744660
17
Verklein
Vergroot
Pagina terug
1/36
Pagina verder
|17
EN
16
11. INSTALLING THE STOVE
General information
Note
Assembly may only be performed by authorised specialist
companies.
Note
Please observe the regional safety and building regulations. Please
contact your master chimney sweep in this context.
Note
Only use heat-resistant sealing materials as well as corresponding
sealing strips, heat-resistant silicon and rock wool.
Note
Also take care that the flue does not project into the free cross-
section of the chimney.
Note
In case of room-air independent operation the stove pipe
connections must be tightly sealed permanently. Use a heat-proof
silicon to position the stove pipe on the conical supports of the flue
tube nozzles and for insertion in the chimney flue lining.
Note
The stove should not be pushed on unprotected floors.
Tip
Strong corrugated cardboard, cardboard or e.g. old carpet is useful
to assist assembly and as a base. The stove can also be pushed on
this cardboard or carpet.
We recommend original flue pipes from RIKA for proper connection.
Connection to the chimney
Q The device must be connected to an approved
chimney for solid fuels. The chimney must have
a diameter of min. 100 mm for pellet stoves and
130 mm -150 mm for log wood stoves depending on the diameter
of the flue pipes.
Q Avoid long flue pipes to the chimney. The horizontal length of the
flue pipe should not exceed 1.5 metres.
Q Avoid to many bends of the flue gas pipes. There should not be
more than 3 bends in the exhaust pipe.
Q Please use a connection with a cleaning opening.
Q Connections must be made of metal and must meet the
requirements of the standard (install the connections airtight).
Q Before installing a chimney calculation must be made. The
evidence must be performed for single occupancy to EN13384-1
and EN13384-2 for multiple occupancy.
Q The maximum draft of the chimney should not exceed 15 Pa.
Q The derivation of the flue gases must be guaranteed even during
a temporary power outage.
Note
If connecting to multiple connection chimneys and depending on
country regulations, additional safety equipment is required. Your
local chimney sweep will advise you in this case.
Note
Be sure to prevent condensed water from entering via the flue
connection. You may need to have a condensate ring installed -
ask your chimney sweeping expert for more information. Damages
caused by condensate are excluded from manufacturer’s warranty.
Connecting to a steel chimney
The connection must be calculated and shown with EN13384-1
and EN13384-2.
Use only insulated (double) stainless steel tubes (flexible aluminum
or steel tubes are not permitted).
An inspection door for regular inspection and cleaning must be
present.
The flue pipe connection to the chimney has to be air-tight.
Combustion air
Every combustion process requires oxygen from the surrounding air.
This so-called combustion air is removed from the living are in the
case of individual stoves without external air connections.
This air removed must be replaced in the living space. Very tightly
sealed windows and doors in modern flats may mean that too little
air replaces that used. The situation also becomes problematical due
to additional venting in flats (e.g. in the kitchen or WC). If you cannot
feed in external combustion air, then air the room several times a
day to prevent negativce pressure in the room or poor combustion.
Feeding in external combustion air
only for devices which are able to run in room-air independent
operation.
Q Combustion air must be fed to the stove from outside via a sealed
pipe for operation independent of the room air. According to
EnEV, it must be possible to shut off the combustion air pipe. The
open/closed setting must be clearly recognisable.
Q Connect at the air intake either a pipe Ø 125 mm for log wood and
combi stoves, or Ø 50 mm or Ø 60 mm for pellet stoves. Fix it with
a hose clamp (not included!). At pellet stoves with longer intake
pipes than 1 m the diameter should be increased to 100 mm. (see
RIKA range).
Q To ensure sufficient air intake, the intake pipe should not exceed
max. 4 metres and have max. 3 bends.
Q If the line leads outside it must have a windbreak.
Q In extreme cold pay attention to icing on the air intake opening
(check).
Q It is also possible to suction in combustion air directly from
another sufficiently vented room (e.g. cellar).
Q The combustion air pipe must be tightly connected (adhesive or
cement) permanently to the air nozzles of the stove.
Q If you do not use the stove for a long time, please close the
combustion air intake to prevent the stove from moisture.
Note
Please note that problems may arise due to updrafts in the case
of combustion air supply from an integrated chimney ventilation
shaft. If the combustion air flowing downwards is heated it may
rise and thus counter the chimney with a resistance which in turn
reduces the negative pressure in the combustion chamber. The
chimney manufacturer is to guarantee that the resistance for the
combustion air is a maximum 2 Pa even in the least favourable
operating state of the chimney.
If one or more of these conditions does NOT apply, the result is poor
combustion in the stove and negative pressure in the installation
room.
17

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Rika Revo II RAO bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Rika Revo II RAO in de taal/talen: Nederlands, Duits, Engels, Frans, Italiaans, Spaans, Zweeds als bijlage per email.

De handleiding is 11,65 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Andere handleiding(en) van Rika Revo II RAO

Rika Revo II RAO Gebruiksaanwijzing - Nederlands - 24 pagina's

Rika Revo II RAO Gebruiksaanwijzing - Deutsch - 24 pagina's

Rika Revo II RAO Gebruiksaanwijzing - English - 24 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info