689790
82
Verklein
Vergroot
Pagina terug
1/88
Pagina verder
United Kingdom
en
Installation and User Manual
High-efficiency wall-hung gas boiler
Quinta Ace
30 - 45 - 55 - 65 - 90 - 115
HMI T-control
Dear Customer,
Thank you very much for buying this appliance.
Please read through the manual carefully before using the product, and keep it in a safe place for later reference. In order to
ensure continued safe and efficient operation we recommend that the product is serviced regularly. Our service and customer
service organisation can assist with this.
We hope you enjoy years of problem-free operation with the product.
Contents
1 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1 General safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1.1 For the installer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1.2 For the end user . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.2 Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.3 Liabilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.3.1 Manufacturer's liability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.3.2 Installer's liability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.3.3 User's liability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
2 About this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.2 Additional documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.3 Symbols used in the manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
3 Description of the product . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.1 General description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
3.2 Main components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.3 Introduction to the e-Smart controls platform . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.4 Standard delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.5 Accessories and options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4 Preparation of installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.1 Installation regulations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.2 Choice of the location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.3 Requirements for water connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.3.1 Requirements for CH water connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.3.2 Requirements for condensate drain line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.3.3 Flushing the system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
4.4 Requirements for gas connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.5 Requirements on the flue gas discharge system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.5.1 Classification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.5.2 Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.5.3 Dimensions of flue gas outlet pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
4.5.4 Length of the flue and air supply pipes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4.5.5 Additional guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
4.6 Requirements for the electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
4.7 Water quality and water treatment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
4.8 Process heat application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
4.9 Increase default ΔT setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
4.10 Open-vented application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
5 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5.1 Positioning the boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
5.2 Hydraulic connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
5.2.1 Connecting the heating circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5.2.2 Connecting the expansion vessel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
5.2.3 Connecting the condensate discharge pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
5.3 Gas connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
5.4 Air supply/flue gas outlet connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
5.4.1 Connecting the flue gas outlet and air supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
5.5 Electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
5.5.1 Control unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
5.5.2 Access to the instrument box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
5.5.3 Connection options for the connection PCB - CB-03 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
5.5.4 Connection options for the expansion PCB - IF-01 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
5.5.5 Access to the expansion box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
5.5.6 The SCB-01 expansion PCB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5.5.7 Connecting the standard pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
5.5.8 Connecting the PWM pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
6 Preparation of commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
6.1 Checklist before commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
6.1.1 Filling the siphon . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Contents
7684359 - v.11 - 13122021 3
6.1.2 Filling the system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
6.1.3 Gas circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
6.1.4 Hydraulic circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
6.1.5 Electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
6.2 Control panel description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
6.2.1 Control panel components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
6.2.2 Description of the home screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
6.2.3 Description of the main menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
6.2.4 Description of the icons in the display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
7 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
7.1 Commissioning procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
7.2 Gas settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
7.2.1 Factory setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
7.2.2 Adjusting to a different gas type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
7.2.3 Checking and setting the gas/air ratio . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
7.3 Final instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
7.3.1 Saving the commissioning settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
8 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
8.1 Introduction to parameter codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
8.2 Searching the parameters, counters and signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
8.3 List of parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
8.3.1 CU-GH08 control unit parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
9 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
9.1 Maintenance regulations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50
9.2 Maintenance message . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
9.3 Opening the boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
9.4 Standard inspection and maintenance operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
9.4.1 Checking the water pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
9.4.2 Checking the ionisation current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
9.4.3 Checking the flue gas outlet/air supply connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
9.4.4 Checking the combustion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
9.4.5 Cleaning the siphon . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
9.4.6 Checking the burner and cleaning the heat exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
9.4.7 Checking the non-return valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
9.5 Finalising work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
9.6 Disposal and recycling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
10 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
10.1 Error codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
10.1.1 Display of error codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
10.1.2 Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
10.1.3 Blocking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
10.1.4 Locking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
10.2 Error history . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64
10.2.1 Reading out and clearing the error history . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64
11 User instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
11.1 Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
11.2 Accessing the user level menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
11.3 Home screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65
11.4 Activating holiday programs for all zones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
11.5 Heating circuit configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
11.6 Changing the room temperature of a zone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
11.6.1 Definition of zone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67
11.6.2 Changing the name and symbol of a zone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
11.6.3 Changing the operating mode of a zone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
11.6.4 Timer program to control the room temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
11.6.5 Changing the heating activity temperatures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
11.6.6 Changing the room temperature temporarily . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71
11.7 Changing the domestic hot water temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
11.7.1 Domestic hot water configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
11.7.2 Changing the domestic hot water operating mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
11.7.3 Timer program to control the DHW temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Contents
4 7684359 - v.11 - 13122021
11.7.4 Changing the comfort and reduced hot water temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
11.7.5 Increasing the domestic hot water temperature temporarily . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
11.8 Switching the central heating on or off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
11.9 Switching the summer mode on or off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
11.10 Changing the operating mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .74
11.11 Changing the control panel settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
11.12 Reading the installer's name and phone number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
11.13 Shut-down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75
11.14 Frost protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
11.15 Cleaning the casing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
12 Technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
12.1 Homologations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
12.1.1 Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
12.1.2 BREEAM compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
12.1.3 Unit categories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .76
12.1.4 Directives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
12.1.5 Factory test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
12.2 Electrical diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
12.3 Dimensions and connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
12.4 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .79
12.5 Boiler pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .82
13 Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
13.1 ErP information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
13.1.1 Product fiche . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
13.1.2 Package sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
13.2 EC Declaration of conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Contents
7684359 - v.11 - 13122021 5
1 Safety
1.1 General safety instructions
1.1.1 For the installer
Danger
If you smell gas:
1. Do not use naked flames, do not smoke and do not operate electrical contacts or switches (doorbell, lighting,
motor, lift etc.).
2. Shut off the gas supply.
3. Open the windows.
4. Trace possible leaks and seal them off immediately.
5. If the leak is upstream of the gas meter, notify the gas company.
Danger
If you smell flue gases:
1. Switch the boiler off.
2. Open the windows.
3. Trace possible leaks and seal them off immediately.
Caution
After maintenance or repair work, check the entire heating installation to ensure that there are no leaks.
1.1.2 For the end user
Danger
If you smell gas:
1. Do not use naked flames, do not smoke and do not operate electrical contacts or switches (doorbell, lighting,
motor, lift etc.).
2. Shut off the gas supply.
3. Open the windows.
4. Report any leaks immediately.
5. Evacuate the property.
6. Contact a qualified installer.
Danger
If you smell flue gases:
1. Switch the boiler off.
2. Open the windows.
3. Report any leaks immediately.
4. Evacuate the property.
5. Contact a qualified installer.
Warning
Do not touch the flue gas pipes. Depending on the boiler settings, the temperature of the flue gas pipes can rise to
over 60°C.
Warning
Do not touch radiators for long periods. Depending on the boiler settings, the temperature of the radiators can rise
to over 60°C.
Warning
Be careful when using the domestic hot water. Depending on the boiler settings, the temperature of domestic hot
water can rise to over 65°C.
Warning
The use of the boiler and the installation by you as the end-user must be limited to the operations described in this
manual. All other actions may only be undertaken by a qualified fitter/engineer.
1 Safety
6 7684359 - v.11 - 13122021
Warning
The condensate drain must not be modified or sealed. If a condensate neutralisation system is used, the system
must be cleaned regularly in accordance with the instructions provided by the manufacturer.
Caution
Ensure that the boiler is regularly serviced. Contact a qualified installer or arrange a maintenance contract for the
servicing of the boiler.
Caution
Only genuine spare parts may be used.
Important
Regularly check for the presence of water and pressure in the heating installation.
1.2 Recommendations
Danger
This appliance can be used by children aged eight and above and people with a physical, sensory or mental
disability, or with a lack of experience and knowledge, provided they are supervised and instructed in how to use
the appliance in a safe manner and understand the associated dangers. Children must not be allowed to play with
the appliance. Cleaning and user maintenance should not be carried out by children without adult supervision.
Warning
Installation and maintenance of the boiler must be carried out by a qualified installer in accordance with local and
national regulations.
Warning
The installation and maintenance of the boiler must be undertaken by a qualified installer in accordance with the
information in the supplied manual, doing otherwise may result in dangerous situations and/or bodily injury.
Warning
Removal and disposal of the boiler must be carried out by a qualified installer in accordance with local and national
regulations.
Warning
If the mains lead is damaged, it must be replaced by the original manufacturer, the manufacturer's dealer or
another suitably skilled person to prevent hazardous situations from arising.
Warning
Always disconnect the mains supply and close the main gas tap when working on the boiler.
Warning
Check the entire system for leaks after maintenance and servicing work.
Danger
For safety reasons, we recommend fitting smoke alarms at suitable places and a CO detector near the appliance.
Caution
Make sure the boiler can be reached at all times.
The boiler must be installed in a frost-free area.
If the power cord is permanently connected, you must always install a main bipolar switch with an opening gap of
at least 3 mm (BS EN 60335-1).
Drain the boiler and central heating system if you are not going to use your home for a long time and there is a
chance of frost.
The frost protection does not work if the boiler is out of operation.
The boiler protection only protects the boiler, not the system.
Check the water pressure in the system regularly. If the water pressure is lower than 0.8 bar, the system must be
topped up (recommended water pressure between 1.5 and 2.0 bar).
Important
Keep this document near to the boiler.
1 Safety
7684359 - v.11 - 13122021 7
Important
Only remove the casing for maintenance and repair operations. Refit all panels when maintenance work and
servicing are complete.
Important
Instruction and warning labels must never be removed or covered and must be clearly legible throughout the entire
service life of the boiler. Damaged or illegible instructions and warning stickers must be replaced immediately.
Important
Modifications to the boiler require the written approval of Remeha.
1.3 Liabilities
1.3.1 Manufacturer's liability
Our products are manufactured in compliance with the requirements of the various Directives applicable. They are therefore
delivered with the marking and any documents necessary. In the interests of the quality of our products, we strive constantly
to improve them. We therefore reserve the right to modify the specifications given in this document.
Our liability as manufacturer may not be invoked in the following cases:
Failure to abide by the instructions on installing and maintaining the appliance.
Failure to abide by the instructions on using the appliance.
Faulty or insufficient maintenance of the appliance.
1.3.2 Installer's liability
The installer is responsible for the installation and initial commissioning of the appliance. The installer must observe the
following instructions:
Read and follow the instructions given in the manuals provided with the appliance.
Install the appliance in compliance with prevailing legislation and standards.
Carry out initial commissioning and any checks necessary.
Explain the installation to the user.
If maintenance is necessary, warn the user of the obligation to check the appliance and keep it in good working order.
Give all the instruction manuals to the user.
1.3.3 User's liability
To guarantee optimum operation of the system, you must abide by the following instructions:
Read and follow the instructions given in the manuals provided with the appliance.
Call on a qualified professional to carry out installation and initial commissioning.
Get your installer to explain your installation to you.
Have the required inspections and maintenance carried out by a qualified installer.
Keep the instruction manuals in good condition close to the appliance.
2 About this manual
2.1 General
This manual describes the installation, use and maintenance of the Quinta Ace boiler. This manual is part of all the
documentation supplied with the boiler.
2.2 Additional documentation
The following documentation is available in addition to this manual:
Cascade description
Service manual
Water quality instructions
2 About this manual
8 7684359 - v.11 - 13122021
2.3 Symbols used in the manual
This manual contains special instructions, marked with specific symbols. Please pay extra attention when these symbols are
used.
Danger
Risk of dangerous situations that may result in serious personal injury.
Danger of electric shock
Risk of electric shock that may result in serious personal injury.
Warning
Risk of dangerous situations that may result in minor personal injury.
Caution
Risk of material damage.
Important
Please note: important information.
The symbols mentioned below are of lower importance, but they can help you navigate or give useful information.
See
Reference to other manuals or pages in this manual.
Helpful information or extra guidance.
Direct menu navigation, confirmations will not be shown. Use if you are familiar with the system.
3 Description of the product
3.1 General description
The Quinta Ace boiler is a high-efficiency wall-hung gas boiler with the
following properties:
High-efficiency heating.
Limited emissions of polluting substances.
Ideal choice for cascade configurations.
All Quinta Ace boiler models are supplied without a pump.
Take the boiler resistance and system resistance into account when
selecting a pump.
Caution
The pump may have a maximum input of 200 W. Use an auxiliary
relay for a pump with greater power.
If possible, install the pump directly under the boiler on the return
connection.
3 Description of the product
7684359 - v.11 - 13122021 9
3.2 Main components
Fig.1 Main components
AD-4000070-03
17
14
13
10
9
6
7
8
2
1
12
19
4
11
5
18
20
21
16
15
3
2
1Casing/air box
2Heat exchanger (CH)
3Interior light
4Type plate
5Flow sensor
6Ionisation/ignition electrode
7Mixing tube
8Non-return valve
9Combined gas valve unit
10 Return sensor
11 Air intake silencer
12 Instrument box
13 Siphon
14 Expansion box for the control PCBs
(= accessory)
15 Automatic air vent
16 Hydraulic pressure sensor
17 Fan
18 Supply line
19 Flue gas measuring point
20 Flue gas discharge
21 Air supply
Heating circuit flow
Heating circuit return
3.3 Introduction to the e-Smart controls platform
The Quinta Ace boiler is equipped with the e-Smart controls platform. This
is a modular system, and offers compatibility and connectivity between all
products that make use of the same platform.
Fig.2 Generic example
AD-3001366-02
CB
CU B
A
C
L-Bus
SCB
GTW
GTW
MK
R-Bus
S-Bus
RU
3 Description of the product
10 7684359 - v.11 - 13122021
Tab.1 Components in the example
Item Description Function
CU Control Unit: Control unit The control unit handles all basic functionality of the appli
ance.
CB Connection Board: Connection PCB The connection PCB provides easy access to all connectors
of the control unit.
SCB Smart Control Board: Expansion PCB An expansion PCB provides extra functionality, like an internal
calorifier or multiple zones.
GTW Gateway: Conversion PCB A gateway can be fitted to an appliance or system, to provide
one of the following:
Extra (wireless) connectivity
Service connections
Communication with other platforms
MK Control panel: Control panel and display The control panel is the user interface to the appliance.
RU Room Unit: Room unit (for example, a thermo
stat)
A room unit measures the temperature in a reference room.
L-Bus Local Bus: Connection between devices The local bus provides communication between devices.
S-Bus System Bus: Connection between appliances The system bus provides communication between appliances.
R-Bus Room unit Bus: Connection to a room unit The room unit bus provides communication to a room unit.
A Device A device is a PCB, control panel or a room unit.
B Appliance An appliance is a set of devices connected via the same L-
Bus
C System A system is a set of appliances connected via the same S-Bus
Tab.2 Specific devices delivered with the Quinta Ace boiler
Name visible
in display
Software ver
sion
Description Function
CU-GH08 1.12 Control unit CU-GH08 The CU-GH08 control unit handles all basic functionality of the
Quinta Ace boiler.
MK3 1.85 Control panel HMI T-control The HMI T-control is the user interface to the Quinta Ace boil
er.
SCB-01 1.3 Expansion PCB SCB-01 The SCB-01 provides a 0-10 V connection for a PWM system
pump and two potential-free contacts for status notification.
3.4 Standard delivery
The delivery includes:
The boiler, with:
Power supply cable
Expansion PCB SCB-01
PCB IF-01
Suspension bracket with fasteners for wall mounting
Siphon with condensate drain hose
Documentation set, with:
Sticker: Adjusted for ...
This manual only deals with the standard scope of supply. For the
installation or mounting of any accessories supplied with the boiler, please
refer to the mounting instructions delivered with the accessories in
question.
3.5 Accessories and options
Various accessories can be obtained for the boiler.
Important
Contact us for more information.
3 Description of the product
7684359 - v.11 - 13122021 11
4 Preparation of installation
4.1 Installation regulations
Important
The Quinta Ace must be installed by a qualified installer in
accordance with local and national regulations.
Warning
The installer must be registered with Gas Safe and have the
correct ACS qualifications.
Important
Practical guidelines - see the latest version.
4.2 Choice of the location
When choosing the best installation location, consider:
The regulations.
The required installation space.
The required space around the boiler for good access and to facilitate
maintenance.
The required space under the boiler for the installation and removal of
the siphon.
The permitted position of the flue gas outlet and/or air supply opening.
The evenness of the surface.
A≥ 1000 mm
B500 mm
C500 mm
D≥ 400 mm
E750 mm
F350 mm (siphon)
G≥ 250 mm
If the boiler is installed in a closed cupboard, the minimum distance
between the boiler and the walls of the cupboard must be taken into
account.
1≥ 1000 mm (front)
2≥ 15 mm (left-hand side)
3≥ 15 mm (right-hand side)
Also allow for openings to prevent the following hazards:
Accumulation of gas
Heating of the casing
Minimum cross section of the openings: S1 + S2 = 150 cm2
Fig.3 Installation area
AD-3001371-01
C
A
D
F
E
B
G
S2
S1
3
1
2
4 Preparation of installation
12 7684359 - v.11 - 13122021
Danger
It is forbidden to store, even temporarily, combustible products
and substances in the boiler or near the boiler.
Warning
Fix the appliance to a solid wall capable of bearing the weight of
the boiler when full of water and fully equipped.
Do not place the appliance above a heat source or a cooking
appliance.
Do not locate the boiler in direct or indirect sunlight.
Caution
The boiler must be installed in a frost-free area.
An earthed electrical connection must be available close to the
boiler.
A connection to the drain must be present for the condensate
drain close to the boiler.
4.3 Requirements for water connections
Before installation, check that the connections meet the set
requirements.
Carry out any welding work required at a safe distance from the boiler.
If using synthetic pipes, follow the manufacturer's instructions.
4.3.1 Requirements for CH water connections
When fitting service shut-off valves, position the filling and drain valve,
the expansion vessel and the safety valve between the shut-off valve
and the boiler.
Carry out any welding work required at a safe distance from the boiler or
before the boiler is fitted.
For filling and tapping the boiler, install a filling and drain valve in the
system, preferably in the return.
Install an expansion vessel in the return pipe.
When installing open-vented systems, the cold feed and expansion tank
heights must comply with the requirements laid down in the Health and
Safety Executive publication PM5. The Quinta Ace boilers require a
minimum static height of 3 m (Quinta Ace 30/45/55/65/90 or 5 m ( 115).
4.3.2 Requirements for condensate drain line
The siphon must always be filled with water. This prevents flue gases
from entering the room.
Never seal the condensate drain.
The drain pipe must slope down at least 30 mm per metre, the maximum
horizontal length is 5 metres.
Condensed water must not be discharged into a gutter.
4.3.3 Flushing the system
The installation must be cleaned and flushed in accordance with BS 7593
(2019) and BSRIA BG 33/2014.
Before a new boiler can be connected to a system, the entire system must
be thoroughly cleaned by flushing it. The flushing will remove residue from
the installation process (weld slag, fixing products etc.) and accumulations
of dirt (silt, mud etc.)
Important
Flush the heating system with a volume of water equivalent to at
least three times the volume of the system.
Flush the domestic hot water pipes with at least 20 times the
volume of the pipes.
4 Preparation of installation
7684359 - v.11 - 13122021 13
Important
Due to the presence of an aluminium heat exchanger, suitable
chemicals and the correct use of these chemicals should be
discussed with specialist water treatment companies.
4.4 Requirements for gas connection
Before starting work on the gas pipes, turn off the main gas tap.
Before installing, check that the gas meter has sufficient capacity. Take
into account the consumption of all appliances.
Notify the local energy company if the gas meter has insufficient
capacity.
Remove dirt and dust from the gas pipe.
Always perform welding work at a sufficient distance from the boiler.
We recommend installing a gas filter to prevent clogging of the gas
valve unit.
4.5 Requirements on the flue gas discharge system
4.5.1 Classification
Important
The installer is responsible ensuring that the right type of flue
gas outlet system is used and that the diameter and length are
correct.
Always use connection materials, roof terminal and/or outside
wall terminal supplied by the same manufacturer. Consult the
manufacturer for compatibility details.
The use of flue gas outlet systems from other manufacturers is
allowed in addition to the recommended manufacturers listed in
this manual. Use is only allowed when all our requirements are
met and the description of flue gas connection C63 is respected.
Tab.3 Type of flue gas connection: B23P
Principle Description Recommended manufactur
ers(1)
AD-3000924-01
Room-ventilated version
Without down-draught diverter.
Flue gas discharge via the roof.
Air from the installation area.
The air supply opening of the boiler must stay open.
The installation area must be vented to ensure sufficient air
supply. The vents must not be obstructed or shut off.
The IP rating of the boiler is lowered to IP20.
Connection material and roof
terminal:
Centrotherm
Cox Geelen
Muelink & Grol
Natalini
Poujoulat
Ubbink
(1) The material must also satisfy the material property requirements from the relevant chapter.
4 Preparation of installation
14 7684359 - v.11 - 13122021
Tab.4 Type of flue gas connection: B33
Principle Description Recommended manufactur
ers(1)
AD-3000925-01
Room-ventilated version
Without down-draught diverter.
Joint flue gas discharge via the roof, with guaranteed natural
draft (at all times underpressure in the joint discharge duct).
Flue gas discharge rinsed with air, air from the installation
area (special construction).
The IP rating of the boiler is lowered to IP20.
Connection material:
Centrotherm
Cox Geelen
Muelink & Grol
Natalini
Poujoulat
Ubbink
(1) The material must also satisfy the material property requirements from the relevant chapter.
Tab.5 Type of flue gas connection: C13
Principle Description Recommended manufactur
ers(1)
AD-3000926-01
Room-sealed version
Discharge in the outside wall.
Air supply opening is in the same pressure zone as the dis
charge (e.g. a combined outside wall terminal).
Parallel wall terminal not permitted.
Outside wall terminal and con
nection material:
Remeha, combined with con
nection material from Muelink
& Grol
Cox Geelen
Muelink & Grol
(1) The material must also satisfy the material property requirements from the relevant chapter.
Tab.6 Type of flue gas connection: C33
Principle Description Recommended manufactur
ers(1)
AD-3000927-01
Room-sealed version
Flue gas discharge via the roof.
Air supply opening is in the same pressure zone as the dis
charge (e.g. a concentric roof terminal).
Roof terminal and connection
material
Centrotherm
Cox Geelen
Muelink & Grol
Natalini
Poujoulat
Ubbink
(1) The material must also satisfy the material property requirements from the relevant chapter.
4 Preparation of installation
7684359 - v.11 - 13122021 15
Tab.7 Type of flue gas connection: C53
Principle Description Recommended manufactur
ers(1)
AD-3000929-02
Connection in different pressure zones
Closed unit.
Separate air supply duct.
Separate flue gas discharge duct.
Discharging into various pressure areas.
The air supply and the flue gas outlet must not be placed on
opposite walls.
Connection material and roof
terminal:
Centrotherm
Cox Geelen
Muelink & Grol
Natalini
Poujoulat
Ubbink
(1) The material must also satisfy the material property requirements from the relevant chapter.
Tab.8 Type of flue gas connection: C63
Principle Description Recommended manufactur
ers(1)
This type of unit is supplied by us without an air supply system
and flue gas system.
When selecting the material, please note the following:
Condensed water must flow back to the boiler.
The material must be resistant to the flue gas temperature of
this boiler.
Maximum permissible recirculation of 10%.
The air supply and the flue gas outlet must not be placed on
opposite walls.
Minimum permitted pressure difference between the air supply
and the flue gas outlet is -200 Pa (including -100 Pa wind
pressure).
Use is only allowed when all
our requirements are met and
the description of this type of
flue gas connection is respec
ted.
(1) The material must also satisfy the material property requirements from the relevant chapter.
Tab.9 Type of flue gas connection: C93
Principle(1) Description Recommended manufactur
ers(2)
AD-3000931-01
Room-sealed version
Air supply and flue gas discharge duct in shaft or ducted:
Concentric.
Air supply from existing duct.
Flue gas discharge via the roof.
Inlet opening for the air supply is in the same pressure zone
as the discharge.
Connection material and roof
terminal:
Centrotherm
Cox Geelen
Muelink & Grol
Natalini
Poujoulat
Ubbink
(1) See table for shaft or duct requirements.
(2) The material must also satisfy the material property requirements from the relevant chapter.
Tab.10 Minimum dimensions of shaft or duct C93
Version (D) Without air supply With air supply
Rigid 80 mm Ø 130 mm □ 130 x 130 mm Ø 140 mm □ 130 x 130 mm
Rigid 100 mm Ø 160 mm □ 160 x 160 mm Ø 170 mm □ 160 x 160 mm
Concentric 80/125 mm Ø 145 mm □ 145 x 145 mm Ø 145 mm □ 145 x 145 mm
Concentric 100/150 mm Ø 170 mm □ 170 x 170 mm Ø 170 mm □ 170 x 170 mm
4 Preparation of installation
16 7684359 - v.11 - 13122021
Important
The shaft must comply with the air density requirements of the
local regulations.
Important
Always clean shafts thoroughly when using lining pipes and/or
an air supply connection.
It must be possible to inspect the lining duct.
4.5.2 Material
Use the string on the flue gas outlet material to check whether it is suitable
for use on this appliance.
1 EN 14471 or EN 1856–1: The material is CE approved according
to this standard. For plastic this is EN 14471, For aluminium and
stainless steel this is EN 1856-1.
2 T120: The material has temperature class T120. A higher number
is also allowed, but not lower.
3 P1: The material falls into pressure class P1. H1 is also allowed.
4 W: The material is suitable for draining condensation water
(W=’wet’). D is not allowed (D=’dry’).
5 E: The material falls into fire resistance class E. Class A to D are
also allowed, F is not allowed. Only applicable to plastic.
Warning
The coupling and connection methods may vary depending on
the manufacturer. It is not permitted to combine pipes, coupling
and connection methods from different manufacturers. This also
applies to roof terminal and common shared flue ducts.
The materials used must comply with the prevailing regulations
and standards.
Please contact us to discuss using flexible flue gas outlet
material.
Tab.11 Overview of material properties
Version Flue gas outlet Air supply
Material Material properties Material Material properties
Single-wall, rigid Plastic(1)
Stainless steel(2)
Thick-walled,
aluminium(2)
With CE marking
Temperature class T120 or
higher
Condensate class W (wet)
Pressure class P1 or H1
Fire resistance class E or bet
ter(3)
Plastic
Stainless steel
Aluminium
With CE marking
Pressure class P1 or H1
Fire resistance class E or bet
ter(3)
(1) according to EN 14471
(2) according to EN 1856
(3) according to EN 13501-1
Fig.4 Minimum dimensions of shaft or
duct C93
AD-3000330-03
D
Ø
D
Fig.5 Sample string
AD-3001120-01
EN 14471 - T120 P1 W 1 O50 LI E U0
EN 1856-1 - T120 P1 W VxL40045 G(xx)
13
245
4 Preparation of installation
7684359 - v.11 - 13122021 17
4.5.3 Dimensions of flue gas outlet pipe
Warning
The pipes connected to the flue gas adapter must satisfy the
following dimension requirements.
d1External dimensions of flue gas outlet pipe
D1External dimensions of air supply pipe
L1Length difference between flue gas outlet pipe and air supply pipe
Tab.12 Dimensions of pipe
d1 (min-max) D1 (min-max) L1(1) (min-max)
80/125 mm 79.3 - 80.3 mm 124 - 125.5 mm 0 - 15 mm
100/150 mm 99.3 - 100.3 mm 149 - 151 mm 0 - 15 mm
(1) Shorten the inner pipe if the length difference is too great.
4.5.4 Length of the flue and air supply pipes
The maximum length of the flue and air supply vary per appliance type.
Consult the relevant chapter for the correct lengths.
If a boiler is not compatible with a specific flue system or diameter, it is
indicated with "-" in the table.
When using bends, the maximum flue length (L) must be shortened
according to the reduction table.
Use approved flue reducers for adaptation to another diameter.
The boiler also supports other flue lengths and diameters than those
specified in the tables. Contact us for more information.
Room-ventilated model (B23P, B33)
L Length of the flue gas outlet channel to roof terminal
Connecting the flue gas outlet
Connecting the air supply
With a room-ventilated version, the air supply opening stays open; only the
flue gas outlet opening is connected. This will ensure that the boiler
obtains the necessary combustion air directly from the installation area.
Caution
The air supply opening must stay open.
The installation area must be equipped with the necessary air
supply openings. These openings must not be obstructed or
shut off.
Tab.13 Maximum length (L)
Diameter(1) 80 mm 90 mm 100 mm 110 mm 130 mm
Quinta Ace 30 33 m 40 m 40 m(1) 40 m(1) 40 m(1)
Quinta Ace 45 39 m 40 m(1) 40 m(1) 40 m(1) 40 m(1)
Quinta Ace 55 16 m 26 m 39 m 40 m(1) 40 m(1)
Quinta Ace 65 11 m 17 m 26 m 40 m 40 m(1)
Quinta Ace 90 10 m 16 m 24 m 40 m 40 m(1)
Quinta Ace 115 8 m 13 m 19 m 38 m 40 m(1)
(1) Retaining the maximum chimney length it is possible to use an extra 5 x 90º or 10 x 45º elbows.
Fig.6 Dimensions of concentric
connection
AD-3000962-01
ød1
L1
øD1
Fig.7 Room-ventilated version
4 Preparation of installation
18 7684359 - v.11 - 13122021
Room-sealed model (C13, C33, C63, C93)
L Total length of the flue gas outlet and air supply duct
Connecting the flue gas outlet
Connecting the air supply
With a room-sealed version, both the flue gas outlet and the air supply
openings are connected (concentrically).
Tab.14 Maximum chimney length (L)
Diameter(1) 80/125 mm 100/150 mm
Quinta Ace 30 20 m 20 m(1)
Quinta Ace 45 20 m 20 m(1)
Quinta Ace 55 8 m 20 m(1)
Quinta Ace 65 4 m 18 m
Quinta Ace 90 4 m 17 m
Quinta Ace 115 - 13 m
(1) Retaining the maximum chimney length it is possible to use an extra 5 x 90º
or 10 x 45º elbows.
Connection in different pressure areas (C53)
LTotal length of the flue gas outlet and air supply duct
Connecting the flue gas outlet
Connecting the air supply
An 80/80 or 100/100 mm flue gas adapter (accessory) must be fitted for
this connection.
Combustion air supply and flue gas discharge are possible in different
pressure areas and semi-CLV systems, with the exception of the coastal
area. The maximum permitted height difference between the combustion
air supply and the flue gas outlet is 36 m.
Tab.15 Maximum length (L)
Diameter(1) 80 mm 90 mm 100 mm 110 mm 130 mm
Quinta Ace 30 17 m 29 m 40 m 40 m(1) 40 m(1)
Quinta Ace 45 29 m 40 m 40 m(1) 40 m(1) 40 m(1)
Quinta Ace 55 9 m 17 m 27 m 40 m 40 m(1)
Quinta Ace 65 5 m 10 m 16 m 34 m 40 m(1)
Quinta Ace 90 - - 17 m 37 m 40 m(1)
Quinta Ace 115 - - 14 m 31 m 40 m(1)
(1) Retaining the maximum chimney length it is possible to use an extra 5 x 90º or 10 x 45º elbows.
Reduction table
Tab.16 Pipe reduction for each bend - radius ½D (parallel)
Diameter 80 mm 100 mm
45° bend 1.2 m 1.4 m
90° bend 4.0 m 4.9 m
Fig.8 Room-sealed version (concentric)
AD-0000029-02
L =
Fig.9 Different pressure areas
AD-0000030-02
= L +
Fig.10 Bend radius ½D
AD-3001608-01
R=½D
D
4 Preparation of installation
7684359 - v.11 - 13122021 19
Tab.17 Pipe reduction for each bend - radius ½D (concentric)
Diameter 80/125 mm 100/150 mm
45° bend 1.0 m 1.0 m
90° bend 2.0 m 2.0 m
4.5.5 Additional guidelines
Installation
For installing the flue gas outlet and air supply materials, refer to the
instructions of the manufacturer of the relevant material. After
installation, check at least all flue gas outlet and air supply parts for
tightness.
Warning
If the flue gas outlet and air supply materials are not installed in
accordance with the instructions (e.g. not leak-proof, not correctly
bracketed), this can result in dangerous situations and/or physical
injury.
Make sure that the flue gas outlet pipe towards the boiler has a sufficient
gradient (at least 50 mm per metre) and that there is a sufficient
condensate collector and discharge (at least 1 m before the outlet of the
boiler). The bends used must be larger than 90° to guarantee the
gradient and a good seal on the lip rings.
Condensation
Direct connection of the flue gas outlet to structural ducts is not
permitted because of condensation.
If condensate from a plastic or stainless steel pipe section can flow back
to an aluminium part in the flue gas outlet, this condensate must be
discharged via a collector before it reaches the aluminium.
Newly installed aluminium flue gas pipes with longer lengths can
produce relatively larger quantities of corrosion products. Check and
clean the siphon more often in this case.
Important
Contact us for more information.
4.6 Requirements for the electrical connections
Establish the electrical connections in accordance with all local and
national current regulations and standards.
Electrical connections must always be made with the power supply
disconnected and only by qualified installers.
The boiler is completely pre-wired. Never change the internal
connections of the control panel.
Always connect the boiler to a well-earthed installation.
The wiring must comply with the instructions in the electrical diagrams.
Follow the recommendations in this manual.
Separate the sensor cables from the 230 V cables
Make sure the following requirements are met when connecting the cables
to the CB and SCB connectors:
Tab.18 PCB connectors
Wire cross section Stripping length Tightening torque
solid wire: 0.14 – 4.0 mm² (AWG 26 – 12)
stranded wire: 0.14 – 2.5 mm² (AWG 26 – 14)
stranded wire with ferrule: 0.25 – 2.5 mm² (AWG 24 – 14)
8 mm 0.5 N⋅m
4 Preparation of installation
20 7684359 - v.11 - 13122021
4.7 Water quality and water treatment
The quality of the heating water must comply with the limit values in our
Water quality instructions. The guidelines in these instructions must be
followed at all times. In many cases, the boiler and central heating system
can be filled with normal tap water and water treatment will not be
necessary.
4.8 Process heat application
In process heat applications (for example pasteurisation and drying and
washing processes), the boiler is being used for industrial purposes and
not for central heating. With process heat, the nominal flow (at ΔT 20°C) in
the primary CH circuit must be guaranteed. The flow in the secondary
circuit may vary.
To ensure that this is the case, a flow rate sensor can be fitted, which
locks out the boiler if the flow falls below a specified level (due to a
defective pump or valve, for example).
Important
The service life of the boiler may be reduced if it is used for
process heat applications.
4.9 Increase default ΔT setting
In some cases, the default ΔT setting of the boiler will need to be
increased, for example in systems with:
underfloor heating
air heating
district heating
a heat pump.
Important
Do not increase the default ΔT setting when the boiler is used in
an open-vented system.
Important
To limit the amount of short cycling, ensure minimum water
circulation by using a bypass or low loss header.
4.10 Open-vented application
In open vented applications the boiler is often operating with lower water
pressure levels. In these cases the default minimum water pressure
setting must be decreased to a value of 0,0 bar.
4 Preparation of installation
7684359 - v.11 - 13122021 21
5 Installation
5.1 Positioning the boiler
The fitting bracket on the back of the casing can be used to mount the
boiler directly on the suspension bracket.
The boiler is supplied with a mounting template.
1. Attach the mounting template of the boiler to the wall using adhesive
tape.
Warning
Use a level to check whether the mounting template is hanging
perfectly horizontally.
Protect the boiler against building dust and cover the connection
points for the flue gas outlet and air supply. Only remove this
cover to assemble the relevant connections.
2. Drill 2 holes of Ø 10 mm.
Important
The extra fixing holes in the suspension bracket are intended for
use in the event that one of the two holes is not suitable for the
correct fastening of the plug.
3. Fit the Ø 10 mm plugs.
4. Remove the mounting template.
5. Attach the suspension bracket to the wall with the Ø 10 mm bolts
supplied.
6. Mount the boiler on the suspension bracket.
5.2 Hydraulic connections
5.2.1 Connecting the heating circuit
1. Remove the dust cap from the CH flow connection at the bottom
of the boiler.
2. Fit the outlet pipe for CH water to the CH flow connection.
3. Remove the dust cap from the CH return connection at the
bottom of the boiler.
4. Fit the inlet pipe for CH water to the CH return connection.
5. Install the pump in the CH return pipe (if applicable).
See also
Connecting the standard pump, page 31
Connecting the PWM pump, page 31
Fig.11 Mounting the boiler
AD-0000018-02
2
1
5
4
3
Fig.12 Connecting the CH flow and CH
return
AD-4100110-01
1
3
2
4
4
5
5 Installation
22 7684359 - v.11 - 13122021
5.2.2 Connecting the expansion vessel
1. Ensure that there is an expansion vessel with the correct volume and
pre-charge.
2. Fit the expansion vessel on the central heating return pipe .
5.2.3 Connecting the condensate discharge pipe
1. Fit a plastic drain pipe of Ø 32 mm or larger, terminating in the drain.
2. Insert the flexible condensate drain hose into the pipe.
3. Fit a stench-trap or siphon in the drain pipe.
4. Fit the siphon.
5.3 Gas connection
1. Remove the dust cap from the gas supply pipe at the bottom of
the boiler.
2. Fit the gas supply pipe.
3. Fit a gas tap in this pipe, directly underneath the boiler (within 1
metre).
4. Fit the gas pipe to the gas tap.
Important
The gas tap must always be accessible
Fig.13 Connecting the condensate
discharge pipe
AD-0000024-02
4
1
2
3
Fig.14 Connecting the gas pipe
AD-0000025-02
2
3
4
1
5 Installation
7684359 - v.11 - 13122021 23
5.4 Air supply/flue gas outlet connections
5.4.1 Connecting the flue gas outlet and air supply
SInsertion depth 25 mm
1. Connect the flue gas outlet pipe and the air supply pipe to the boiler.
2. Fit the subsequent flue gas outlet pipes and air supply pipes in
accordance with the manufacturer's instructions.
Caution
The pipes must not be resting on the boiler.
Fit the horizontal parts sloping down towards the boiler, with a
gradient of 50 mm per metre.
5.5 Electrical connections
5.5.1 Control unit
The table gives important connection values for the control unit.
Tab.19 Connection values for control unit
Supply voltage 230 VAC/50 Hz
Main fuse value F1 (230 VAC) 2.5 AT
Fan 230 VAC
Danger of electric shock
The following components of the boiler are connected to a 230
VAC power supply:
Electrical connection to circulating pump.
Electrical connection to gas combination block.
Electrical connection to fan.
Control unit.
Ignition transformer.
Power supply cable connection.
The boiler has a three-wire mains lead (lead length 1.5 m) and is suitable
for a 230 VAC/50 Hz supply with a phase/neutral/earth system. The power
supply cable is connected to the X1 connector. A spare fuse can be found
in the casing of the control unit. The boiler is not phase sensitive. The
control unit is fully integrated with the fan, venturi and gas valve unit. The
boiler is completely pre-wired.
Caution
Always order a replacement mains lead from Remeha. The
power supply cable should only be replaced by Remeha , or by
an installer certified by Remeha.
The boiler switch must be easily accessible at all times.
Use an isolating transformer for connection values other than
those stated above.
The boiler has several control, protection and regulation connection
options. The standard PCB can be extended with optional PCBs.
Fig.15 Connecting the flue gas outlet and
air supply
AD-0000034-01
80/125 mm
100/150 mm
S
Fig.16 CU-GH08
AD-3001374-01
5 Installation
24 7684359 - v.11 - 13122021
5.5.2 Access to the instrument box
The following is installed in the instrument box:
the standard PCB CB-03 with connector X3.
the IF-01 PCB with connectors X4 and X5
1. Unscrew the two screws located under the front housing by a quarter
turn and remove the front housing.
2. Press the clips on the sides of the instrument box inwards slightly.
3. Tilt the instrument box forwards.
4. Press the clip on the side of the instrument box flap inwards slightly.
5. Open the instrument box flap.
The connector X3 on the CB-03 PCB is now accessible.
6. Release the 4 clips of the instrument box cover gently with a
screwdriver.
7. Lift the instrument box cover
The connectors X4 and X5 on the IF-01 PCB are now accessible.
8. Guide the relevant connection cable(s) through the round grommet(s)
on the boiler's bottom plate.
9. Guide the relevant connection cable(s) through the instrument box via
the cable ducts provided.
10. Undo the strain relief clip(s) and feed the cable(s) underneath.
11. Connect the cables to the appropriate terminals on the connector.
12. Press the strain relief clip(s) firmly into place.
13. Close the instrument box.
5.5.3 Connection options for the connection PCB - CB-03
The boiler is fitted with a connection PCB, to which various thermostats
and regulators can be connected.
R-Bus Room unit (thermostat) connector
BL Blocking input
RL Release input
Tout Outdoor sensor connector
Tdhw DHW sensor connector
Connecting a modulating room thermostat
The boiler is fitted with a R-Bus connection as standard instead of an OT-
connector. The R-Bus connector supports the following types:
Fig.17 Access to the instrument box
AD-3001411-01
3
2
2
1
90 º
Fig.18
AD-3001412-01
5
4
Fig.19
AD-3001413-01
7
6
Fig.20
AD-3001415-01
8
11
10
9
12
Fig.21 Connectors on the connection PCB
AD-3001367-01
R-Bus Tout
BL RL
Tdhw
X03
5 Installation
7684359 - v.11 - 13122021 25
R-Bus thermostat (for example, the eTwist)
OpenTherm thermostat (for example, the iSense)
On/off thermostat
The software recognizes which type of thermostat is connected.
Tm Modulating thermostat
1. In the case of a room thermostat: install the thermostat in a reference
room.
2. Connect the two-wire cable of the modulating thermostat (Tm) to the
terminals R-Bus of the connector. It does not matter which wire is
connected to which cable clamp.
Connecting the on/off thermostat
The boiler is suitable for connection to a 2-wire on/off ambient thermostat.
Tk On/off thermostat
1. Fit the thermostat in a reference room.
2. Connect the two-wire cable of the thermostat (Tk) to the R-Bus
terminals of the connector. It does not matter which wire is connected
to which cable clamp.
Frost protection combined with on/off thermostat
When an on/off thermostat is used, the pipes and radiators in a frost-
sensitive room can be protected by a frost protection thermostat. The
radiator valve in the frost-sensitive room must be open.
Tk On/off thermostat
Tv Frost protection thermostat
1. Place a frost protection thermostat (Tv) in a frost-sensitive room (e.g.
a garage).
2. Connect the frost protection thermostat (Tv) parallel with an on/off
thermostat (Tk) to the terminals R-Bus of the connector.
Warning
If an OpenTherm thermostat (for example, the eTwist) is used, a
frost protection thermostat cannot be connected in parallel to the
R-Bus terminals. In such cases, install frost protection in the
central heating system in combination with an outdoor
temperature sensor.
Blocking input
Caution
Only suitable for potential-free contacts (dry contact).
Important
First remove the bridge if this input is used.
Fig.22 Connecting the modulating
thermostat
AD-3000968-02
Tm
R-Bus
Fig.23 Connecting the on/off thermostat
AD-3000969-02
Tk
R-Bus
Fig.24 Connecting the frost protection
thermostat
AD-3000970-02
Tk Tv
R-Bus
5 Installation
26 7684359 - v.11 - 13122021
The boiler has a blocking input. A potential-free contact can be connected
to the BL terminals of the connector. If the contact is opened, the boiler will
be blocked.
Change the function of the input using parameter AP001. This parameter
has the following 3 configuration options:
Complete blocking: no frost protection with the outdoor sensor and no
boiler frost protection (pump does not start and burner does not start)
Partial blocking: boiler frost protection (pump starts when the
temperature of the heat exchanger is < 6°C and the burner starts when
the temperature of the heat exchanger is < 3°C)
Lock out: no frost protection with outdoor sensor and partial boiler frost
protection (pump starts when the temperature of the heat exchanger is <
6°C, the burner does not start when the temperature of the heat
exchanger is < 3°C).
Release input
Caution
Only suitable for potential-free contacts (dry contact).
The boiler has a release input. A potential-free contact can be connected
to the RL terminals of the connector.
If the contact is closed during a heat demand, the boiler will be blocked
immediately.
If the contact is closed when there is no heat demand, the contact does
nothing until the main PCB receives a ‘start burner’- command. After that
command, a waiting time starts. If the contact is closed during this
waiting time, the burner does not start and the boiler will be blocked. Set
the waiting time with parameter AP008. A waiting time of 0 will disable
the contact.
Connecting an outdoor sensor
An outdoor sensor can be connected to the Tout connector. In the case of
an on/off thermostat, the boiler will control the temperature with the set
point from the internal heating curve. An OpenTherm controller can also
use this outdoor sensor. In that case, the desired internal heating curve
must be set on the controller.
Use below mentioned sensors, or sensors with identical characteristics.
Set parameter AP056 to the installed outdoor sensor type.
AF60 = NTC 470 Ω/25°C
QAC34 = NTC 1000 Ω/25°C
1. Connect the plug from the outdoor sensor to the Tout connector.
Frost protection combined with outdoor sensor
The central heating system can also be protected against frost in
combination with an outdoor sensor. The radiator valve in the frost-
sensitive room must be open.
Fig.25 Blocking input
AD-3000972-02
BL
Fig.26 Release input
AD-3001303-02
RL
Fig.27 Connecting an outdoor sensor
AD-3000973-02
Tout
5 Installation
7684359 - v.11 - 13122021 27
1. Connect the plug from the outdoor sensor to the Tout connector.
The frost protection works as follows with an outdoor sensor:
If the outdoor temperature is lower than the threshold for frost
protection: heat demand from the boiler and the pump starts working.
If the outdoor temperature is higher than the threshold for frost
protection: no heat demand from the boiler.
Important
The outdoor temperature threshold for frost protection can be
changed with parameter AP080.
Connecting the calorifier sensor/thermostat
A calorifier sensor or thermostat can be connected to the Tdhw terminals
of the connector. Only NTC 10 kΩ/25°C sensors can be used.
1. Connect the two-wire cable to the Tdhw terminals of the connector.
5.5.4 Connection options for the expansion PCB - IF-01
The expansion board IF-01 is pre-installed in the instrument box as
standard.
Caution
Do not connect a frost thermostat or room thermostat to the boiler
if using the 0–10 V control PCB.
Connecting the status relay (Nc)
If the boiler locks out, a relay is de-energised and the alarm can be
transmitted via a potential-free contact (maximum 230 V, 1 A) on terminals
Nc and C of the connector.
Connection (OTm)
The interface uses OpenTherm to communicate with the boiler control
unit. To make this possible, the OTm connection must be connected to the
OpenTherm input of the boiler control unit.OTm
Analogue input (0-10 V)
A choice can be made with this control between control based on
temperature or heat output. The two controls are described briefly below.
1. Connect the input signal to terminals 0–10 of the connector.
Fig.28 Connecting an outdoor sensor
AD-3000973-02
Tout
Fig.29 Connecting the calorifier sensor/
thermostat
AD-3000971-02
Tdhw
Fig.30 IF-01 PCB
AD-0000054-01
Status 0-10 0-10
Nc NoC
Nc No OTm 0 + 0 +C
OTm 0 + 0 +
X5
X4
X1
IF-01
%
1
2
5 Installation
28 7684359 - v.11 - 13122021
Tab.20 Temperature-based control (°C)
Jumper 2 Input signal (V) Temperature °C Description
0–1.5 0–15 Boiler off
1.5–1.8 15–18 Hysteresis
1.8–10 18–100 Desired temperature
The 0–10 V signal controls the boiler supply temperature. This control
modulates on the basis of flow temperature. The output varies between
the minimum and maximum value on the basis of the flow temperature set
point calculated by the controller.
A jumper (2) on the interface is used to select either temperature-based
control ( ) or output-based control (%).
Tab.21 Control based on heat output
Jumper 2 Input signal (V) Heat output (%) Description
%
0–2.0(1) 0–20 Boiler off
2.0–2.2 (1) 20–22 Hysteresis
2.0–10 (1) 20–100 Desired heat output
(1) Dependent on the minimum modulation depth (set speeds, standard 20%)
The 0–10 V signal controls the boiler output. This control modulates on the
basis of the heat output. The minimum output is linked to the boiler's
modulation depth. The output varies between the minimum and maximum
value on the basis of the value defined by the controller.
Analogue output (0–10 V)
This feedback can be based on temperature or heat output. The two
controls are described briefly below.
A jumper (1) on the interface is used to select either temperature ( ) or
output (%).
Tab.22 Temperature message
Jumper 1 Output signal (V) Temperature °C Description
0.5 Alarm
1–10 10–100 Supplied tempera
ture
Tab.23 Output message
Jumper 2 Output signal (V) Heat output (%) Description
%
0 0–15 Boiler off
0.5 15–20 Alarm
2.0–10(1) 20–100 Supplied heat output
(1) Dependent on the minimum modulation depth (set speeds, standard 20%)
Fig.31 Switch jumper (2)
AD-0000055-01
1
2
%
2 2
Fig.32 Switch jumper (1)
AD-0000056-01
1
2
%
1 1
5 Installation
7684359 - v.11 - 13122021 29
5.5.5 Access to the expansion box
If there is no space in the boiler’s instrument box to install an (optional)
expansion PCB, install the PCB in the electronics expansion box This is
available as an accessory.
1. Unclip the housing cover.
2. Remove the cover.
3. Install the expansion PCB in accordance with the instructions
supplied.
The following is installed in the expansion box:
SCB-01 PCB.
5.5.6 The SCB-01 expansion PCB
The SCB-01 has the following features:
Two potential free contacts for status notifications
0–10 V output connection for a PWM system pump
Expansion PCBs are automatically recognised by the control unit of the
boiler. If expansion PCBs are removed, the boiler will show an error code.
To resolve this error, an auto-detect must be carried out after removal.
Connecting status notifications
The two potential-free contacts, Status, can be configured as required.
Depending on the setting, a particular status can be transmitted by the
boiler.
Connect a relais as follows:
Nc Normally closed contact. Contact will open when status occurs.
CMain contact.
No Normally opened contact. Contact will close when status occurs.
Select the desired status notification (setting) using parameter EP018 and
EP019.
Connecting 0–10 V output
The 0-10 contact can be used to connect a PWM system pump. The
speed of the pump is modulated based on the signal received from the
boiler. Depending on the make and type of pump, the pump can be
controlled by a 0–10 V or a PWM signal.
Connect the system pump controller to connector 0-10.
Select the type of signal that will be sent from the boiler using the
parameter EP029.
Select the type of signal that controls the pump using the parameter
EP028.
Fig.33 Access to the expansion box
AD-4000062-01
x3
1
2
Fig.34 SCB-01 PCB
AD-3001514-01
NoCNc
Status
NoCNc
Status
+0
0-10
Fig.35 Status notifications
AD-3001312-01
C No
Nc
Status A
C No
Nc
Status B
Fig.36 0–10 V output connector
AD-3001305-01
+
-
0-10
5 Installation
30 7684359 - v.11 - 13122021
Caution
If possible, use the pump modulation signal. This provides the
most accurate pump control.
If the automatic burner unit does not support pump modulation,
the pump will behave as an on/off pump.
5.5.7 Connecting the standard pump
The pump must be connected to the standard control PCB. To do this,
proceed as follows:
1. Connect the X81 power cable to the pump.
2. Remove the grommet from the opening in the middle of the base of
the boiler.
3. Pass the pump X81 cable through the base of the boiler and seal the
opening by tightening the bayonet fitting to the cable.
4. Connect the X81 pump cable to the X81 cable that runs along the
cable duct to the left of the instrument box.
5.5.8 Connecting the PWM pump
The energy-efficient modulating pump must be connected to the standard
control PCB. To do this, proceed as follows:
1. Connect the power supply cable and the cable for the PWM signal to
the pump.
2. Remove the grommet from the opening in the middle of the base of
the boiler.
3. Pass the pump power supply cable through the base of the boiler and
seal the opening by tightening the bayonet fitting to the cable.
4. Pass the PWM cable from the pump through one of the grommets on
the right in the base of the boiler.
5. Connect the X81 pump power supply cable to the X81 cable that runs
along the cable duct to the left of the instrument box.
6. Connect the X116A pump PWM cable to the X112 cable that runs
along the cable duct to the right of the instrument box.
Important
The pump's various settings can be adjusted using the
parameters.
Fig.37 Connecting the power supply cable
AD-4000093-01
X81
2
3
1
X81
X81
4
Fig.38 Connecting the power supply cable
AD-4000094-03
2
3
X81
X116a
4
1
5
6
X81
X81
X116a
X112
X120
5 Installation
7684359 - v.11 - 13122021 31
6 Preparation of commissioning
6.1 Checklist before commissioning
6.1.1 Filling the siphon
Danger
The siphon must always be sufficiently filled with water. This
prevents flue gases from entering the room.
1. Remove the siphon.
2. Fill the siphon up with water.
3. Fit the siphon.
Check that the siphon is securely fitted and that there are no leaks.
6.1.2 Filling the system
Caution
Before filling, open the valves on every radiator in the installation.
Important
In order to be able to read off the water pressure from the boiler
display, the boiler must be switched on.
1. Fill the central heating system with clean tap water.
Important
The recommended water pressure is between 1.5 bar and 2 bar.
2. Check the water-side connections for tightness.
6.1.3 Gas circuit
1Gas valve unit on the Quinta Ace 30 - 45 - 55 - 65 - 90
2Quinta Ace 115
Warning
Ensure that the boiler is switched off.
Do not put the boiler into operation if the type of gas supplied
does not conform to the approved gas types.
1. Open the main gas tap.
2. Open the boiler gas tap.
3. Unscrew the two screws located under the front housing by a quarter
turn and remove the front housing.
Fig.39 Filling the siphon
AD-0000086-01
1
3
2
Fig.40 Gas valve unit measuring points C
AD-0000066-02
C C
1 2
6 Preparation of commissioning
32 7684359 - v.11 - 13122021
4. Check the gas inlet pressure at the measuring point C on the gas
valve unit.
Warning
The gas pressure that was measured at the measuring point C
must fall within the stated gas inlet pressure limits. See
Technical data, page 79
For authorised gas pressures, see: Unit categories, page 76
5. Vent the gas supply pipe by unscrewing the measuring point on the
gas valve unit.
6. Tighten the measuring point again when the pipe has been fully
vented.
7. Check all connections for gas tightness. The maximum allowable test
pressure is 60 mbar.
6.1.4 Hydraulic circuit
1. Check the siphon; it should be fully filled with clean water.
2. Check the water-side connections for tightness.
6.1.5 Electrical connections
1. Check the electrical connections.
6.2 Control panel description
6.2.1 Control panel components
1 Rotary knob to select a tile, menu or setting
2 Confirm button to confirm the selection
3 Back button :
Short button press: Return to the previous level or previous
menu
Long button press: Return to home screen
4 Menu button to go to the main menu
5 Display
6 Status LED
See also
Additional documentation, page 8
6.2.2 Description of the home screen
This screen is shown automatically after start-up of the appliance. The
control panel automatically enters standby mode (black screen) if the
buttons are not used for 5 minutes. Press one of the buttons on the control
panel to activate the screen again.
You can navigate from any menu to the home screen by pressing the back
button for several seconds.
The tiles on the home screen provide quick access to the corresponding
menus. Use the rotary knob to navigate to the desired item and press the
button to confirm the selection.
Fig.41 Control panel components
AD-3000932-02
4
6
3
2
1
5
6 Preparation of commissioning
7684359 - v.11 - 13122021 33
1Tiles: the selected tile is highlighted
2Date and time | Name of the screen (actual position in the menu)
3Information about the selected tile
4Icons indicating navigation level, operating mode, errors and other
information.
6.2.3 Description of the main menu
You can navigate from any menu directly to the main menu by pressing
the menu button . The number of accessible menus depends on the
access level (user or installer).
ADate and time | Name of the screen (actual position in the menu)
BAvailable menus
CBrief explanation of the selected menu
Tab.24 Available menus for the user
Description Icon
Enable installer access
System Settings
Version Information
Tab.25 Available menus for the installer
Description Icon
Disable installer access
Installation Setup
Commissioning Menu
Advanced Service Menu
Error History
System Settings
Version Information
6.2.4 Description of the icons in the display
Tab.26 Icons
Icon Description
User menu: user-level parameters can be configured.
Installer menu: installer-level parameter can be configured.
Information menu: read out various current values.
System settings: system parameters can be configured.
Error indicator.
Gas boiler indicator.
Domestic hot water tank is connected.
The outdoor temperature sensor is connected.
Boiler number in cascade system.
The solar calorifier is on and its heat level is displayed.
Burner output level (1 to 5 bars, with each bar representing 20% output).
Fig.42 Icons on home screen
AD-3001157-03
All OK
Error Status
i
i
All OK
Home Screen
22/02/2018 11:20
2 43
1
Fig.43 Items in the main menu
AD-3000935-02
........ ....... .......... ... ...... .........
....... ........
........ .......
...... .....11:20
.......... ......... ............
.... ..........
.................. ......
B
C
A
6 Preparation of commissioning
34 7684359 - v.11 - 13122021
Icon Description
The pump is running.
Three-way valve indicator.
Display of the system water pressure.
Chimney sweep mode is enabled (forced full load or low load for O2 measurement).
Energy-saving mode is enabled.
DHW boost is enabled.
Timer program is enabled: The room temperature is controlled by a timer program.
Manual mode is enabled: The room temperature is set to a fixed setting.
Temporary overwrite of the timer program is enabled: The room temperature is changed temporarily.
The holiday program (including frost protection) is active: The room temperature is reduced during your holiday to
save energy.
Frost protection is enabled: Protect the boiler and installation from freezing in winter.
Service notification: service needed.
Installer contact details are displayed or can be filled in.
Tab.27 Icons - On/off
Icon Description Icon Description
CH operation is enabled. CH operation is disabled.
DHW operation is enabled. DHW operation is disabled.
The burner is on. The burner is off.
Bluetooth enabled and connected (icon is non-trans
parent).
Bluetooth enabled and disconnected (icon is trans
parent).
Heating enabled.
Cooling enabled.
Heating/cooling enabled. Heating/cooling disabled.
Tab.28 Icons - Zones
Icon Description
All zones (groups) icon.
Living room icon.
Kitchen icon.
Bedroom icon.
Study icon.
Cellar icon.
7 Commissioning
7.1 Commissioning procedure
Warning
Initial commissioning must be done by a qualified installer.
If adapting to another type of gas, e.g. propane, the boiler must
be adjusted before it is switched on.
See
Fan speed for different gas types, page 37
1. Open the main gas tap.
2. Open the boiler gas tap.
7 Commissioning
7684359 - v.11 - 13122021 35
3. Switch the power on with the boiler's on/off switch.
The start-up program will start and cannot be interrupted. During the
program, all segments of the display are shown briefly.
4. Set the components (thermostats, control) so that heat is demanded.
Important
In the event of an error during the start-up, a message with the
corresponding code is displayed. The meaning of the error codes
can be found in the error table.
7.2 Gas settings
7.2.1 Factory setting
The factory setting of the boiler is for operation with the natural gas group
G20 (H gas).
Tab.29 Factory settings G20 (H-gas)
Code Display text Description Adjustment range 30 45 55 65 90 115
DP003 Abs. max fan
DHW
Maximum fan speed on Do
mestic Hot Water
1400 - 7500 Rpm 4100 5400 5100 5600 6300 6800
GP007 Fan RPM
Max CH
Maximum fan speed during
Central Heating mode
1400 - 7500 Rpm 4100 5400 5100 5600 6300 6800
GP008 Fan RPM Min Minimum fan speed during
Central Heating + Domestic
Hot Water mode
1000 - 4000 Rpm 1550 1550 1600 1600 1600 1750
GP009 Fan RPM
Start
Fan speed at appliance start 1400 - 4000 Rpm 2500 2500 2500 2500 2500 2500
7.2.2 Adjusting to a different gas type
Warning
Only a qualified installer may carry out the following operations.
Important
If the boiler is adapted to another gas type, this must be stated on
the sticker supplied. This sticker must be affixed next to the data
plate.
Before operating with a different type of gas, carry out the following steps.
Adjusting the gas valve unit for propane
Important
For the Quinta Ace 90 boiler; replace the current gas valve unit
with the propane gas valve unit according to the instructions
supplied with the propane conversion kit.
1 Gas valve unit on the Quinta Ace 30 - 45 - 55 - 65 - 90
2 Gas valve unit on the Quinta Ace 115
Fig.44 Position of adjusting screw A
AD-0000067-02
A A
1 2
7 Commissioning
36 7684359 - v.11 - 13122021
1. Using adjusting screw A, adjust the factory setting to the setting for
propane. The rotations for each boiler type are described in the table.
Tab.30 Settings for propane
Boiler type Action
Quinta Ace 30 Rotate the adjusting screw A on the venturi 3½
turns in a clockwise direction
Quinta Ace 45 Rotate the adjusting screw A on the venturi 4¾
turns in a clockwise direction
Quinta Ace 55 Rotate the adjusting screw A on the venturi 6½
turns in a clockwise direction
Quinta Ace 65 Rotate the adjusting screw A on the venturi 6½
turns in a clockwise direction
Quinta Ace 115 Rotate the adjusting screw A in a clockwise direc
tion until it is closed, then:
Rotate the adjusting screw A on the gas valve unit
3½–4 turns in an anticlockwise direction
Adjusting fan speed parameters for different gas types
The factory fan speed settings can be adjusted for a different type of gas
at installer level.
> Parameters, counters, signals > Parameters
Use the rotary knob to navigate.
Use the button to confirm your selection.
1. Enable Installer access.
1.1. Select the tile [ ].
1.2. Enter code: 0012.
2. Select the tile [ ].
3. Select Parameters, counters, signals.
4. Select Parameters.
5. Select the required parameter.
6. Change the setting.
Fan speed for different gas types
1. Adjust the fan speed (if necessary) for the gas type used according to
the table below. The setting can be changed with a parameter setting.
If a boiler is not suitable for a certain gas type, it is indicated with "-" in
the table.
Tab.31 Adjustment for gas type G31 (propane)
Code Display text Description Adjustment range 30 45 55 65 90 115
DP003 Abs. max fan
DHW
Maximum fan speed on Do
mestic Hot Water
1400 - 7500 Rpm 3800 5100 4800 5400 6000 6700
GP007 Fan RPM
Max CH
Maximum fan speed during
Central Heating mode
1400 - 7500 Rpm 3800 5100 4800 5400 6000 6700
GP008 Fan RPM Min Minimum fan speed during
Central Heating + Domestic
Hot Water mode
1000 - 4000 Rpm 1550 1550 1500 1600 2000 1800
GP009 Fan RPM
Start
Fan speed at appliance start 1400 - 4000 Rpm 2500 3000 2500 2500 2500 3500
2. Check the setting of the gas/air ratio.
Fan speeds for BREEAM compliance
To comply with the BREEAM regulation, the fan speeds need to be
adjusted.
7 Commissioning
7684359 - v.11 - 13122021 37
Warning
For the Quinta Ace 115, a flue gas pressure switch must be fitted
before setting the fan speeds for BREEAM. This switch has a
switch value of 600 Pa and protects against high flue pressures.
1. Adjust the fan speed according to the tables below. The setting can be
changed with a parameter setting.
Tab.32 Adjustment for BREEAM with gas type G20 (H gas)
Code Display text Description Adjustment range 30 45 55 65 90 115
DP003 Abs. max fan
DHW
Maximum fan speed on Do
mestic Hot Water
1400 - 7500 Rpm 4100 5800 5600 6100 6600 7300
GP007 Fan RPM
Max CH
Maximum fan speed during
Central Heating mode
1400 - 7500 Rpm 4100 5800 5600 6100 6600 7300
GP008 Fan RPM Min Minimum fan speed during
Central Heating + Domestic
Hot Water mode
1000 - 4000 Rpm 1550 1550 1650 1600 1600 1750
GP009 Fan RPM
Start
Fan speed at appliance start 1400 - 4000 Rpm 2500 2500 2500 2500 2500 2500
Tab.33 Adjustment for BREEAM with gas type G31 (propane)
Code Display text Description Adjustment range 30 45 55 65 90 115
DP003 Abs. max fan
DHW
Maximum fan speed on Do
mestic Hot Water
1400 - 7500 Rpm 4100 5700 5600 6200 6500 7300
GP007 Fan RPM
Max CH
Maximum fan speed during
Central Heating mode
1400 - 7500 Rpm 4100 5700 5600 6200 6500 7300
GP008 Fan RPM Min Minimum fan speed during
Central Heating + Domestic
Hot Water mode
1000 - 4000 Rpm 1550 1550 1650 1650 2100 1800
GP009 Fan RPM
Start
Fan speed at appliance start 1400 - 4000 Rpm 2500 3000 2500 2500 2500 3500
2. Check the setting of the gas/air ratio.
Important
Make sure to apply the O2 values specified for BREEAM.
7.2.3 Checking and setting the gas/air ratio
1. Unscrew the cap from the flue gas measuring point.
2. Insert the probe for the flue gas analyser into the measurement
opening.
Warning
During measurement, seal the opening around the sensor fully.
Important
The flue gas analyser must have a minimum accuracy of
±0.25% O2.
The flue gas analyser must meet the requirements of BS 7927
or BS-EN 503793 and be calibrated according to the
manufacturer's requirements.
Fig.45 Flue gas measuring point
AD-0000069-01
7 Commissioning
38 7684359 - v.11 - 13122021
3. Measure the percentage of O2 in the flue gases. Take measurements
at full load and at part load.
Important
Measurements must be taken with the front casing off.
Important
This appliance is suitable for category I2H containing up to 20%
Hydrogen gas (H2). Due to variations in the H2 percentage, the
O2 percentage can vary over time. (For example: a percentage
of 20% H2 in the gas can lead to an increase of 1,5% of O2 in
the flue gasses)
A significant adjustment of the gas valve may be needed.
Adjustment can be done using the standard O2 values of the
gas used.
Performing the full load test
1. Select the tile [ ].
The Change load test mode menu appears.
2. Select the test Medium power.
AChange load test mode
BMedium power
The full load test starts. The selected load test mode is shown in the
menu and the icon appears in the top right of the screen.
3. Check the load test settings and adjust if necessary.
Only the parameters shown in bold can be changed.
Checking/setting values for O2 at full load
1 Gas valve unit on the Quinta Ace 30 - 45 - 55 - 65 - 90
2 Quinta Ace 115
1. Measure the percentage of O2 in the flue gases.
2. Compare the measured value with the checking values in the table.
3. If the measured value is outside of the values given in the table,
correct the gas/air ratio.
Warning
Only a qualified installer may carry out the following operations.
4. Using adjusting screw A, adjust the percentage of O2 for the gas type
being used to the nominal value. This should always be inside the
highest and lowest setting limit.
If a boiler is not suitable for a certain gas type, it is indicated with "-" in
the table.
Tab.34 Checking/setting values for O2 at full load for G20 (H gas)
Values at full load for G20 (H gas) O2 (%)(1)
Quinta Ace 30 4,3 - 4,8 (1)
Quinta Ace 45 4,3 - 4,8 (1)
Quinta Ace 55 4,3 - 4,8 (1)
Quinta Ace 65 4,3 - 4,8 (1)
Quinta Ace 90 4,3 - 4,7 (1)
Quinta Ace 115 4,2 - 4,7 (1)
(1) Nominal value
Fig.46 Full load test
AD-3000941-03
..... ... ....... .... .. ..... .... .........
..... ... ....... ....
..... ... ....... ....
....... .... .. ..... .... .......
....... ...........
......
.....
...
.....
..... ... ....... .... .. ..... ....... .... ..... .......
i
.....
....... .... ....... .... .......
.... ...... ....... ......11:20
A
B
Fig.47 Position of adjusting screw A
AD-0000067-02
A A
1 2
7 Commissioning
7684359 - v.11 - 13122021 39
Tab.35 Checking/setting values for O2 at full load for BREEAM with
G20 (H gas)
Values at full load for G20 (H gas) O2 (%)(1)(2)
Quinta Ace 30 4,9 - 5,4 (1)
Quinta Ace 45 5,6 - 6,1 (1)
Quinta Ace 55 5,6 - 6,1 (1)
Quinta Ace 65 5,4 - 5,9 (1)
Quinta Ace 90 5,3 - 5,7 (1)
Quinta Ace 115 5,6 - 6,1 (1)
(1) Nominal value
(2) These values are only applicable when the fan speeds have been set
for BREEAM.
Tab.36 Checking/setting values for O2 at full load for G31 (propane)
Values at full load for G31 (propane) O2 (%)
(1)
Quinta Ace 30 4,4 - 4,9 (1)
Quinta Ace 45 4,4 - 4,9 (1)
Quinta Ace 55 4,1 - 4,6 (1)
Quinta Ace 65 4,6 - 4,9 (1)
Quinta Ace 90 4,9 - 5,2 (1)
Quinta Ace 115 4,9 - 5,4 (1)
(1) Nominal value
Tab.37 Checking/setting values for O2 at full load for BREEAM with
G31 (propane)
Values at full load for G31 (propane) O2 (%)(1) (2)
Quinta Ace 30 5,9 - 6,4 (1)
Quinta Ace 45 6,2 - 6,7 (1)
Quinta Ace 55 6,2 - 6,7 (1)
Quinta Ace 65 6,6 - 6,9 (1)
Quinta Ace 90 6,3 - 6,6 (1)
Quinta Ace 115 6,1 - 6,6 (1)
(1) Nominal value
(2) These values are only applicable when the fan speeds have been set
for BREEAM.
Caution
The O2 values at full load must be lower than the O2 values at part
load.
Performing the low load test
1. If the full load test is still running, press the button to change the
load test mode.
7 Commissioning
40 7684359 - v.11 - 13122021
2. If the full load test was finished, select the tile [ ] to restart the
chimney sweep menu.
A Change load test mode
B Low power
3. Select the Low power test in the menu Change load test mode.
The low load test starts. The selected load test mode is shown in
the menu and the icon appears in the top right of the screen.
4. Check the load test settings and adjust if necessary.
Only the parameters shown in bold can be changed.
5. End the low load test by pressing the button.
The message Running load test(s) stopped! is displayed.
Checking/setting values for O2 at part load
1 Gas valve unit on the Quinta Ace 30 - 45 - 55 - 65 - 90
2 Quinta Ace 115
1. Measure the percentage of O2 in the flue gases.
2. Compare the measured value with the checking values in the table.
3. If the measured value is outside of the values given in the table,
correct the gas/air ratio.
Warning
Only a qualified installer may carry out the following operations.
4. Using adjusting screw B, adjust the percentage of O2 for the gas type
being used to the nominal value. This should always be inside the
highest and lowest setting limit.
5. Set the boiler back to the normal operating status.
If a boiler is not suitable for a certain gas type, it is indicated with "-" in
the table.
Tab.38 Checking/setting values for O2 at part load for G20 (H gas)
Values at part load for G20 (H gas) O2 (%)(1)
Quinta Ace 30 5,7 (1) - 6,2
Quinta Ace 45 5,7 (1) - 6,2
Quinta Ace 55 4,8 (1) - 5,3
Quinta Ace 65 4,8 (1) - 5,3
Quinta Ace 90 5,2 (1) - 5,6
Quinta Ace 115 5,6 (1) - 6,1
(1) Nominal value
Tab.39 Checking/setting values for O2 at part load for BREEAM with
G20 (H gas)
Values at part load for G20 (H gas) O2 (%)(1)(2)
Quinta Ace 30 6,1 (1) - 6,6
Quinta Ace 45 6,5 (1) - 7,0
Quinta Ace 55 6,1 (1) - 6,6
Quinta Ace 65 5,9 (1) - 6,4
Quinta Ace 90 5,7 (1) - 6,1
Quinta Ace 115 6,1 (1) - 6,6
(1) Nominal value
(2) These values are only applicable when the fan speeds have been set
for BREEAM.
Fig.48 Low load test
AD-3000941-03
..... ... ....... .... .. ..... .... .........
..... ... ....... ....
..... ... ....... ....
....... .... .. ..... .... .......
....... ...........
......
.....
...
.....
..... ... ....... .... .. ..... ....... .... ..... .......
i
.....
....... .... ....... .... .......
.... ...... ....... ......11:20
A
B
Fig.49 Position of adjusting screw B
AD-0000072-02
B B
B
1 2
7 Commissioning
7684359 - v.11 - 13122021 41
Tab.40 Checking/setting values for O2 at part load for G31
(propane)
Values at part load for G31 (propane) O2 (%)(1)
Quinta Ace 30 5,4 (1) - 5,9
Quinta Ace 45 5,7 (1) - 6,2
Quinta Ace 55 5,1 (1) - 5,6
Quinta Ace 65 5,4 (1) - 5,7
Quinta Ace 90 5,7 (1) - 6,0
Quinta Ace 115 5,8 (1) - 6,3
(1) Nominal value
Tab.41 Checking/setting values for O2 at part load for BREEAM with
G31 (propane)
Values at part load for G31 (propane) O2 (%)(1)(2)
Quinta Ace 30 6,7 (1) - 7,2
Quinta Ace 45 7,1 (1) - 7,6
Quinta Ace 55 6,7 (1) - 7,2
Quinta Ace 65 6,9 (1) - 7,2
Quinta Ace 90 7,4 (1) - 7,7
Quinta Ace 115 6,9 (1) - 7,4
(1) Nominal value
(2) These values are only applicable when the fan speeds have been set
for BREEAM.
Caution
The O2 values at part load must be higher than the O2 values at
full load.
7.3 Final instructions
1. Remove the measuring equipment.
2. Screw the cap on to the flue gas measuring point.
3. Seal the gas valve unit.
4. Put the front casing back.
5. Heat up the central heating system to approximately 70°C.
6. Switch the boiler off.
7. Vent the central heating system after approx. 10 minutes.
8. Turn on the boiler.
9. Check the water pressure. If necessary, top up the central heating
system.
7 Commissioning
42 7684359 - v.11 - 13122021
10. Fill in the following data on the sticker included, and attach it next to
the data plate on the appliance.
The gas supply pressure;
The flue type, if set to overpressure application;
The parameters modified for the changes mentioned above;
Any fan speed parameters modified for other purposes.
11. Optimise the settings as required for the system and user
preferences.
See
For more information; Settings, page 43 and User instructions,
page 65.
12. Save the commissioning settings on the control panel, so they can be
restored after a reset.
13. Instruct the user in the operation of the system, boiler and controller.
14. Inform the user of the maintenance to be performed.
15. Hand over all manuals to the user.
7.3.1 Saving the commissioning settings
You can save all current settings on the control panel. These settings can
be restored if necessary, for example after replacement of the control unit.
> Advanced Service Menu > Save as commissioning settings
Use the rotary knob to navigate.
Use the button to confirm your selection.
1. Press the button.
2. Select Advanced Service Menu.
3. Select Save as commissioning settings.
4. Select Confirm to save the settings.
When you have saved the commissioning settings, the option Revert
commissioning settings becomes available in the Advanced Service Menu.
8 Settings
8.1 Introduction to parameter codes
The controls platform makes use of an advanced system to categorise
parameters, measurements and counters. Knowing the logic behind these
codes, makes it easier to identify them. The code consists of two letters
and three numbers.
The first letter is the category the code relates to.
AAppliance: Appliance
CCircuit: Zone
DDomestic hot water: Domestic hot water
GGas fired: Gas-fired heat engine
PProducer: Central heating
Category D codes are appliance controlled only. When the domestic hot
water is controlled by an SCB, it is handled like a circuit, with C-category
codes.
Fig.50 Example filled-in sticker
AD-3001124-01
Adjusted for / Réglée pour /
Ingesteld op / Eingestellt auf
/ Regolato per / Ajustado
para / Ρυθμισμένο για /
Nastawiony na / настроен
для / Reglat pentru /
настроен за / ayarlanmıştır /
Nastavljen za / beállítva/
Nastaveno pro / Asetettu
kaasulle / Justert for/
indstillet til/ ضبط ل :
C(10)3(X)
Gas
C(12)3(X)
mbar
Parameters / Paramètres /
Parameter / Parametri /
Parámetros / Παράμετροι /
Parametry / Параметры /
Parametrii / Параметри /
Parametreler / Paraméterek
/ Parametrit / Parametere /
Parametre / المعلمات :
G20
20
DP003 - 3300
GP007 - 3300
GP008 - 2150
GP009 -
Fig.51 Code on a HMI T-control
AD-3001373-02
00:12 ...... ......
........ .......
........ .......
....................
..... ... ....... .... .. ..... ....... .... ..... .......
..... ... ....... .... .. ..... .... .........
..... ... ....... ....
..... ... ....... ....
....... .... .. ..... .... .......
....... ...........
......
.....
...
CP010
CP010
Fig.52 First letter
AD-3001375-01
CP010
8 Settings
7684359 - v.11 - 13122021 43
The second letter is the type.
PParameter: Parameters
CCounter: Counters
MMeasurement: Signals
The number is always three digits. In certain cases, the last of the three
digits relates to a zone.
8.2 Searching the parameters, counters and signals
You can search and change data points (Parameters, counters, signals) of
the appliance, connected control boards and sensors.
> Installation Setup > Search datapoints
Use the rotary knob to navigate.
Use the button to confirm your selection.
1. Press the button.
2. Select Installation Setup.
3. Select Search datapoints.
4. Select the search criteria (code):
4.1. Select the first letter (datapoint category).
4.2. Select the second letter (datapoint type).
4.3. Select the first number.
4.4. Select the second number.
4.5. Select the third number.
The * symbol can be used to indicate any character within the
search field.
The list of datapoints appears in the display. Only the first 30 results
are shown when searching.
5. Select the desired datapoint.
8.3 List of parameters
8.3.1 CU-GH08 control unit parameters
All tables show the factory setting for the parameters.
Important
The tables also list parameters that are only applicable if the boiler
is combined with other equipment.
Tab.42 Navigation for basic installer level
Level Menu path
Basic installer > Installation Setup > CU-GH08 > Submenu (1) > Parameters, counters, signals > Parameters >
General
(1) See the column "Submenu" in the following table for the correct navigation. The parameters are grouped in specific functionalities.
Fig.53 Second letter
AD-3001376-01
CP010
Fig.54 Number
AD-3001377-01
CP010
Fig.55 Search
AD-3001916-01
00:12 ........ .......
........ .......
........ ......... ...
..... ... ....... .... .. ..... ....... .... ..... .......
*
A
B
C
D
E
*
C
M
P
*
0
1
2
3
4
*
0
1
2
3
4
*
0
1
2
3
4
i
Fig.56 List of datapoints
AD-3001917-01
00:12 ........ .......
........ .......
........ ......... ...
..... ... ....... .... .. ..... ....... .... ..... .......
AC001
AC002
AM001
AM002
AP001
...... ... ....... ....... .... ...
...... .......... .......
.............. ...
...... ... .
........ ..
....... ...
.......
.... ...
...... ..
....... .... ...
AC001
..... ... ....... .... .. ..... ....... .... ..... .......
i
8 Settings
44 7684359 - v.11 - 13122021
Tab.43 Factory settings at basic installer level
Code Display text Description Adjustment range Subme
nu
30 45 55 65 90 115
AP016 CH function
on
Enable central heating
heat demand processing
0 = Off
1 = On
Gas
fired ap
pliance
1 1 1 1 1 1
AP017 DHW func
tion on
Enable domestic hot water
heat demand processing
0 = Off
1 = On
Gas
fired ap
pliance
1 1 1 1 1 1
AP073 Summer
Winter
Outdoor temperature: up
per limit for heating
10 - 30 °C Outdoor
tempera
ture
22 22 22 22 22 22
AP074 Force sum
mer mode
The heating is stopped.
Hot water is maintained.
Force Summer Mode
0 = Off
1 = On
Outdoor
tempera
ture
0 0 0 0 0 0
AP083 Enable mas
ter func
Enable the master func
tionality of this device on
the S-Bus for system con
trol
0 = No
1 = Yes
Manda
tory bus
master
0 0 0 0 0 0
AP089 Installer
name
Name of the installer Manda
tory bus
master
None None None None None None
AP090 Installer
phone
Telephone number of the
installer
Manda
tory bus
master
0 0 0 0 0 0
AP107 Color dis
play Mk2
Color display Mk2 0 = White
1 = Red
2 = Blue
3 = Green
4 = Orange
5 = Yellow
Manda
tory bus
master
2 2 2 2 2 2
CP000 MaxZoneT
FlowSet
point
Maximum Flow Tempera
ture setpoint zone
0 - 90 °C CIRCA 80 80 80 80 80 80
CP080
CP081
CP082
CP083
CP084
CP085
User
T.Room Ac
tivity
Room setpoint tempera
ture of the user zone activ
ity
5 - 30 °C CIRCA 16
20
6
21
22
20
16
20
6
21
22
20
16
20
6
21
22
20
16
20
6
21
22
20
16
20
6
21
22
20
16
20
6
21
22
20
CP200 Manu Zo
neRoom
TempSet
Manually setting the room
temperature setpoint of
the zone
5 - 30 °C CIRCA 20 20 20 20 20 20
CP320 Operating
ZoneMode
Operating mode of the
zone
0 = Scheduling
1 = Manual
2 = Off
CIRCA 1 1 1 1 1 1
CP510 Temporary
Room Setp
Temporary room setpoint
per zone
5 - 30 °C CIRCA 20 20 20 20 20 20
CP550 Zone, fire
place
Fire Place mode is active 0 = Off
1 = On
CIRCA 0 0 0 0 0 0
CP660 Icon display
zone
Choice icon to display this
zone
0 = None
1 = All
2 = Bedroom
3 = Livingroom
4 = Study
5 = Outdoor
6 = Kitchen
7 = Basement
CIRCA 3 3 3 3 3 3
DP060 DHW time
prog. select
Time program selected for
DHW.
0 = Schedule 1
1 = Schedule 2
2 = Schedule 3
Internal
DHW
0 0 0 0 0 0
8 Settings
7684359 - v.11 - 13122021 45
Code Display text Description Adjustment range Subme
nu
30 45 55 65 90 115
DP070 DHW com
fort setpoint
Comfort temperature set
point for the Domestic Hot
Water tank
40 - 65 °C Internal
DHW
60 60 60 60 60 60
DP080 DHW re
duced set
point
Reduced temperature set
point from the Domestic
Hot Water tank
7 - 50 °C Internal
DHW
15 15 15 15 15 15
DP200 DHW mode DHW primary mode cur
rent working setting
0 = Scheduling
1 = Manual
2 = Off
Internal
DHW
1 1 1 1 1 1
DP337 DHW holi
day setpoint
Holiday temperature set
point from the Domestic
Hot Water tank
10 - 60 °C Internal
DHW
10 10 10 10 10 10
Tab.44 Navigation for installer level
Level Menu path
Installer > Installation Setup > CU-GH08 > Submenu (1) > Parameters, counters, signals > Parameters >
General
(1) See the column "Submenu" in the following table for the correct navigation. The parameters are grouped in specific functionalities.
Tab.45 Factory settings at installer level
Code Display text Description Adjustment range Subme
nu
30 45 55 65 90 115
AP001 BL function BL input function selection 1 = Full blocking
2 = Partial blocking
3 = User reset lock
ing
Gas
fired ap
pliance
1 1 1 1 1 1
AP003 Flue valve
wait time
Heat generator wait time
to open the flue gas
0 - 255 Sec Gas
fired ap
pliance
0 0 0 0 0 0
AP006 Min. water
pressure
Appliance will report low
water pressure below this
value
0 - 6 bar Gas
fired ap
pliance
0.8 0.8 0.8 0.8 0.8 0.8
AP008 Release
wait time
Waiting time after closing
the release contact to start
the heat generator.
0 - 255 Sec Gas
fired ap
pliance
0 0 0 0 0 0
AP009 Service
hours
Number of heat generator
operating hours for raising
a service notification
0 - 51000 Hours Gas
fired ap
pliance
6000 6000 6000 6000 6000 6000
AP010 Service noti
fication
Select the type of service
notification
0 = None
1 = Custom notifi
cation
2 = ABC notifica
tion
Gas
fired ap
pliance
2 2 2 2 2 2
AP011 Service
hours mains
Hours powered to raise a
service notification
0 - 51000 Hours Gas
fired ap
pliance
3500
0
3500
0
3500
0
3500
0
3500
0
3500
0
AP013 Release
function
Function of the release in
put contact
0 = Disabled
1 = Full blocking
2 = Central heat
blocked
Gas
fired ap
pliance
1 1 1 1 1 1
AP018 Sets release
input
Configuration of the re
lease input contact (nor
mally open or normally
closed)
0 = Normally open
1 = Normally
closed
Gas
fired ap
pliance
0 0 0 0 0 0
AP079 Building In
ertia
Inertia of the building used
for heat up speed
0 - 15 Outdoor
tempera
ture
3 3 3 3 3 3
8 Settings
46 7684359 - v.11 - 13122021
Code Display text Description Adjustment range Subme
nu
30 45 55 65 90 115
AP080 Frost min
out temp
Outside temperature be
low which the antifreeze
protection is activated
-60 - 25 °C Outdoor
tempera
ture
-10 -10 -10 -10 -10 -10
AP082 Enable day
light save
Enable daylight saving for
the system to save energy
during winter
0 = Off
1 = On
Manda
tory bus
master
1 1 1 1 1 1
AP091 Outside
Sens.
Source
Type of outside sensor
connection to be used
0 = Auto
1 = Wired sensor
2 = Wireless sen
sor
3 = Internet meas
ured
4 = None
Outdoor
tempera
ture
0 0 0 0 0 0
AP098 BL1 contact
config.
BL1 input contact configu
ration
0 = Open
1 = Closed
Gas
fired ap
pliance
1 1 1 1 1 1
AP108 OutsideSen
sorEnabled
Enable the function Out
side Sensor
0 = Auto
1 = Wired sensor
Outdoor
tempera
ture
0 0 0 0 0 0
CP020 Zone Func
tion
Functionality of the zone 0 = Disable
1 = Direct
CIRCA 1 1 1 1 1 1
CP060 RoomT.
Holiday
Wished room zone tem
perature on holiday period
5 - 20 °C CIRCA 6 6 6 6 6 6
CP070 MaxRedu
ce
dRoomT.Li
m
Max Room Temperature
limit of the circuit in re
duced mode, that allows
switching to comfort mode
5 - 30 °C CIRCA 16 16 16 16 16 16
CP210 Zone HCZP
Comfort
Comfort footpoint of the
temperature of heat curve
of the circuit
15 - 90 °C CIRCA 15 15 15 15 15 15
CP220 Zone HCZP
Reduced
Reduced footpoint of the
temperature of heat curve
of the circuit
15 - 90 °C CIRCA 15 15 15 15 15 15
CP230 Zone Heat
ing Curve
Heating curve temperature
gradient of the zone
0 - 4 CIRCA 1.5 1.5 1.5 1.5 1.5 1.5
CP340 TypeRedu
cedNight
Mode
Type of reduced night
mode, stop or maintain
heating of circuit
0 = Stop heat de
mand
1 = Continue heat
demand
CIRCA 1 1 1 1 1 1
CP470 Zone screed
drying
Setting of the screed dry
ing program of the zone
0 - 30 Days CIRCA 0 0 0 0 0 0
CP480 ScreedStart
Temp
Setting of the start temper
ature of the screed drying
program of the zone
20 - 50 °C CIRCA 20 20 20 20 20 20
CP490 ScreedStop
Temp
Setting of the stop temper
ature of the screed drying
program of the zone
20 - 50 °C CIRCA 20 20 20 20 20 20
CP570 ZoneTime
Prog Select
Time Program of the zone
selected by the user
0 = Schedule 1
1 = Schedule 2
2 = Schedule 3
CIRCA 0 0 0 0 0 0
CP730 Zone Heat
up speed
Selection of heat up speed
of the zone
0 = Extra Slow
1 = Slowest
2 = Slower
3 = Normal
4 = Faster
5 = Fastest
CIRCA 3 3 3 3 3 3
8 Settings
7684359 - v.11 - 13122021 47
Code Display text Description Adjustment range Subme
nu
30 45 55 65 90 115
CP740 Zone cool
down speed
Selection of cool down
speed of the zone
0 = Slowest
1 = Slower
2 = Normal
3 = Faster
4 = Fastest
CIRCA 2 2 2 2 2 2
CP750 MaxZone
Preheat
time
Maximum zone preheat
time
0 - 240 Min CIRCA 90 90 90 90 90 90
CP780 Control
strategy
Selection of the control
strategy for the zone
0 = Automatic
1 = Room Temp.
based
2 = Outdoor Temp.
based
3 = Outdoor &
room based
CIRCA 0 0 0 0 0 0
DP004 Legionella
calor.
Legionella mode protec
tion calorifier
0 = Disabled
1 = Weekly
2 = Daily
Internal
DHW
Tank
DHW
1 1 1 1 1 1
DP007 Dhw 3wv
Standby
Position of three way valve
during standby
0 = CH position
1 = DHW position
Tank
DHW
0 0 0 0 0 0
DP140 DHW load
type
DHW load type (0 : Combi,
1 : Solo)
0 = Combi
1 = Solo
2 = Layered cylin
der
3 = Process heat
4 = External
Internal
DHW
Tank
DHW
Gas
fired ap
pliance
1 1 1 1 1 1
DP160 DHW Anti
Leg Set
point
Setpoint for DHW anti le
gionella
50 - 90 °C Internal
DHW
70 70 70 70 70 70
DP410 DHW anti-
leg runtime
Duration of the DHW anti-
legionella program
0 - 600 Min Internal
DHW
60 60 60 60 60 60
DP430 Start day
anti-leg
Day to start the DHW anti-
legionella program
1 = Monday
2 = Tuesday
3 = Wednesday
4 = Thursday
5 = Friday
6 = Saturday
7 = Sunday
Internal
DHW
6 6 6 6 6 6
DP440 Start time
anti-leg
Starting time for the DHW
anti-legionella program
0 - 143 HoursMi
nutes
Internal
DHW
18 18 18 18 18 18
PP015 CH Pump
postrun time
Central heating pump post
run time
0 - 99 Min Gas
fired ap
pliance
1 1 1 1 1 1
Tab.46 Navigation for advanced installer level
Level Menu path
Advanced installer > Installation Setup > CU-GH08 > Submenu (1) > Parameters, counters, signals > Parameters >
Advanced
(1) See the column "Submenu" in the following table for the correct navigation. The parameters are grouped in specific functionalities.
8 Settings
48 7684359 - v.11 - 13122021
Tab.47 Factory settings at advanced installer level
Code Display text Description Adjustment range Subme
nu
30 45 55 65 90 115
AP002 Manual
Heat De
mand
Enable manual heat de
mand function
0 = Off
1 = With setpoint
Gas
fired ap
pliance
0 0 0 0 0 0
AP026 Setpoint
manual HD
Flow temperature setpoint
for manual heat demand
10 - 90 °C Gas
fired ap
pliance
40 40 40 40 40 40
AP056 Outdoor
sensor
Enable outdoor sensor 0 = No outside sen
sor
1 = AF60
2 = QAC34
Outdoor
tempera
ture
1 1 1 1 1 1
AP102 Boiler Pump
function
Configuration of the boiler
pump as zone pump or
system pump (feed low
loss header)
0 = No
1 = Yes
Gas
fired ap
pliance
0 0 0 0 0 0
CP010 Tflow set
point zone
Zone flow temperature
setpoint, used when the
zone is set to a fixed flow
setpoint.
0 - 90 °C CIRCA 90 90 90 90 90 90
CP130 T.Outdoor
ToZone
Assigning the outdoor sen
sor to zone …
0 - 4 CIRCA 0 0 0 0 0 0
CP240 ZoneRoo
mUnitInfl
Adjustment of the influ
ence of the zone room unit
0 - 10 CIRCA 3 3 3 3 3 3
CP250 CalSon
deAmbZone
Calibration of Zone Room
Unit
-5 - 5 °C CIRCA 0 0 0 0 0 0
CP770 Zone Buf
fered
The zone is after a Buffer
tank
0 = No
1 = Yes
CIRCA 0 0 0 0 0 0
DP003 Abs. max
fan DHW
Maximum fan speed on
Domestic Hot Water
1400 - 7500 Rpm Gas
fired ap
pliance
4100 5400 5100 5600 6300 6700
DP005 Calorifier Tf
offset
Flow setpoint offset for
loading calorifier
0 - 50 °C Tank
DHW
20 20 20 20 20 20
DP006 Hyst calorifi
er
Hysteresis to start heating
calorifier
2 - 15 °C Tank
DHW
5 5 5 5 5 5
DP020 Postrun
DHW
pump/3wv
Post run time of the DHW
pump/3 way valve after
DHW production
0 - 99 Sec Gas
fired ap
pliance
10 10 10 10 10 10
DP034 DhwCalori
fierOffset
Offset for calorifier sensor 0 - 10 °C Tank
DHW
2 2 2 2 2 2
GP007 Fan RPM
Max CH
Maximum fan speed dur
ing Central Heating mode
1400 - 7500 Rpm Gas
fired ap
pliance
4100 5400 5100 5600 6300 6800
GP008 Fan RPM
Min
Minimum fan speed during
Central Heating + Domes
tic Hot Water mode
1000 - 4000 Rpm Gas
fired ap
pliance
1550 1550 1600 1600 1600 1750
GP009 Fan RPM
Start
Fan speed at appliance
start
1400 - 4000 Rpm Gas
fired ap
pliance
2500 2500 2500 2500 2500 2500
GP010 GPS Check Gas Pressure Switch
check on/off
0 = No
1 = Yes
Gas
fired ap
pliance
0 0 0 0 0 0
GP021 Temp diff
Modulating
Modulate back when delta
temperature is larger than
this threshold
10 - 40 (1)°C Gas
fired ap
pliance
25 25 25 25 25 20
GP082 Chimney
over DHW
Enable the DHW circuit
during chimney sweep
0 = Off
1 = On
Gas
fired ap
pliance
0 0 0 0 0 0
8 Settings
7684359 - v.11 - 13122021 49
Code Display text Description Adjustment range Subme
nu
30 45 55 65 90 115
PP014 ChPumpD
TReduction
Reduction of temperature
delta modulating for pump
modulation
0 - 40 °C Gas
fired ap
pliance
18 18 18 18 18 18
PP016 Max. CH
pump speed
Maximum central heating
pump speed (%)
30 - 100 % Gas
fired ap
pliance
100 100 100 100 100 100
PP017 ChPump
SpeedMax
Factor
Maximum central heating
at minimum load as per
centage of max pump
speed
0 - 100 % Gas
fired ap
pliance
100 100 100 100 100 100
PP018 Min CH
pump speed
Minimum central heating
pump speed (%)
30 - 100 % Gas
fired ap
pliance
30 30 30 30 30 30
(1) For the Quinta Ace115, this value is 35°C
9 Maintenance
9.1 Maintenance regulations
Important
The boiler must be maintained by a qualified installer in
accordance with local and national regulations.
Important
Adjust the frequency of inspection and service to the conditions of
use. This applies especially if the boiler is:
In constant use (for specific processes).
Used with a low supply temperature.
Used with a high ΔT.
Caution
Replace defective or worn parts with original spare parts. Not
doing so will void warranty.
During inspection and maintenance work, always replace all
gaskets on the parts removed.
Check whether all gaskets have been positioned properly
(absolutely flat in the appropriate groove means they are gas,
air and water tight).
During the inspection and maintenance work, water (drops,
splashes) must never come into contact with the electrical parts.
Warning
Always wear safety goggles and a dust mask during cleaning work
(involving compressed air).
Danger of electric shock
Ensure that the boiler is switched off.
9.2 Maintenance message
The boiler display will clearly indicate that a service is required at the
appropriate time. Use the automatic maintenance message for preventive
maintenance, to keep faults to a minimum. The service messages show
which service kit must be used. These service kits contain all parts and
gaskets that are required for the relevant service. These service kits (A, B
or C) put together by Remeha are available from spare parts suppliers.
9 Maintenance
50 7684359 - v.11 - 13122021
Important
Maintenance messages must be followed up within 2 months.
Important
If the iSense or eTwist modulating thermostat is connected to the
boiler, this thermostat can also display the maintenance message.
Consult the thermostat manual.
Caution
Reset the maintenance message following every service.
See
The service manual of the boiler.
See also
Additional documentation, page 8
9.3 Opening the boiler
1. Remove the two screws at the bottom of the front casing.
2. Remove the front panel.
9.4 Standard inspection and maintenance operations
For a service, always perform the following standard inspection and
maintenance operations.
See
The boiler service manual for the specific maintenance work.
9.4.1 Checking the water pressure
1. Check the water pressure.
Important
The recommended water pressure is between 1.5 bar and 2 bar.
The water pressure must be at least 0.8 bar.
2. If necessary, top up the central heating system.
9.4.2 Checking the ionisation current
1. Check the ionisation current at full load and at low load.
The value is stable after 1 minute.
2. Clean or replace the ionisation/ignition electrode if the value is lower
than 4 µA.
Fig.57 Opening the boiler
AD-3001159-01
11
22
9 Maintenance
7684359 - v.11 - 13122021 51
9.4.3 Checking the flue gas outlet/air supply connections
1. Check the flue gas outlet and air supply connections for condition and
tightness.
9.4.4 Checking the combustion
Combustion is checked by measuring the O2percentage in the flue gas
outlet duct.
9.4.5 Cleaning the siphon
Danger
The siphon must always be sufficiently filled with water. This
prevents flue gases from entering the room.
1. Dismantle the siphon and clean it.
2. Fill the siphon up with water.
3. Fit the siphon.
9.4.6 Checking the burner and cleaning the heat exchanger
1. Disconnect the two fan plugs on the front and rear.
2. Remove the screwed-on plug from the gas control valve.
3. Remove the ignition electrode plug from the ignition transformer.
Fig.58 Checking flue gas outlet/air supply
connections
AD-0000084-01
Fig.59 Cleaning the siphon
AD-0000086-01
1
3
2
Fig.60 Disconnecting the fan
AD-3001178-02
1
2
3
9 Maintenance
52 7684359 - v.11 - 13122021
4. Unscrew the nut of the gas valve unit.
5. Remove the air inlet pipe from the venturi.
6. Unscrew the front plate nuts.
7. Carefully lift the front plate, including the burner and fan, away from
the heat exchanger.
8. Use a vacuum cleaner fitted with a special end piece (accessory) to
clean the top part of the heat exchanger (combustion chamber).
9. Vacuum again without the top brush on the end piece.
10. Clean the lower section of the heat exchanger with the special
cleaning blade (accessory).
11. Check (e.g. using a mirror) whether any visible contamination has
been left behind. If it has, remove it with the vacuum cleaner.
12. Check that the burner cover of the dismantled burner is free from
cracks and/or damage. If not, replace the burner.
Servicing the burner is usually not necessary, it is self-cleaning. Use
compressed air to carefully blow away any dust.
13. Reassemble the unit in reverse order.
Caution
Check that the gasket is correctly positioned between the mixing
elbow and the heat exchanger. The gasket must lie absolutely
flat in the appropriate groove to ensure that no gas can leak.
Remember to reconnect the fan plugs.
Tighten the nut on the gas valve unit with a torque of 27.5 N⋅m.
Tighten the front plate nuts with a torque of 10 N⋅m.
14. Open the gas supply and switch the power supply to the boiler back
on.
Fig.61 Removing the gas and air supply
pipes
AD-3001971-01
4
5
Fig.62 Removing the front plate, fan and
burner
AD-3001179-01
6
7
Fig.63 Cleaning the heat exchanger
AD-3001180-02
8 9
10
11 12
9 Maintenance
7684359 - v.11 - 13122021 53
9.4.7 Checking the non-return valve
1. Disconnect the two fan plugs on the front and rear.
2. Remove the screwed-on plug from the gas control valve.
3. Remove the ignition electrode plug from the ignition transformer.
4. Unscrew the nut of the gas valve unit.
5. Remove the air inlet pipe from the venturi.
6. Unscrew the two fan nuts.
7. Remove the fan together with the gas control valve.
8. Inspect the non-return valve and replace it in the event of a defect or
damage, or if the maintenance kit contains a non-return valve.
9. Reassemble in the reverse order.
Caution
Remember to reconnect the fan plugs.
Tighten the nut on the gas valve unit with a torque of 27.5 N⋅m.
Tighten the two fan nuts with a torque of 3.8 N⋅m.
9.5 Finalising work
1. Fit all removed parts in the reverse order, but do not close the casing
yet.
Caution
During inspection and maintenance operations, always replace all
gaskets on the parts removed.
2. Fill the siphon with water.
3. Put the siphon back in place.
4. Carefully open all system and supply valves which were closed to
carry out the maintenance.
5. Fill the central heating system with water if necessary.
6. Vent the central heating system.
7. Top up with more water if necessary.
8. Check the tightness of the gas and water connections.
9. Put the boiler back into operation.
10. Carry out an auto-detect when a control board has been replaced or
removed from the boiler.
11. Set the boiler to full load and carry out a gas leak detection and a
thorough visual check.
12. Set the boiler to normal operation.
Fig.64 Disconnecting the fan
AD-3001178-02
1
2
3
Fig.65 Removing the gas and air supply
pipes
AD-3001971-01
4
5
Fig.66 Checking the non-return valve
AD-3001181-02
2x
6
8
7
9 Maintenance
54 7684359 - v.11 - 13122021
13. Close the casing.
9.6 Disposal and recycling
Important
Removal and disposal of the boiler must be carried out by a
qualified person in accordance with local and national regulations.
To remove the boiler, proceed as follows:
1. Cut the power supply to the boiler.
2. Shut off the gas supply.
3. Shut off the water supply.
4. Drain the system.
5. Remove the siphon.
6. Remove the air supply/flue gas outlet pipes.
7. Disconnect all pipes on the boiler.
8. Remove the boiler.
10 Troubleshooting
10.1 Error codes
The Quinta Ace is fitted with an electronic regulation and control unit. The
heart of the control is a e-Smart microprocessor, which controls and also
protects. In the event of an error, a corresponding code is displayed.
Tab.48 Error codes are displayed at three different levels
Code Type Description
A .00.00 (1) Warning The controls continue to operate, but the cause of the warning must be investigated. A
warning can change into a blocking or lock-out.
H .00.00 (1) Blocking The controls will stop normal operation, and will check with set intervals if the cause of
the blocking still exists.(2) Normal operation will resume when the cause of the blocking
has been rectified. A blocking can become a lock-out.
E .00.00 (1) Lock out The controls will stop normal operation. The cause of the lock-out must be rectified and
the controls must be reset manually.
(1) The first letter indicates the type of error.
(2) For some blocking errors, this checking interval is ten minutes. In those cases, it may seem that the controls do not start automatically.
Wait ten minutes before resetting.
The meaning of the code can be found in the various error code tables.
Important
The error code is needed to find the cause of the error quickly and
correctly and for any support from Remeha.
10.1.1 Display of error codes
When an error occurs in the installation, the control panel will show the
following:
Fig.67
MW-3000179-03
10 Troubleshooting
7684359 - v.11 - 13122021 55
1 The display will show a corresponding code and message.
2 The status LED of the control panel will show:
Continuous green = Normal operation
Flashing green = Warning
Continuous red = Blocking
Flashing red = Lock out
When an error occurs, proceed as follows:
1. Press and hold the button to reset the appliance.
The appliance starts up again.
2. If the error code reappears, correct the problem by following the
instructions in the error code tables.
Important
Only qualified professionals are authorised to work on the
appliance and system.
The error code remains visible until the problem is solved.
3. Note the error code when the problem cannot be solved and contact
your installer.
10.1.2 Warning
Tab.49 Warning codes
Code Display text Description Solution
A.00.34 TOutside Missing Outside temperature sensor was ex
pected but not detected
Outdoor sensor not detected:
Outdoor sensor is not connected: Connect the
sensor
Outdoor sensor is not connected correctly:
Connect the sensor correctly
A.00.42 WaterPressureMissing Water pressure sensor was expec
ted but not detected
Water pressure sensor not detected
Water pressure sensor is not connected: con
nect the sensor
Water pressure sensor is not connected cor
rectly: connect the sensor correctly
A.01.23 Poor Combustion Poor combustion Configuration error: No flame during operation:
No ionisation current:
Purge the gas supply to remove air.
Check whether the gas tap is properly open.
Checking the gas supply pressure.
Check the operation and setting of the gas
valve unit.
Check that the air inlet and flue gas dis
charge flues are not blocked.
Check that there is no recirculation of flue
gases.
A.02.06 Water Press Warning Water Pressure Warning active Water pressure warning:
Water pressure too low; check the water pres
sure
A.02.18 OBD Error Object Dictionary Error Configuration error:
Reset CN1 and CN2
See
The data plate for the CN1 and CN2
values.
Fig.68 Error code display on HMI T-control
AD-3001379-01
Error Code: A.00.00
..... ... ....... .... .. ..... ....... .... ..... .......
i
........ .......
Home Screen22/02/2018 11:20
20/02/2018 16:51
.......... ......... .... ............ ........... ... ..... ....
...... ..... ......... ... ....... .......
.......... .........
... .........
1
2
10 Troubleshooting
56 7684359 - v.11 - 13122021
Code Display text Description Solution
A.02.33 AF top comm err Auto filling top communication has
exceeded feedback time
The maximum time for refilling the system auto
matically has been exceeded:
No or low water pressure in the supply line:
check that the main water valve is fully open.
Water leakage from the boiler or system: check
the system for leaks.
Check that the maximum time for refilling is
suitable for the system: Check parame
ter AP069.
Check that the maximum water pressure for re
filling is suitable for this system: Check param
eter AP070.
Important
The pressure difference between the
minimum (parameter AP006) and
maximum (parameter AP070) water
pressure must be high enough to pre
vent there being too short a time be
tween two filling attempts.
The valve on the automatic (re)filling unit is
faulty: Replace the unit.
A.02.34 AF min inter err Auto filling minimum interval time
has not been reached between two
requests
The system must be refilled too quickly by the au
tomatic (re)filling unit:
Water leakage from the boiler or system: check
the system for leaks.
Latest refill ended just above the minimum wa
ter pressure because it was interrupted by the
user, or because the water pressure in the sup
ply line was (temporarily) too low.
A.02.36 Funct device lost Functional device has been discon
nected
SCB not found:
Bad connection: check the wiring and connec
tors
Faulty SCB: Replace SCB
A.02.37 Uncritic device lost Uncritical device has been discon
nected
SCB not found:
Bad connection: check the wiring and connec
tors
Faulty SCB: Replace SCB
A.02.45 Full Can Conn Matrix Full Can Connection Matrix SCB not found:
Carry out an auto-detect
A.02.46 Full Can Device Adm Full Can Device Administration SCB not found:
Carry out an auto-detect
A.02.48 Funct Gr Conf Fault Function Group Configuration Fault SCB not found:
Carry out an auto-detect
A.02.49 Failed Init Node Failed Initialising Node SCB not found:
Carry out an auto-detect
A.02.55 Inval or miss SerNR Invalid or missing device serial num
ber
Contact your supplier.
A.02.69 Fair mode active Fair mode active Contact your supplier.
A.02.76 Memory full The reserved space in memory for
custom parameters value is full. No
more user changed possible
Configuration error:
Reset CN1 and CN2
Faulty CSU: Replace CSU
Replace the CU-GH
10 Troubleshooting
7684359 - v.11 - 13122021 57
Code Display text Description Solution
A.02.80 Missing Cascade Ctrl Missing Cascade controller Cascade controller not found:
Reconnect the cascade master
Carry out an auto-detect
A.08.02 Shower Time Elapsed The time reserved for the shower
has elapsed
Adjust parameter DP357 to the desired shower
time.
10.1.3 Blocking
Tab.50 Blocking codes
Code Display text Description Solution
H.00.81 RoomTempMissing Room Temperature sensor was ex
pected but not detected
Room temperature sensor not detected:
Room temperature sensor is not connected:
Connect the sensor
Room temperature sensor is not connected
correctly: Connect the sensor correctly
H.01.00 Comm Error Communication Error occured Communication error with the security kernel:
Restart the boiler
Replace the CU-GH
H.01.05 Max Delta TF-TR Maximum difference between flow
temperature and return temperature
Maximum difference between the flow and return
temperature exceeded:
No flow or insufficient flow:
Check the flow (direction, pump, valves)
Check the water pressure
Check the cleanliness of the heat exchanger
Sensor error:
Check that the sensors are operating correct
ly
Check that the sensor has been fitted proper
ly
H.01.08 CH Temp Grad. Level3 Maximum CH temperature gradient
level3 exceeded
Maximum heat exchanger temperature increase
has been exceeded:
No flow or insufficient flow:
Check the circulation (direction, pump,
valves)
Check the water pressure
Check the cleanliness of the heat exchanger
Check that the central heating system has
been correctly vented to remove air
Sensor error:
Check that the sensors are operating correct
ly
Check that the sensor has been fitted proper
ly
H.01.09 Gas Pressure Switch Gas Pressure Switch Gas pressure too low:
No flow or insufficient flow:
Make sure that the gas valve is fully opened
Check the gas supply pressure
If a gas filter is present: Make sure that the
filter is clean
Wrong setting on the gas pressure switch:
Make sure that the switch has been fitted
properly
Replace the switch if necessary
10 Troubleshooting
58 7684359 - v.11 - 13122021
Code Display text Description Solution
H.01.14 Max Tflow Flow temperature has exceeded the
maximum operating value
Flow temperature sensor above normal range:
Bad connection: check the wiring and connec
tors
No flow or insufficient flow:
Check the circulation (direction, pump,
valves)
Check the water pressure
Check the cleanliness of the heat exchanger
H.01.15 Max Tflue Gas Flue gas temperature has exceeded
the maximum operating value
Maximum flue gas temperature exceeded:
Check the flue gas outlet system
Check the heat exchanger to ensure that the
flue gas side is not clogged
Faulty sensor: replace the sensor
H.01.21 Dhw Temp GradLevel3 Maximum Dhw Temperature Gradi
ent Level3 Exceeded
The flow temperature has risen too fast:
Check the flow (direction, pump, valves)
Check that the pump is operating correctly
H.02.00 Reset In Progress Reset In Progress Reset procedure active:
No action
H.02.02 Wait Config Number Waiting For Configuration Number Configuration error or unknown configuration
number:
Reset CN1 and CN2
H.02.03 Conf Error Configuration Error Configuration error or unknown configuration
number:
Reset CN1 and CN2
H.02.04 Parameter Error Parameter Error Factory settings incorrect:
Parameters are not correct:
Restart the boiler
Reset CN1 and CN2
Replace the CU-GH PCB
H.02.05 CSU CU mismatch CSU does not match CU type Configuration error:
Reset CN1 and CN2
H.02.09 Partial block Partial blocking of the device recog
nized
Blocking input active or frost protection active:
External cause: remove external cause
Wrong parameter set: check the parameters
Bad connection: check the connection
H.02.10 Full Block Full blocking of the device recog
nized
Blocking input is active (without frost protection):
External cause: remove external cause
Wrong parameter set: check the parameters
Bad connection: check the connection
H.02.12 Release Signal Release Signal input of the Control
Unit from device external environ
ment
Waiting time release signal has elapsed:
External cause: remove external cause
Wrong parameter set: check the parameters
Bad connection: check the connection
H.02.31 AF needed Device requires Auto filling of the
water system due to low pressure
Refill the central heating system using the auto
matic (re)filling unit.
H.02.38 No water hardness No hardness of water -
H.02.70 HRU test error External heat recovery unit test
failed
Heat recovery unit non-return valve check failed:
Check the external heat recovery unit non-re
turn valve.
H.03.00 Parameter Error Safety parameters level 2, 3, 4 are
not correct or missing
Parameter error: security kernel
Restart the boiler
Replace the CU-GH
H.03.01 CU to GVC data error No valid data from CU to GVC re
ceived
Communication error with the CU-GH:
Restart the boiler
10 Troubleshooting
7684359 - v.11 - 13122021 59
Code Display text Description Solution
H.03.02 Flame loss detected Measured ionisation current is below
limit
No flame during operation:
No ionisation current:
Vent the gas supply to remove air
Check that the gas valve is fully opened
Check the gas supply pressure
Check the operation and setting of the gas
valve unit
Check that the air supply inlet and flue gas
outlet are not blocked
Check that there is no recirculation of flue
gases
H.03.05 Internal blocking Gas Valve Control internal blocking
occured
Security kernel error:
Restart the boiler
Replace the CU-GH
H.03.17 Safety check Periodically safety check ongoing Restart the boiler
Replace the CU-GH
10.1.4 Locking
Tab.51 Locking codes
Code Display text Description Solution
E.00.04 TReturn Open Return temperature sensor is either
removed or measures a temperature
below range
Return temperature sensor open:
Bad connection: check the wiring and connec
tors
Incorrectly fitted sensor: check that the sensor
has been correctly fitted
Faulty sensor: replace the sensor
E.00.05 TReturn Closed Return temperature sensor is either
shorted or measures a temperature
above range
Return temperature sensor short-circuited:
Bad connection: check the wiring and connec
tors
Incorrectly fitted sensor: check that the sensor
has been correctly fitted
Faulty sensor: replace the sensor
E.00.06 TReturn Missing Return temperature sensor was ex
pected but not detected
No connection to temperature return sensor:
Bad connection: check the wiring and connec
tors.
Faulty sensor: replace the sensor
E.00.07 dTReturn Too High Return temperature difference is too
large
Difference between the flow and return tempera
tures too great:
No circulation:
Vent the central heating system to remove
air
Check the water pressure
If present: check the boiler type parameter
setting
Check the circulation (direction, pump,
valves)
Check that the heating pump is operating
correctly
Check the cleanliness of the heat exchanger
Sensor not connected or incorrectly connected:
Check that the sensors are operating correct
ly
Check that the sensor has been fitted proper
ly
Faulty sensor: replace the sensor if necessary
10 Troubleshooting
60 7684359 - v.11 - 13122021
Code Display text Description Solution
E.00.16 DHW sensor Open Domestic Hot Water tank tempera
ture sensor is either removed or
measures a temperature below
range
Calorifier sensor open:
Bad connection: check the wiring and connec
tors
Faulty sensor: replace the sensor
E.00.17 DHW sensor Closed Domestic Hot Water tank tempera
ture sensor is either shorted or
measures a temperature above
range
Calorifier sensor short-circuited:
Bad connection: check the wiring and connec
tors
Faulty sensor: replace the sensor
E.00.44 TcombiDhwOutOpen Domestic hot water outlet tempera
ture sensor is either removed or
measures a temperature below
range
DHW temperature sensor open:
Bad connection: check the wiring and connec
tors
Faulty sensor: replace the sensor
E.00.45 DHWoutSens shorted Domestic hot water outlet tempera
ture sensor is either shorted or
measures a temperature above
range
DHW temperature sensor short-circuited:
Bad connection: check the wiring and connec
tors
Faulty sensor: replace the sensor
E.01.04 5x Flame Loss Error 5x Error of unintended Flame Loss
occurance
Flame loss occurs 5 times:
Vent the gas supply to remove air
Check that the gas valve is fully opened
Check the gas supply pressure
Check the operation and setting of the gas
valve unit
Check that the air supply inlet and flue gas out
let are not blocked
Check that there is no recirculation of flue
gases
E.01.11 Fan Out Of Range Fan speed has exceeded normal op
erating range
Fan fault:
Bad connection: check the wiring and connec
tors.
Faulty fan: replace the fan
Fan operates when it should not be operating:
check for excessive chimney draught
E.01.12 Return Higher Flow Return tempearture has a higher
temperature value than the flow tem
perature
Flow and return reversed:
Bad connection: check the wiring and connec
tors
Water circulation in wrong direction: check the
circulation (direction, pump, valves)
Incorrectly fitted sensor: check that the sensor
has been correctly fitted
Malfunctioning sensor: check the Ohmic value
of the sensor
Faulty sensor: replace the sensor
E.01.24 Combustion Error Several combustion errors occurs
with 24 hours
Low ionisation current:
Vent the gas supply to remove air.
Check that the gas valve is fully opened.
Check the gas supply pressure.
Check the operation and setting of the gas
valve unit.
Check that the air supply inlet and flue gas out
let are not blocked.
Check that there is no recirculation of flue
gases.
E.02.13 Blocking Input Blocking Input of the Control Unit
from device external environment
Blocking input is active:
External cause: remove external cause
Wrong parameter set: check the parameters
10 Troubleshooting
7684359 - v.11 - 13122021 61
Code Display text Description Solution
E.02.15 Ext CSU Timeout External CSU Timeout CSU time out:
Bad connection: check the wiring and connec
tors
Faulty CSU: Replace CSU
E.02.17 GVC CommTimeout Gas Valve Control unit communica
tion has exceeded feedback time
Communication error with the security kernel:
Restart the boiler
Replace the CU-GH
E.02.32 AF comm err Auto filling installation communica
tion has exceeded feedback time
Refilling the central heating system takes too
long:
Check the system for leaks.
Check the water pressure in the system.
Check that the inlet gas valve is fully open.
Check that the main water valve is fully open.
Check the operation of the pressure sensor.
Check the operation of the safety valve.
E.02.35 Safety device lost Safety critical device has been dis
connected
Communication fault
Carry out an auto-detect
E.02.39 AF low presure rise No sufficient rise of pressure after
autofilling
The water pressure in the system has not risen
sufficiently during the automatic filling procedure:
Check the system for leaks.
Check the water pressure in the system.
Check that the inlet gas valve is fully open.
Check that the main water valve is fully open.
Check the operation of the pressure sensor.
Check the operation of the safety valve.
E.02.47 Failed Conn Funct Gr Failed Connecting Function Groups Function group not found:
Carry out an auto-detect
Restart the boiler
Replace the CU-GH
E.04.00 Parameter error Safety parameters Level 5 are not
correct or missing
Replace the CU-GH.
E.04.01 TFlow Closed Flow temperature sensor is either
shorted or measuring a temperature
above range
Flow temperature sensor short circuited:
Bad connection: check the wiring and connec
tors
Incorrectly fitted sensor: check that the sensor
has been correctly fitted
Faulty sensor: replace the sensor
E.04.02 TFlow Open Flow temperature sensor is either
removed or measuring a tempera
ture below range
Flow temperature sensor open:
Bad connection: check the wiring and connec
tors
Faulty sensor: replace the sensor
E.04.03 Max Flow temp Measured flow temperature above
savety limit
No flow or insufficient flow:
Check the circulation (direction, pump, valves)
Check the water pressure
Check the cleanliness of the heat exchanger
E.04.04 TFlue Closed Flue temperature sensor is either
shorted or measuring a temperature
above range
Flue gas temperature sensor short-circuited:
Bad connection: check the wiring and connec
tors
Incorrectly fitted sensor: check that the sensor
has been correctly fitted
Faulty sensor: replace the sensor
E.04.05 TFlue Open Flue temperature sensor is either re
moved or measuring a temperature
below range
Flue gas temperature sensor open:
Bad connection: check the wiring and connec
tors
Incorrectly fitted sensor: check that the sensor
has been correctly fitted
Faulty sensor: replace the sensor
10 Troubleshooting
62 7684359 - v.11 - 13122021
Code Display text Description Solution
E.04.06 Max Flue temp Measured flue temperature above
limit
-
E.04.07 TFlow Sensor Deviation in flow sensor 1 and flow
sensor 2 detected
Flow temperature sensor deviation:
Bad connection: check the connection
Faulty sensor: replace the sensor
E.04.08 Safety input Safety input is open Air pressure differential switch activated:
Bad connection: check the wiring and connec
tors
Pressure in flue gas duct is or was too high:
Non-return valve does not open
Siphon blocked or empty
Check that the air supply inlet and flue gas
outlet are not blocked
Check the cleanliness of the heat exchanger
E.04.09 TFlue Sensor Deviation in flue sensor 1 and flue
sensor 2 detected
Flue gas temperature sensor deviation:
Bad connection: check the connection
Faulty sensor: replace the sensor
E.04.10 Unsuccessful start 5 Unsuccessful burners starts detec
ted
Five failed burner starts:
No ignition spark:
Check the wiring between the CU-GH and
the ignition transformer
Check the ionisation/ignition electrode
Check breakdown to earth
Check the condition of the burner cover
Check the earthing
Replace the CU-GH
Ignition spark but no flame:
Vent the gas pipes to remove air
Check that the air supply inlet and flue gas
outlet are not blocked
Check that the gas valve is fully opened
Check the gas supply pressure
Check the operation and setting of the gas
valve unit
Check the wiring on the gas valve unit
Replace the CU-GH
Flame present, but ionisation has failed or is in
adequate:
Check that the gas valve is fully opened
Check the gas supply pressure
Check the ionisation/ignition electrode
Check the earthing
Check the wiring on the ionisation/ignition
electrode.
E.04.11 VPS VPS Gas Valve proving failed Gas leakage control fault:
Bad connection: check the wiring and connec
tors
Gas leakage control VPS faulty: Replace the
valve proving system (VPS)
Gas valve unit faulty: Replace the gas valve
unit
E.04.12 False flame False flame detected before burner
start
False flame signal:
The burner remains very hot: Set the O2
Ionisation current measured but no flame
should be present: check the ionisation/ignition
electrode
Faulty gas valve: replace the gas valve
Faulty ignition transformer: replace the ignition
transformer
10 Troubleshooting
7684359 - v.11 - 13122021 63
Code Display text Description Solution
E.04.13 Fan Fan speed has exceeded normal op
erating range
Fan fault:
Bad connection: check the wiring and connec
tors.
Fan operates when it should not be operating:
check for excessive chimney draught
Faulty fan: replace the fan
E.04.15 FlueGas Pipe Blocked The flue gas pipe is blocked Flue gas outlet is blocked:
Check that the flue gas outlet is not blocked
Restart the boiler
E.04.17 GasValve Driver Err. The driver for the gas valve is bro
ken
Gas valve unit fault:
Bad connection: check the wiring and connec
tors
Faulty gas valve unit: Replace the gas valve
unit
E.04.23 Internal Error Gas Valve Control internal locking Restart the boiler
Replace the CU-GH
E.04.250 Internal error Gas valve relay error detected Internal error:
Replace the PCB.
10.2 Error history
The control panel has an error history that stores the last 32 errors.
Specific details are stored for each error, for example:
Status
Sub-status
Flow temperature
Return temperature
These details and others can contribute to the error solution.
See also
Additional documentation, page 8
10.2.1 Reading out and clearing the error history
You can read out the errors on the control panel. The error history can
also be cleared.
> Error History
Use the rotary knob to navigate.
Use the button to confirm your selection.
1. Press the button.
2. Select Error History.
Enable installer access if Error History is not available.
2.1. Select Enable installer access.
2.2. Use code 0012.
A list up to 32 most recent errors is displayed with:
The error code.
A short description.
The date.
10 Troubleshooting
64 7684359 - v.11 - 13122021
3. Select the error code you want to investigate.
The display shows an explanation of the error code and several
details of the appliance when the error occurred.
4. To clear the error memory, press and hold the button.
11 User instructions
11.1 Start-up
Start the boiler up as follows:
1. Open the boiler gas tap.
2. Power up the boiler.
3. The boiler runs through an automatic venting program lasting approx.
3 minutes.
4. Check the water pressure of the central heating system shown on the
control panel display. If necessary, top up the central heating system.
The current operating condition of the boiler is shown on the display.
11.2 Accessing the user level menus
The tiles on the home screen provide quick access for the user to the
corresponding menus.
1. Use the rotary knob to select the required menu.
2. Press the button to confirm the selection.
The available settings of this selected menu appear in the display.
3. Use the rotary knob to select the desired setting.
4. Press the button to confirm the selection.
All options for change will appear in the display (if a setting cannot
be changed, Cannot edit read-only datapoint will appear in the
display).
5. Use the rotary knob to change the setting.
6. Press the button to confirm the selection.
7. Use the rotary knob to select the next setting or press the button to
return to the home screen.
11.3 Home screen
The tiles on the home screen provide quick access to the corresponding
menus. Use the rotary knob to navigate to the menu of your choice and
press the button to confirm the selection. All options for change will
appear in the display (Cannot edit read-only datapoint will appear in the
display if a setting cannot be changed).
Fig.69 Error details
AD-3001381-01
20/02/2018 16:51
.......... ......... .... ............ ........... ... ..... ....
...... ..... ......... ... ....... .......
Error Code: A.00.00
..... ... .......:
....... .... .......:
....... ...... .....:
..... .. .......:
..... ........
....... ...
.......
..... .........
........ .......
...... .....22/02/2018 11:20
Fig.70 Menu selection
AD-3001387-01
Not set
Home Screen
22/02/2018 11:20
... ...
........ .......
........ .......
......
Fig.71 Confirm menu selection
AD-3001388-01
... ...
........ .......
........ .......
......
Not set
Home Screen
22/02/2018 11:20
11 User instructions
7684359 - v.11 - 13122021 65
Tab.52 Selectable tiles for the user
Tile Menu Function
Information menu. Read out various current values.
Error indicator. Read out details about the current error.
With some errors the icon will appear with installer contact details (when
filled in).
Holiday Mode. Set the start and end date of your holiday to lower the room and domestic hot
water temperatures of all zones.
, ,
,
Operating mode. Change whether your appliance is set to heating, cooling, both or off.
Gas boiler indicator. Read out burning details of the boiler and switch the heating function of the
boiler on or off.
Water pressure indicator. Shows the water pressure. Top up the installation when the water pressure is
too low.
, ,
, ,
, ,
Heating circuit set-up. Configure the settings per heating circuit.
DHW setup. Configure the domestic hot water temperatures.
Outdoor sensor setup. Configure the temperature regulation using the outdoor sensor.
11.4 Activating holiday programs for all zones
If you go on holiday, the room temperature and domestic hot water
temperature can be reduced to save energy. With the following procedure
you can activate the holiday mode for all zones and domestic hot water
temperature.
Use the rotary knob to navigate.
Use the button to confirm your selection.
1. Select the tile [ ].
2. Select Start date holiday.
3. Configure the start date.
4. Select End date holiday.
The day after the start date of your holiday is displayed.
5. Configure the end date.
6. Select Wished room zone temperature on holiday period.
7. Configure the temperature.
You can reset or cancel the holiday program by selecting Reset in the
holiday mode menu.
11.5 Heating circuit configuration
For every heating circuit there is a quick user settings menu available.
Select the heating circuit you want to configure by selecting the tile [ ],
[ ], [ ], [ ], [ ], [ ] or [ ]
Tab.53 Menu to configure domestic hot water
Menu Function
Set heating temperatures Set the temperatures for the timer program.
Operating mode Set the operating mode.
Time programs heating Set and configure the time programs used when in operating mode
Scheduling.
Zone configuration Configure the settings of the zone circuit.
11 User instructions
66 7684359 - v.11 - 13122021
Tab.54 Extended menu to configure a heating circuit Zone configuration
Menu Function
Short temperature change Change the room temperature temporarily, if required.
OperatingZoneMode Select the heating operating mode: Scheduling, Manual.
Manu ZoneRoomTempSet Set the room temperature manually to a fixed setting.
Holiday Mode Set the start and end date of your holiday and the reduced temperature for
this zone.
Zone friendly Name Create or change the name of the heating circuit.
Icon display zone Select the icon of the heating circuit.
11.6 Changing the room temperature of a zone
11.6.1 Definition of zone
Zone is the term given to the different hydraulic circuits CIRCA, CIRCB
and so on. It designates several areas of a building served by the same
circuit.
Tab.55 Example of two zones
Zone Factory name
1 Zone 1 CIRCA
2 Zone 2 CIRCB
11.6.2 Changing the name and symbol of a zone
The zones have a factory set symbol and name. Depending on your
appliance you can change the symbol and name for the zones, not all
appliances and zone types will support changing the symbol and name.
Select zone > Zone configuration > Zone friendly Name or Icon
display zone
Installer access enabled: Select zone > Zone friendly Name or
Icon display zone
Use the rotary knob to navigate.
Use the button to confirm your selection.
1. Select the tile of the zone you want to change.
2. Select Zone configuration
This menu will not appear if you have installer access enabled,
continue to the next step.
3. Select Zone friendly Name
A keyboard with letters, numbers and symbols (characters) is
shown.
4. Change the name of the zone (20 characters maximum):
Fig.72 Two zones
AD-3001404-01
1
2
11 User instructions
7684359 - v.11 - 13122021 67
4.1. Use the top row to change between capitalization, numbers,
symbols or special characters.
4.2. Select a character or action.
4.3. Select to delete a character.
4.4. Select to add a space.
4.5. Select to finish changing the zone name.
5. Select Icon display zone.
All available icons appear in the display.
6. Select the desired icon of the zone.
11.6.3 Changing the operating mode of a zone
To regulate the room temperature of the different areas of the house, you
can choose from 5 operating modes:
Select zone > Operating mode
Use the rotary knob to navigate.
Use the button to confirm your selection.
1. Select the tile of the zone you want to change.
2. Select Operating mode
3. Select the desired operating mode:
Tab.56 Operating modes
Icon Mode Description
Scheduling The room temperature is controlled by a timer program
Manual The room temperature is set to a fixed setting
Short temperature change The room temperature is changed temporarily
Holiday The room temperature is reduced during your holiday to save energy
Antifrost Protect the boiler and installation from freezing in winter
11.6.4 Timer program to control the room temperature
Creating a timer program
A timer program allows you to vary the room temperature per hour and per
day. The room temperature is linked to the activity of the timer program.
You can create up to three timer programs per zone. For example, you
can create a program for a week with normal working hours and a
program for a week when you are at home most of the time.
Select zone > Time programs heating
Use the rotary knob to navigate.
Use the button to confirm your selection.
1. Select the tile of the zone you want to change.
2. Select Time programs heating.
Fig.73 Letter selection
AD-3001382-01
: .... ...... ........ ..............
11:20
xs t u v w
rm n o p q
fab c d e
lg h i j k
y z
ÀÁÄabc ABC 123 !@# áäà
...
Fig.74 Finish changing the zone name
AD-3001383-01
: .... ...... ........ ..............
11:20
xs t u v w
rm n o p q
fa b c d e
lg h i j k
y z
ÀÁÄabc ABC 123 !@# áäà
...
11 User instructions
68 7684359 - v.11 - 13122021
3. Select the timer program you want to modify: Schedule 1, Schedule 2
or Schedule 3.
Activities scheduled for Monday are displayed. The last scheduled
activity of a day is active until the first activity of the next day. At
initial start-up, all weekdays have two standard activities; Home
starting at 6:00 and Sleep starting at 22:00.
4. Select the weekday you want to modify.
A Weekday
B Overview of scheduled activities
C List of actions
5. You can perform the following actions:
5.1. Select scheduled activity to edit the time this activity will start,
change the temperature or to delete the selected activity.
5.2. Add time and Activity to add a new activity to the scheduled
activities.
5.3. Copy to other day to copy the scheduled activities of the
weekday to other days.
The activities including the configured time and temperature
will be copied to the selected days.
5.4. Set activity temperatures to change the temperature.
Definition of activity
Activity is the term used when programming time slots in a timer program.
The timer program sets the room temperature for different activities during
the day. A temperature setpoint is associated with each activity. The last
activity of the day is valid until the first activity of the next day.
Fig.76 Activities of a timer program
AD-3001403-01
0
15
20
25
T
0:00 2:00 4:00 6:00 8:00 10:00 12:00
h
14:00 16:00 18:00 20:00 22:00 0:00
1
2
3
4
5
Tab.57 Example of activities
Start of the activity Activity Temperature setpoint
1 6:30 Morning 20 °C
2 9:00 Away 19 °C
3 17:00 Home 20 °C
4 20:00 Evening 22 °C
5 23:00 Sleep 16 °C
Changing the name of an activity
You can change the names of the activities in the timer program.
> System Settings > Set Heating Activity Names
Use the rotary knob to navigate.
Use the button to confirm your selection.
1. Press the button.
2. Select System Settings .
Fig.75 Weekday
AD-3001384-01
........ .......
..... ... ....... ....
....... ...........
.... ...... ........ ..............
11:20
..:.. ........ ....
..:.. ........ ....
................ ..............
A
B
C
11 User instructions
7684359 - v.11 - 13122021 69
3. Select Set Heating Activity Names.
A list of 6 activities and their standard names is shown:
Activity 1 Sleep
Activity 2 Home
Activity 3 Away
Activity 4 Morning
Activity 5 Evening
Activity 6 Custom
4. Select an activity.
A keyboard with letters, numbers and symbols is shown.
5. Change the name of the activity (20 characters maximum):
5.1. Use the top row to change between capitalization, numbers,
symbols or special characters.
5.2. Select a letter, number or action.
5.3. Select to delete a letter, number or symbol.
5.4. Select to add a space.
5.5. Select to finish changing the activity name.
Activating a timer program
In order to use a timer program, it is necessary to activate the operating
mode Scheduling. This activation is done separately for each zone.
Select zone > Operating mode > Scheduling
Use the rotary knob to navigate.
Use the button to confirm your selection.
1. Select the tile of the zone you want to change.
2. Select Operating mode.
3. Select Scheduling.
4. Select the timer program Schedule 1, Schedule 2 or Schedule 3.
11.6.5 Changing the heating activity temperatures
You can change the heating temperatures of each activity.
Select zone > Set heating temperatures
Use the rotary knob to navigate.
Use the button to confirm your selection.
1. Select the tile of the zone you want to change.
2. Select Set heating temperatures.
A list of 6 activities and their temperatures is shown.
3. Select an activity.
4. Set the heating activity temperature.
Fig.77 Letter selection
AD-3001382-01
: .... ...... ........ ..............
11:20
xs t u v w
rm n o p q
fab c d e
lg h i j k
y z
ÀÁÄabc ABC 123 !@# áäà
...
Fig.78 Confirm sign
AD-3001383-01
: .... ...... ........ ..............
11:20
xs t u v w
rm n o p q
fa b c d e
lg h i j k
y z
ÀÁÄabc ABC 123 !@# áäà
...
11 User instructions
70 7684359 - v.11 - 13122021
11.6.6 Changing the room temperature temporarily
Regardless of the operating mode selected for a zone, it is possible to
change the room temperature for a short period. After this period has
elapsed, the selected operating mode resumes.
Select zone > Operating mode > Short temperature change
Use the rotary knob to navigate.
Use the button to confirm your selection.
The room temperature can only be adjusted in this way if a room
temperature sensor/thermostat is installed.
1. Select the tile of the zone you want to change.
2. Select Operating mode
3. Select Short temperature change.
4. Set the duration in hours and minutes.
5. Set the temporary room temperature.
11.7 Changing the domestic hot water temperature
11.7.1 Domestic hot water configuration
Configure the domestic hot water settings by selecting the tile [ ]
Tab.58 Menu to configure domestic hot water
Menu Function
Domestic Hot Water Setpoints Set the DHW temperatures for the timer program.
Operating mode Set the operating mode.
Time programs Set and configure the time programs used when in operating mode
Scheduling.
DHW configuration Configure the settings of the DHW circuit.
Tab.59 Extended menu to configure the domestic hot water circuit DHW configuration
Menu Function
Hot water boost Change the DHW temperature temporarily.
Holiday Mode Set the start and end date of your holiday.
DHW mode Select the DHW operating mode: Scheduling, Manual.
11.7.2 Changing the domestic hot water operating mode
You can change the operating mode for hot water production. You can
choose from 5 operating modes.
> Operating mode
Use the rotary knob to navigate.
Use the button to confirm your selection.
1. Select the tile [ ].
2. Select Operating mode
This option is not available when installer access is enabled.
11 User instructions
7684359 - v.11 - 13122021 71
3. Select the desired operating mode:
Tab.60 Operating modes
Icon Mode Description
Scheduling The domestic hot water temperature is controlled by a timer program
Manual The domestic hot water temperature is set to a fixed setting
Hot water boost The domestic hot water temperature is increased temporarily
Holiday The domestic hot water temperature is reduced during your holiday to save
energy
Antifrost Protect the appliance and installation from freezing.
11.7.3 Timer program to control the DHW temperature
Creating a timer program
A timer program allows you to vary the domestic hot water temperature
per hour and per day. The hot water temperature is linked to the activity of
the timer program.
> Operating mode
Use the rotary knob to navigate.
Use the button to confirm your selection.
You can create up to three timer programs. For example, you can
create a program for a week with normal working hours and a
programme for a week when you are at home most of the time.
1. Select the tile [ ].
2. Select Time programs.
3. Select the timer program you want to modify: Schedule 1, Schedule 2
or Schedule 3.
Activities scheduled for Monday are displayed. The last scheduled
activity of a day is active until the first activity of the next day. The
scheduled activities are shown. At initial start-up, all weekdays have
two standard activities; Comfort starting at 6:00 and Reduced
starting at 22:00.
4. Select the weekday you want to modify.
AWeekday
BOverview of scheduled activities
CList of actions
5. You can perform the following actions:
5.1. Select scheduled activity to edit the time this activity will start,
change the temperature or to delete the selected activity.
5.2. Add time and Activity to add a new activity to the scheduled
activities.
5.3. Copy to other day to copy the scheduled activities of the
weekday to other days.
5.4. Set activity temperatures to change the temperature.
Activating a DHW timer program
In order to use a DHW timer program, it is necessary to activate the
operating mode Scheduling. This activation is done separately for each
zone.
> Operating mode > Scheduling
Use the rotary knob to navigate.
Use the button to confirm your selection.
1. Select the tile [ ].
2. Select Operating mode.
3. Select Scheduling.
Fig.79 Weekday
AD-3001384-01
........ .......
..... ... ....... ....
....... ...........
.... ...... ........ ..............
11:20
..:.. ........ ....
..:.. ........ ....
................ ..............
A
B
C
11 User instructions
72 7684359 - v.11 - 13122021
4. Select the DHW timer program Schedule 1, Schedule 2 or Schedule
3.
11.7.4 Changing the comfort and reduced hot water temperature
You can change the comfort and reduced hot water temperature for the
timer program.
> Domestic Hot Water Setpoints
Use the rotary knob to navigate.
Use the button to confirm your selection.
1. Select the tile [ ].
2. Select Domestic Hot Water Setpoints.
3. Select the setpoint you want to change:
DHW comfort setpoint: The temperature when the hot water
production is switched on.
DHW reduced setpoint: The temperature when the hot water
production is switched off.
4. Set the desired temperature.
11.7.5 Increasing the domestic hot water temperature temporarily
Regardless of the operating mode selected for domestic hot water
production, it is possible to increase the domestic hot water temperature
for a short period. After this period the hot water temperature decreases to
the Reduced setpoint. This is called a hot water boost.
> Operating mode > Hot water boost
Use the rotary knob to navigate.
Use the button to confirm your selection.
Important
The domestic hot water temperature can only be adjusted in this
way if a domestic hot water sensor is installed.
1. Select the tile [ ].
2. Select Operating mode.
3. Select Hot water boost.
4. Set the duration in hours and minutes.
The temperature is increased to the DHW comfort setpoint for the
duration of the boost.
11.8 Switching the central heating on or off
You can switch off the central heating function to save energy.
When an outdoor sensor is connected to the installation, it's also
possible to use the summer mode function for switching the
central heating on or off.
> CH function on
Use the rotary knob to navigate.
Use the button to confirm your selection.
1. Select the tile [ ].
2. Select CH function on.
11 User instructions
7684359 - v.11 - 13122021 73
3. Select the following setting:
Off to switch off the central heating function.
On to switch on the central heating function.
Caution
Frost protection is not available when the central heating function
is switched off.
11.9 Switching the summer mode on or off
You can use summer mode to switch off the central heating function.
While summer mode is active central heating will be turned off but hot
water remains available.
The summer mode function is only available when an outdoor
sensor is connected to the installation.
> Force summer mode
Use the rotary knob to navigate.
Use the button to confirm your selection.
1. Select the tile [ ].
2. Select Force summer mode.
3. Select the following setting:
On to switch on summer mode.
Off to switch off summer mode.
11.10 Changing the operating mode
You can set the operating mode of your appliance. The modes available
may vary per appliance.
Use the rotary knob to navigate.
Use the button to confirm your selection.
1. Select the tile [ ].
2. You can choose between the following operating modes:
Off Disable the appliance, does not affect hot water production.
Heating (auto) Enable heating.
Forced cooling Enable cooling.
Heating/cooling (auto) Enable both heating and cooling.
The operating mode tile will update to reflect the selected operating
mode.
11.11 Changing the control panel settings
You can change the control panel settings within system settings.
> System Settings
Use the rotary knob to navigate.
Use the button to confirm your selection.
1. Press the button.
2. Select System Settings .
11 User instructions
74 7684359 - v.11 - 13122021
3. Perform one of the operations described in the table below:
Tab.61 Control panel settings
System Settings menu Settings
Set Date and Time Set the current date and time
Select Country and Language Select your country and language
Daylight Saving Time Enable or disable daylight saving time. When enabled daylight saving time will
update the systems internal time to correspond with summer and winter time.
Installer Details Read out the name and phone number of the installer
Set Heating Activity Names Create the names for the activities of the timer program
Set Screen Brightness Adjust the brightness of the screen
Set click sound Enable or disable the click sound of the rotary knob
License Information Read out detailed license information from the device platform application
11.12 Reading the installer's name and phone number
The installer can set his name and phone number in the control panel. You
can read this information when you want to contact the installer.
> System Settings > Installer Details
Use the rotary knob to navigate.
Use the button to confirm your selection.
1. Press the button.
2. Select System Settings
3. Select Installer Details.
The installer’s name and phone number is shown.
11.13 Shut-down
Shut-down the boiler as follows:
1. Turn off the boiler using the on/off switch.
2. Shut off the gas supply.
3. Keep the installation frost-free.
Do not shut-down the boiler if the installation can't be kept frost-free.
11.14 Frost protection
Caution
Drain the boiler and central heating system if you are not going
to use your home or the building for a long time and there is a
chance of frost.
The frost protection does not work if the boiler is out of
operation.
The built-in boiler protection is only activated for the boiler and
not for the system and radiators.
Open the valves of all the radiators connected to the system.
Set the temperature control low, for example to 10°C.
If the temperature of the central heating water in the boiler drops too low,
the built-in boiler protection system is activated. This system works as
follows:
If the water temperature is lower than 7°C, the pump switches on.
If the water temperature is lower than 4°C, the boiler switches on.
If the water temperature is higher than 10℃, the burner shuts down and
the pump continues to run for a short time.
To prevent the system and radiators freezing in frost-sensitive areas (e.g.
a garage), a frost thermostat or, if feasible, an outdoor sensor can be
connected to the boiler.
11 User instructions
7684359 - v.11 - 13122021 75
11.15 Cleaning the casing
1. Clean the outside of the appliance using a damp cloth and a mild
detergent.
12 Technical specifications
12.1 Homologations
12.1.1 Certifications
Tab.62 Certifications
CE identification number PIN 0063CS3928
Class NOx(1) 6
Type of flue gas connection B23P , B33 (2)
C13 , C33 , C53 , C63 , C93
(1) EN 15502–1
(2) When installing a boiler with connection type B23P, B33, the IP rating of the boiler is lowered to IP20.
12.1.2 BREEAM compliance
The Quinta Ace complies with the BREEAM emission requirements. In
order to meet these requirements, some boiler parameter values need to
be changed.
Important
Refer to the chapter for the boiler’s BREEAM settings.
12.1.3 Unit categories
Tab.63 Unit categories
Country Category(1) Gas type Connection pressure
(mbar)
Great Britain II2H3B/P G20 (H gas)
G30/G31 (butane/propane)
20
30-50
(1) This appliance is suitable for category I2H containing up to 20% Hydrogen gas (H2).
12.1.4 Directives
In addition to the legal requirements and guidelines, the supplementary
guidelines in this manual must also be followed.
Supplements or subsequent regulations and guidelines that are valid at
the time of installation shall apply to all regulations and guidelines
specified in this manual.
12.1.5 Factory test
Before leaving the factory, each boiler is optimally set and tested for:
Electrical safety.
Adjustment of O2.
Water tightness.
Gas tightness.
Parameter setting.
12 Technical specifications
76 7684359 - v.11 - 13122021
12.2 Electrical diagram
Fig.80 Electrical diagram
AD-3001177-04
BR
BR
BL
BL
GN/
YW
GN/
YW
2 31
X32
1 32
X33
2 31
24
13 X31
N L
230V, 50Hz
4 132
1 3 42
X1
BR
BL
GN/
YW
1
BL
GN/
YW
BR
X41
1 2 3
2 3
1
BR
BLGN/
YW
3 1
2 3
2
X81
2 1 3
WH
BK
RD
1 3 2
2
BK
BL
GN/
YW
GY
1 23
X51
3 4 1 1 2
GN/
YW
WH
BL
153
3 4
X21/X61
1 2
BL
32
BKBK
BK
11 2
X102
4
4 7 5 8 6 9 123
X105
1 2 3 4
X104 X101
1 2
321
X133
54
CB-03 7 81 2 3 4 5 6
R-Bus Tout
BL RL
1 3 4 52 1 3 4 52 6
1 32 54 1 32 54
321
X134
54
321
X135
54
6 7 8 9 10 11
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
X03
X136 X131
X4 L-Bus
9 10
Tdhw
1 3 4 52
321
X132
54
12
BK
BK
1 2
14
BK
BK
2 3
BK
1
X114
9
X111
BK
BK
BK
BK
4 2 3 1
14
X115
BK
BK
BKBK
1 2 4 5
2 3 6 8 7 10 13 15
1 2 3
X112
1 3
X1151
X4
X3 X13
X11
X6X5 X8
X7 X10
X11
X13
X4
X3
X10
X14
X6
X5
F1
X12
X7
X8
7
1
25
23
22
20
18 19
15
17
16
14
13
10
11
9
6
12
234
24
8
21 5
1Power supply
2On/off switch
3Power supply for SCB-xx control PCBs
4Power supply for IF-01 control PCB
5Interior lighting
6Display
7Connection points for additional SCB-xx control
PCBs
8Service connection
9L-Bus connection for SCB-xx control PCBs
10 Fan supply
11 Standard CB-03 control PCB
12 CU-GH08 control unit
13 Ignition transformer
14 Ionisation/ignition electrode
15 Combined gas valve unit
Connector X6 to X21 for Quinta Ace 30, 45, 55,
65, 90
Connector X6 to X61 for Quinta Ace 115
16 Connection to CB-08 PCB (for 24 V or 230 V three-
way valve)
17 Power supply for pump
18 Return sensor (NTC 10 kΩ/25°C)
19 Flow sensor (NTC 10 kΩ/25°C)
20 Connection point for flue gas sensor (PTC <20Ω/
25°C)
21 Connection point for air pressure differential switch
(remove bridge)
22 Fan control
12 Technical specifications
7684359 - v.11 - 13122021 77
23 Pressure sensor
24 Control for PWM pump
25 Storage information (CSU)
BK Black
BL Blue
BR Brown
GN Green
GY Grey
RD Red
WH White
YW Yellow
12.3 Dimensions and connections
Fig.81 Dimensions
AD-4100113-03
500
100
50
191
500
750
50
130
191
365
839
Tab.64 Connections
Symbol Connection Quinta Ace
30
Quinta Ace
45
Quinta Ace
55
Quinta Ace
65
Quinta Ace
90
Quinta Ace
115
Flue gas outlet Ø 80 mm Ø 80 mm Ø 100 mm Ø 100 mm Ø 100 mm Ø 100 mm
Air supply Ø 125 mm Ø 125 mm Ø 150 mm Ø 150 mm Ø 150 mm Ø 150 mm
Siphon 25 mm 25 mm 25 mm 25 mm 25 mm 25 mm
CH flow 1 ¼" male
thread
1 ¼" male
thread
1 ¼" male
thread
1 ¼" male
thread
1 ¼" male
thread
1 ¼" male
thread
CH return 1 ¼" male
thread
1 ¼" male
thread
1 ¼" male
thread
1 ¼" male
thread
1 ¼" male
thread
1 ¼" male
thread
Gas ¾" male thread ¾" male thread ¾" male thread ¾" male thread ¾" male thread ¾" male thread
12 Technical specifications
78 7684359 - v.11 - 13122021
12.4 Technical data
Tab.65 General
Quinta Ace 30 45 55 65 90 115
Nominal output (Pn)
Central heating operation
(80/60°C)
min-max
(1)
kW 8.0 - 29.8
29.8
8.0 - 40.8
40.8
11.1 -
55.3
55.3
12.0 -
61.5
61.5
14.1 -
84.2
84.2
18.9 -
103.9
103.9
Nominal output (Pnc)
Central heating operation
(50/30°C)
min-max
(1)
kW 9.1 - 30.9
30.9
9.1 - 42.4
42.4
12.3 -
58.6
58.6
13.5 -
65.0
65.0
15.8 -
89.5
89.5
21.2 -
109.7
109.7
Nominal load (Qnh)
Central heating operation (Hi)
min-max
(1)
kW 8.2 - 30.0
30.0
8.2 - 41.2
41.2
11.3 -
56.5
56.5
12.2 -
62.0
62.0
14.6 -
86.0
86.0
19.6 -
107.0
107.0
Nominal load (Qnh)
Central heating operation (Hs)
min-max
(1)
kW 9.1 - 33.3
33.3
9.1 - 45.7
45.7
12.5 -
62.7
62.7
13.6 -
68.8
68.8
16.2 -
95.5
95.5
21.9 -
118.8
118.8
Nominal load (Qnh)
Central heating operation (Hi)
G31 (propane)
min-max
(1)
kW 8.8 - 30.0
30.0
8.8 - 41.2
41.2
12.2 -
56.5
56.5
12.2 -
62.0
62.0
22.1 -
86.0
86.0
21.2 -
107.0
107.0
Nominal load (Qnh)
Central heating operation (Hs)
G31 (propane)
min-max
(1)
kW 9.6 - 32.6
32.6
9.6 - 44.8
44.8
13.3 -
61.5
61.5
13.3 -
67.4
67.4
24.0 -
93.6
93.6
23.1 -
116.4
116.4
Reduced load (QY20h)
Central heating operation (Hi)
min-max
(1)
kW 7.6 - 27.9
27.9
7.6 - 38.3
38.3
10.5 -
52.5
52.5
11.3 -
57.7
57.7
13.9 -
80.0
80.0
18.2 -
99.5
99.5
Reduced load (QY20h)
Central heating operation (Hs)
min-max
(1)
kW 8.5 - 31.0
31.0
8.5 - 42.5
42.5
11.6 -
58.3
58.3
12.6 -
64.0
64.0
15.1 -
88.8
88.8
20.4 -
110.5
110.5
Full load central heating efficien
cy (Pn) (Hi) (80°C/60°C)
% 97.5 97.2 97.8 98.3 97.9 97.1
Full load central heating efficien
cy (Pa) (Hi) (80°C/60°C)
% 99.4 99.1 97.8 99.2 97.9 97.1
Full load central heating efficien
cy (Hi) (50°C/30°C)
% 102.9 102.9 103.8 104.6 104.1 102.5
Central heating efficiency under
part load (Hi)
(Return temperature 60 °C)
% 97.5 97.2 97.8 98.3 96.6 96.5
Part load central heating efficien
cy (Pn) (Hi)
(Return temperature 30 °C)
% 108.5 108.4 108.7 108.9 108.1 108.0
Part load central heating efficien
cy (Pa) (Hi)
(Return temperature 30 °C)
% 110.4 110.6 108.7 110.4 108.1 108.0
Full load central heating efficien
cy (Pn) Hs) (80/60°C)
% 87.8 87.5 88.1 88.5 88.2 87.4
Full load central heating efficien
cy (Pa) (Hs) (80/60°C)
% 89.5 89.2 88.1 89.3 88.2 87.4
Full load central heating efficien
cy (Hs) (50/30°C)
% 92.7 92.7 93.5 94.2 93.7 92.3
Heating efficiency under part
load (Hs)
(Return temperature 60 °C)
% 87.8 87.5 88.1 88.5 87.0 86.9
12 Technical specifications
7684359 - v.11 - 13122021 79
Quinta Ace 30 45 55 65 90 115
Central heating efficiency under
partial load (Pn) (Hs)
(Return temperature 30 °C)
% 97.7 97.6 97.9 98.1 97.3 97.3
Central heating efficiency under
partial load (Pa) (Hs)
(Return temperature 30 °C)
% 99.4 99.6 97.9 99.4 97.3 97.3
(1) Factory setting
Tab.66 Gas and flue gas data
Quinta Ace 30 45 55 65 90 115
Gas test pressure G20 (H gas) min-max mbar 17 - 25 17 - 25 17 - 25 17 - 25 17 - 25 17 - 25
Gas test pressure G31 (propane) min-max mbar 37 - 50 37 - 50 37 - 50 37 - 50 37 - 50 37 - 50
Gas consumption G20 (H gas)(1) min-max m3/h 0.9 - 3.2 0.9 - 4.4 1.2 - 6.0 1.3 - 6.6 1.5 - 9.1 2.1 - 11.3
Gas consumption G31 (propane) min-max m3/h 0.4 - 1.2 0.4 - 1.7 0.5 - 2.3 0.5 - 2.5 0.9 - 3.5 0.9 - 4.4
Gas resistance between boiler
connection point and measure
ment point on the gas valve unit
(measured with G20)
max mbar 0.5 1.0 2.0 2.0 2.5 3.0
NOx annual emission G20
(BREEAM EN15502)
mg/kW
h
24 24 23 23 23 23
NOx annual emission G31
(BREEAM EN15502)
mg/kW
h
22 22 24 22 23 22
BREEAM Credits 2 2 2 2 2 2
Flue gas quantity min-max kg/h 14 - 50 14 - 69 19 - 93 21 - 104 28 - 138 36 - 178
Flue gas temperature min-max °C 30 - 65 30 - 67 30 - 68 30 - 68 30 - 68 30 - 72
Maximum counter pressure Pa 70 150 120 100 160 220
Central heating chimney efficien
cy (Hi)
(80/60°C) at 20°C ambient tem
perature
% 99.4 99.1 97.8 99.2 97.9 97.1
Central heating chimney losses
(Hi)
(80/60°C) at 20°C ambient tem
perature
% 0.6 0.9 2.2 0.8 2.1 2.9
(1) Gas consumption based on lower heating value under standard conditions: T=288.15 K, p=1013.25 mbar.
Tab.67 Central heating circuit data
Quinta Ace 30 45 55 65 90 115
Water content l 4.3 4.3 6.4 6.4 9.4 9.4
Water operating pressure min bar 0.8 0.8 0.8 0.8 0.8 0.8
Water operating pressure (PMS) max bar 4.0 4.0 4.0 4.0 4.0 4.0
Water temperature max °C 110.0 110.0 110.0 110.0 110.0 110.0
Operating temperature max °C 90.0 90.0 90.0 90.0 90.0 90.0
Hydraulic resistance (ΔT=20K) mbar 70 114 130 163 153 250
Casing-related losses ΔT 30°C
ΔT 50°C
W 101
201
101
201
110
232
110
232
123
254
123
254
Tab.68 Electrical data
Quinta Ace 30 45 55 65 90 115
Supply voltage VAC 230 230 230 230 230 230
Power consumption - Full load
central heating(1)
max W 40 75 81 89 114 182
Power consumption - Part load
30% central heating(1)
max W 20 22 29 29 30 36
12 Technical specifications
80 7684359 - v.11 - 13122021
Quinta Ace 30 45 55 65 90 115
Power consumption - Minimum
load central heating (1)
min W 19 20 26 26 26 32
Power consumption - Stand-by
(Psb)(1)
max W 6 6 7 7 7 6
Electrical protection index IP X4D X4D X4D X4D X4D X4D
Fuses (slow) CU-
GH08
A 2.5 2.5 2.5 2.5 2.5 2.5
(1) without pump
Tab.69 Other data
Quinta Ace 30 45 55 65 90 115
Total weight including packaging kg 60.5 60.5 66.5 66.5 76.5 76.5
Minimum mounting weight(1) kg 50 50 56 56 65.2 65.2
Average acoustic level at a dis
tance of one metre from the boil
er
dB(A) 38.3 45.1 46.7 46.7 51.6 51.1
(1) Without front panel.
Tab.70 Technical parameters
Quinta Ace 30 45 55 65 90 115
Condensing boiler Yes Yes Yes Yes Yes Yes
Low-temperature boiler(1) No No No No No No
B1 boiler No No No No No No
Cogeneration space heater No No No No No No
Combination heater No No No No No No
Rated heat output
Prated
kW 30 41 55 62 84 104
Useful heat output at nominal
heat output and high tempera
ture operation(2)
P4
kW 29.8 40.8 55.3 61.5 84.2 103.9
Useful heat output at 30% of
rated heat output and low tem
perature regime(1)
P1
kW 9.9 13.7 18.4 20.5 27.9 34.7
Seasonal space heating energy
efficiency
ƞs
% 94 94 92 94 - -
Useful efficiency at rated heat
output and high temperature
regime(2)
ƞ4
% 89.6 89.3 88.1 89.4 88.2 87.5
Useful efficiency at 30% of rat
ed heat output and low tem
perature regime(1)
ƞ1
% 99.5 99.6 97.9 99.5 97.4 97.3
Auxiliary electricity consumption
Full load
elmax
kW 0.040 0.075 0.100 0.100 0.124 0.184
Part load
elmin
kW 0.020 0.020 0.042 0.029 0.030 0.036
Standby mode
PSB
kW 0.006 0.006 0.007 0.007 0.007 0.006
Other items
Standby heat loss
Pstby
kW 0.101 0.101 0.110 0.110 0.123 0.123
Ignition burner power con
sumption
Pign
kW - - - - - -
Annual energy consumption
QHE
GJ 91 125 173 188 - -
12 Technical specifications
7684359 - v.11 - 13122021 81
Quinta Ace 30 45 55 65 90 115
Sound power level, indoors
LWA
dB 46 53 55 55 60 59
Emissions of nitrogen oxides NOXmg/kW
h
42 42 48 48 53 41
(1) Low temperature means 30 °C for condensing boilers, 37 °C for low temperature boilers and 50 °C (at heater inlet) for other heating
appliances.
(2) High temperature operation means 60 °C return temperature at heater inlet and 80 °C feed temperature at heater outlet.
See
The back cover for contact details.
12.5 Boiler pump
A boiler pump is not supplied with this boiler. Take the boiler resistance
and system resistance into account when selecting a pump. The graph
shows the hydraulic resistance at various water flow rates. The table
shows some significant nominal flow data and the corresponding hydraulic
resistance.
If possible, install the pump directly under the boiler on the return
connection.
Important
When the pump is managed by the boiler's control unit, check if
the deaeration program is correctly set (parameter AP101 = 1).
Fig.82 Hydraulic resistance
AD-3001405-01
Q
87653 421
0
0
100
200
300
400
500
600
H
700
800
30 / 45 kW 30 / 45 kW
55 / 65 kW 55 / 65 kW
90 / 115 kW 90 / 115 kW
QWater flow (m3/h) HHydraulic resistance (mbar)
Tab.71 Nominal flow data
Unit 30 45 55 65 90 115
Q at ΔT = 10°C m3/h 2,60 3,50 4,80 5,28 7,20 9,0
H at ΔT = 10°C mbar 280 456 520 652 612 1000
Q at ΔT = 20°C m3/h 1,30 1,75 2,40 2,64 3,60 4,50
H at ΔT = 20°C mbar 70 114 130 163 153 250
Q at ΔT = 35°C m3/h - - - - - 2,55
H at ΔT = 35°C mbar - - - - - 72
12 Technical specifications
82 7684359 - v.11 - 13122021
Unit 30 45 55 65 90 115
Q at ΔT = 40°C m3/h 0,65 0,90 1,20 1,32 1,80 not permit
ted
H at ΔT = 40°C mbar 15 30 36 45 40 not permit
ted
13 Appendix
13.1 ErP information
13.1.1 Product fiche
Tab.72 Product fiche
Remeha – Quinta Ace 30 45 55 65 90 115
Seasonal space heating energy efficiency
class
A
A
A
A
- -
Rated heat output
(Prated or Psup)
kW 30 41 55 62 84 104
Seasonal space heating energy efficiency % 94 94 92 94 - -
Annual energy consumption GJ 91 125 173 188 - -
Sound power level LWA indoors dB 46 53 55 55 60 59
13 Appendix
7684359 - v.11 - 13122021 83
13.1.2 Package sheet
Fig.83 Package sheet for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
%
1
‘I’
2
%+
3
%( - ‘I’ ) x 0.1 = ±
4
%(‘III’ x + ‘IV’ x ) x 0.9 x ( /100) x = +
(1)
A* = 0.95, A = 0.91,
B = 0.86, C = 0.83,
D - G = 0.81
5
%( - ‘I’ ) x ‘II’ = +
6
%0.5 x 0.5 x = -
54
<30%
G F E D C B A A
+A
++ A
+++
%+ (50 x ‘II’) =
7
7
%
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building, as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics.
Boiler and supplementary heat pump installed with low temperature heat emitters at 35°C ?
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in %)
Supplementary heat pump
Tank rating
Collector effi ciency (in
%)
Tank volume (in m³) Collector size (in m²)
Seasonal space heating energy effi ciency (in %)
Supplementary boiler
Class I = 1%, Class II = 2%, Class III = 1.5%,
Class IV = 2%, Class V = 3%, Class VI = 4%,
Class VII = 3.5%, Class VIII = 5%
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A, use 0.95
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
13 Appendix
84 7684359 - v.11 - 13122021
IThe value of the seasonal space heating energy efficiency of the
preferential space heater, expressed in %.
II The factor for weighting the heat output of preferential and
supplementary heaters of a package as set out in the following
table.
III The value of the mathematical expression: 294/(11 · Prated),
whereby ‘Prated’ is related to the preferential space heater.
IV The value of the mathematical expression 115/(11 · Prated),
whereby ‘Prated’ is related to the preferential space heater.
Tab.73 Weighting of boilers
Psup / (Prated + Psup)(1)(2) II, package without hot water storage tank II, package with hot water storage tank
0 0 0
0.1 0.3 0.37
0.2 0.55 0.70
0.3 0.75 0.85
0.4 0.85 0.94
0.5 0.95 0.98
0.6 0.98 1.00
≥ 0.7 1.00 1.00
(1) The intermediate values are calculated by linear interpolation between the two adjacent values.
(2) Prated is related to the preferential space heater or combination heater.
13.2 EC Declaration of conformity
This appliance complies with the standard type described in the EC
declaration of conformity. It has been manufactured and commissioned in
accordance with European directives.
The original declaration of conformity is available from the manufacturer.
13 Appendix
7684359 - v.11 - 13122021 85
13 Appendix
86 7684359 - v.11 - 13122021
Original instructions - © Copyright
All technical and technological information contained in these technical instructions, as well as any drawings and technical
descriptions supplied, remain our property and shall not be multiplied without our prior consent in writing. Subject to alterations.
Remeha Commercial UK
Brooks House
Coventry Road
Warwick
CV34 4LL
T+44 (0)330 678 0140
Etechnical@remeha.co.uk
Wwww.remeha.co.uk
7684359 - v.11 - 13122021
7684359
82

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Remeha Quinta ACE 45 T-Control bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Remeha Quinta ACE 45 T-Control in de taal/talen: Engels als bijlage per email.

De handleiding is 4.19 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

Andere handleiding(en) van Remeha Quinta ACE 45 T-Control

Remeha Quinta ACE 45 T-Control Gebruiksaanwijzing en installatiehandleiding - Nederlands - 80 pagina's

Remeha Quinta ACE 45 T-Control Gebruiksaanwijzing en installatiehandleiding - Deutsch - 116 pagina's

Remeha Quinta ACE 45 T-Control Gebruiksaanwijzing en installatiehandleiding - Français - 84 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info