17
5.3 MINIMUM AND/OR MAXIMUM TEMPERATURE LIMIT
A separate high and/or low limit for the temperature can be set. The limits
can be set between -35 ºC and +70 ºC, with one decimal. Negative values
are set by a “-” before the value.
5.4 LOG INTERVAL
When using the Mobeye Internet Portal the Mobeye CML4255 will log
values and send these to the portal. The logging interval is the interval in
which the measured values are logged (with a timestamp). The data are
stored in the system until the next data transfer. The logging interval can be
set between 0 and 9999 minutes. The default log interval is set at 60
(minutes).
5.5 TRANSFER INTERVAL
If the log interval is active the recorded values are periodically transmitted
to the Portal during the data synchronisation. The transmission interval can
be set between 1 and 999 hours. The standard transmission interval is set to
24 (hours).
5.6 TEMPERATURE DELAY TIME
The temperature delay time defines the duration a temperature limit is
violated before an alarm is initiated. If the temperature returns to the non-
alarm status within the delay time, no alarm is sent. The time can be set
between 0 and 999 minutes.
As default, the temperature delay time is set to 0 minutes.
5.7 TEMPERATURE CALIBRATION
The high quality digital temperature sensor is calibrated in the factory. For
special applications it is possible to calibrate the sensor and program a
correction. The adjusted temperature will be used in the measurement and
reports. Example: the Mobeye CML4255 measures 13 °C. Actual ambient
temperature is measured as 13,5 °C. To adjust this difference, +0,5 degrees
shall be programmed.