17
5.8 ALARM DELAY TIME
The input delay time defines the time that the input is triggered before an
alarm is initiated. If the input returns to the non-alarm status within the delay
time, no alarm is sent. The time can be set between 0 and 999 seconds. As
default, the input delay time is set to 1 second.
5.9 INACTIVE TIME
The “inactive time” defines the time an input is not active after an activation.
During the inactive time, no new alarm message will be sent. Only when the
input returned to the non-alarm status, gets activated again and remains
active, an alarm will be sent yet after the inactive time. If the time is set to “0”
(minutes), the input will be active again immediately after returning to the
non-alarm status. The time can be set between 0 and 60 minutes. As default,
the inactive time is set to “0”.
5.10 ALARM REPEAT TIME
In order to emphasize the urgency of the alarm messages, all alarms can be
repeated. As long as the temperature value or an input has not returned to
the inactive status, the alarm messages will be repeated after the ‘alarm
repeat time’. The repeat interval can be set between 0 and 999 minutes. As
default the alarm repeat time is set to 0 minutes (no repeat).
5.11 POWER FAILURE MESSAGE
If the Mobeye ThermoGuard is supplied with external power and the power
fails, it can send alarm messages. If the setting is "OFF", no message is sent.
When set to “ALARM”, notifications are sent to the set contacts. When using
your own SIM card, the setting “ALERT” only results in an SMS notification to
TEL1. The default setting is "ALARM".
5.12 POWER FAILURE DELAY TIME
To avoid false alarms caused by short power failures, a power failure delay
time can be set. This defines the time between the initial power failure and
the alarm notification. If the power is restored within the delay time, no
alarm is sent. The time can be set between 0 and 999 minutes. As default, the
delay time is set to "0".