EN
Prior to set up
Floor bearing capacity
Ensure that the substructure is capable of bearing the weight of the
stove prior to set-up.
Note
No modifications may be made to the firing installation. This also
leads to loss of warranty and guarantee.
Floor protection
A glass, sheet steel or ceramic plate is recommended, if the floor is
combustible (wood, carpet, etc.). Please observe the respective local
regulations and rules.
Flue pipe connection
Q Flue pipes pose a particular source of hazard regarding gas leaks
and fire. Get the advice of an authorised specialist company for
the layout and assembly.
Q Please observe the corresponding installation guidelines for walls
panelled with wood when connecting your flue pipes to the stove.
Q Observe the formation of flue gas (atmospheric inversion) and
draughts when the weather is unfavourable.
Q Infeed of too little combustion air can lead to smoke in the rooms
or to flue gas leaks. Hazardous deposits in the stove and chimney
may also occur.
Q If flue gas escapes, let the fire burn out and check whether all the
air inlet openings are free and the flue gas pipes and the stove
pipe are clean. If in doubt notify the master chimney sweep since
draught malfunctions may be connected to your chimney.
The correct chimney connection
There are several ways to connect your stove to the chimney, eg:
*1
*2
*3
*1
*2
*3
1) wind break, 2) chimney, 3) inspection opening
For the selection of the connection and to ensure a proper connection
between the stove and chimney, please read the guide „INSTALLING
THE STOVE“ or ask your local chimney sweep.
Stoves type 1 (BA 1):
Q Suitable for multiple occupancy. (Note the different country
regulations.)
Q These may only be operated with the combustion chamber door
closed.
Q The combustion chamber door is to be kept closed when the
stove is not in operation.
Q Fouling of the chimney i.e. deposits of highly inflammable materials
such as soot and tar and subsequently fire in the chimney may
occur if the chimney is miscalculated and dimensioned wrong.
Q If this occurs, disconnect the mains plug. Phone the fire brigade
and get yourself and other residents out of harm’s way.
Note
Your pellet stove has been tested as a room-air independent stove
according to EN14785. It can be operated room air dependent or
room air independent.
ROOM-AIR INDEPENDENT OPERATION:
The stove is certificated for type FC62x of the approval principles
for the inspection and evaluation of ambient air independent
fireplaces specified by the Deutsches Institut für Bautechnik (DIBT)
(German Institute for Building Technology). Thanks to an air-tight
configuration of the air supply line and flue pipes the stove may be
operated in air-tight rooms and in rooms with room-air installations
(e.g. controlled ventilation and venting systems, extractors etc.).
ROOM-AIR DEPENDENT OPERATION:
In combination with room-air installations (e.g. controlled
ventilation and venting systems (extractors etc.) it must
be ensured that the stove and the room air system are
monitored and safeguarded mutually (e.g. via a differential
pressure controller). The combustion air infeed of approx.
20 m
3
/h must be ensured.
Please observe the respective local regulations and rules in
consultation with your master chimney sweep. For changes after
the printing of this manual, we can not assume any liability. We
reserve the right to change without notice.
Convection air conduction
Only for stoves with MultiAir
The stove is delivered with a cover on the convection air outlet to
prevent direct heat to the wall.
Operation without this cover or without attached convection pipes is
not allowed. If you do though no warranty and no liability is accepted
for damage.
Q The amount of air and temperature is designed to heat one
additional room.
Q Note the regional specific fire safety regulations and clarify the
connection situation with the competent authority
Q The max. temperature of the convection air is 180° C at the air
outlet.
Q The convection air should be as short as possible.
Q Keep the number of deflections as small as possible.
Note
Please pay attention to the national and country-specific building
and fire regulations when connecting the convection air pipes.
Installation and assembly must be performed by a trained
specialist only.
example
11

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Rika Livo RAO bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Rika Livo RAO in de taal/talen: Engels als bijlage per email.

De handleiding is 10,37 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Andere handleiding(en) van Rika Livo RAO

Rika Livo RAO Gebruiksaanwijzing - Nederlands - 24 pagina's

Rika Livo RAO Gebruiksaanwijzing - Deutsch - 24 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info