10.00 mm.ss 00.10 mm.ss
52 Alarm delay AUX
12)
00.00...05.00 mm.ss 00.00 mm.ss
53 E7, E8 control input on time 4) 00.00...12.00 hh.mm 00.00 hh.mm
54 Startup time (damper fully closed)
5)
00.00...60.00 mm.ss 00.00 mm.ss
55 Preheating time 00.00...10.00 mm.ss 00.00 mm.ss
56 Power up start delay
13)
00.00...30.00 mm.ss 00.00 mm.ss
57 Setpoint 10...+30 °C 1 °C
58 P-Band 1...100 K 10 K
59 TN
2)
00.00...04.00 mm.ss 01.00 mm.ss
60 Switching value fan speed I 500...1800 ppm 700 ppm
61 Switching value fan speed II 500...1800 ppm 1200 ppm
62 Design value full occupancy 500...1800 ppm 1000 ppm
63 P-band 100...800 ppm 400 ppm
64 Hours run counter
9)
0...9999 x 10 h (Read value)
65 Operation lock
6)
OFF/On OFF
66 RWI software version
7)
"00.00" (Read value)
67 Communication address
8)
----,0...126 - - - -
1) Indicates whether input E7, E8 is open or closed (control signal «yes» or «no»)
2) Integral action time (T
n
) = 0 s means: P-control for the respective control sequence
Integral action time (T
n
) > 0 s means: PI-control for the respective control sequence
3) Only when the RWI65.02 is configured for an electric air heater battery.
During the overrun time, the fan runs at speed I. On completion of the selected overrun time, the fans will
be switched off and the outside air dampers closed
4) Period of time during which the plant - after arrival of a pulse (> 2 s) at E7 or E8 - shall operate.
When set to 0 min, the plant is switched on or off the moment the signal arrives at E7 and E8 (external
time switch) (only in Automatic mode and when the internal time switch has switched off or is permanently
deactivated)
5) Period of time during which the plant may operate with 100 % recirculated air (after plant startup)
6) If operating level 1 is locked (data point value = On), it is not possible to change any values for two
minutes after closing the front door (exception: summer-/wintertime changeover).
Enabling by reopening the front door
7) The display shows the actual program number (software version)
8) Must be set if the controller is equipped with a communication module. If no communication module is
used, the value set has no effect on the RWI 65.02
9) Counted are the number of fan operating hours.
The reading can be reset either to zero or to the former value. Proceed as follows:
1. Press function button 10 (line 10)
2. Press setting button «» if the meter shall be reset to zero, or setting button «+» if the meter
shall
be reset to the former value
3. To confirm the resetting, press function button 10 again.
10) Active only if coded for hot water heating coil!
00.00 ð Circulator kick interval is disabled
00.05 - 24.00 ð Circulator kick occurs for 30 s according to the selected interval time
Auto ð Circulator is activated for 30 s every 24 h, or runs continuously when the
outside temperature is < 5 °C; the minimum circulator running time (data
point 48) is maintained
Cont ð Circulator continuously on
11) The setting of a minimum running time avoids too frequent activation/deactivation of the circulator
12) To avoid unnecessary faulty alarms, the fault status signal can be delayed
13) After a power failure and subsequent power restoration, it may be necessary to bring the controller back
into operation with a certain delay. This is to make certain that after a power failure, all plant elements
connected to the same mains network will not be switched on at the same time (peak loads)
14) To protect the plant, the second fan speed is disabled at very low outside temperatures. In that case, only
the first fan speed will be enabled. To avoid unnecessary fan speed changes when outside temperatures
greatly vary, a hysteresis of 2 K is used
Time elements
HR anti-icing protection
Demand controlled ventilation
Miscellaneous
Explanations
17

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Siemens AEROGYR RWI65.02 bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Siemens AEROGYR RWI65.02 in de taal/talen: Engels als bijlage per email.

De handleiding is 0,25 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Andere handleiding(en) van Siemens AEROGYR RWI65.02

Siemens AEROGYR RWI65.02 Gebruiksaanwijzing en installatiehandleiding - Nederlands - 73 pagina's

Siemens AEROGYR RWI65.02 Gebruiksaanwijzing - Deutsch - 50 pagina's

Siemens AEROGYR RWI65.02 Gebruiksaanwijzing - Français - 22 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info