Middle Static Pressure Duct Type
INSTALLATION MANUAL
Thank you very much for purchasing our air conditioner,
Before using your air conditioner , please read this manual carefully and keep it for future reference.
If used as MULTI unit, please refer to the Installation & operation manuals packed with outdoor unit.
1
installation manual
Keep this manual where the operator can easily find them.
Read this manual attentively before starting up the units.
For safety reason the operator must read the following
cautions carefully.
Installation must be performed in accordance with the
requirement of NEC and CEC by authorized personnel only.
Applicable to the North American area only
1. SAFETY PRECAUTIONS
The safty precautions listed here are divided into two categories.
After completing the installation, make sure that the unit operates
properly during the start-up operation. Please instruct the customers
on how to operate the unit and keep it maintained.Also, inform
customers that they should store this installation manual along with
the owner's manual for future reference.
Be sure only trained and qualified service personnel to
install, repair or service the equipment.
Improper installation, repair, and maintenance may result in
electric shocks, short-circuit, leaks, fire or other damage to
the equipment.
If you do not follow these instrutions exactly, the unit may
cause property damage, personal injury or loss of life.
If you do not follow these instrutions exactly, the unit may
cause minor or moderate property damage, personal
injury.
CONTENTS PAGE
SAFETY PRECAUTIONS.......................................................................................1
INSTALLATION INFORMATION........................................................................... 2
ATTACHED FITTINGS.............................................................................................3
INSPECTING AND HANDLING THE UNIT.........................................................4
INDOOR UNIT INSTALLATION.................................................................................4
OUTDOOR UNIT INSTALLATION............................................................................11
INSTALL THE CONNECTING PIPE..................................................................15
REFRIGERANT PIPE..........................................................................................16
REFRIGERANT PIPE CONNECTION ...............................................................17
CONNECTIVE DIAGRAM......................................................................................18
CONNECT THE DRAIN PIPE..............................................................................18
FRESH AIR DUCT INSTALLATION.......................................................................19
CONTROL..............................................................................................20
WIRING.................................................................................................20
TEST OPERATION................................................................................................21
Install according to this installation instructions strictly.
If installation is defective, it will cause water leakage,
electrical shock and fire.
When installing the unit in a small room, take measures
against to keep refrigerant concentration from exceeding
allowable safety limits in the event of refrigerant leakage.
Contact the place of purchase for more information.
Excessive refrigerant in a closed ambient can lead to oxygen
deficiency.
Use the attached accessories parts and specified parts
for installation.
otherwise, it will cause the set to fall, water leakage,
electrical shock and fire.
Install at a strong and firm location which is able to
withstand the set' s weight.
If the strength is not enough or installation is not properly
done, the set will drop to cause injury.
The appliance must be installed 2.3m / 7.5ft above floor.
The appliance shall not be installed in the laundry.
Before obtaining access to terminals, all supply circuits
must be disconnected.
The appliance must be positioned so that the plug is
accessible.
The enclosure of the appliance shall be marked by word,
or by symbols, with the direction of the fluid flow.
For electrical work, follow the local national wiring
standard, regulation and this installation instructions. An
independent circuit and single outlet must be used.
If electrical circuit capacity is not enough or defect in
electrical work, it will cause electrical shock or fire.
Use the specified cable and connect tightly and clamp
the cable so that no external force will be acted on the
terminal.
If connection or fixing is not perfect, it will cause heat-up or
fire at the connection.
Wiring routing must be properly arranged so that control
board cover is fixed properly.
If control board cover is not fixed perfectly, it will cause
heat-up at connection point of terminal, fire or electrical
shock.
If the supply cord is damaged, it must be replaced by the
manufacture or its service agent or a similarly qualified
person in order to avoid a hazard.
An all-pole disconnection switch having a contact
separation of at least 3mm/0.118in in all poles should be
connected in fixed wiring.
When carrying out piping connection, take care not to let
air substances go into refrigeration cycle.
Otherwise, it will cause lower capacity, abnormal high
pressure in the refrigeration cycle, explosion and injury.
Do not modify the length of the power supply cord or use
of extension cord, and do not share the single outlet with
other electrical appliances.
Otherwise, it will cause fire or electrical shock.
Carry out the specified installation work after taking into
account strong winds, typhoons or earthquakes.
Improper installation work may result in the equipment falling
and causing accidents.
WARNING
WARNING
CAUTION
2
installation manual
To install properly, please read this "installation manual" at
first.
The air conditioner must be installed by qualified persons.
When installing the indoor unit or its tubing, please follow
this manual as strictly as possible.
If the air conditioner is installed on a metal part of the
building, it must be electrically insulated according to the
relevant standards to electrical appliances.
When all the installation work is finished, please turn on
the power only after a thorough check.
Regret for no further announcement if there is any change
of this manual caused by product improvement.
2. INSTALLATION INFORMATION
Ground the air conditioner.
Do not connect the ground wire to gas or water pipes,
lightning rod or a telephone ground wire.inappropriate
grounding may result in electric shocks.
Be sure to install an earth leakage breaker.
Failure to install an earth leakage breaker may result in
electric shocks.
Connect the outdoor unit wires , then connect the indoor
unit wires.
You are not allowed to connect the air conditioner with the
power supply until the wiring and piping is done.
While following the instructions in this installation
manual, install drain piping in order to ensure proper
drainage and insulate piping in order to prevent
condensation.
Improper drain piping may result in water leakage and
property damage.
Install the indoor and outdoor units, power supply wiring
and connecting wires should be at least 1 meter away
from televisions or radios in order to prevent image
interference or noise.
Depending on the radio waves, a distance of 1 meter may not
be sufficient enough to eliminate the noise.
The appliance is not intended for use by young children
or infirm persons without supervision.
Don't install the air conditioner in the following
circumstance:
There is petrolatum existing.
There is salty air surrounding (near the coast).
There is caustic gas (the sulfide, for example) existing
in the air (near a hot spring).
The Volt vibrates violently (in the factories).
In buses or cabinets.
In kitchen where it is full of oil gas.
There is strong electromagnetic wave existing.
There are inflammable materials or gas.
There is acid or alkaline liquid evaporating.
Other special conditions.
If the refrigerant leaks during installation, ventilate the
area immediately.
Toxic gas may be produced if the refrigerant comes into the
place contacting with fire.
The temperature of refrigerant circuit will be high, please
keep the interconnection cable away from the copper
tube.
After completing the installation work, check that the
refrigerant does not leak.
Toxic gas may be produced if the refrigerant leaks into the
room and comes into contact with a source of fire, such as a
fan heater, stove or cooker.
INSTALLATION ORDER
Select the location;
Install the indoor unit;
Install the outdoor unit;
Install the connecting pipe ;
Connect the drain pipe;
Wiring;
Test operation.
CAUTION
The appliance shall be installed in accordance with
national wiring regulations.
Do not operate your air conditioner in a wet room such
as a bathroom or laundry room.
An all-pole disconnection device which has at least 3mm
clearances in all poles , and have a leakage current that
may exceed 10mA, the residual current device (RCD)
having a rated residual operating current not exceeding
30mA, and disconnection must be incorporated in the
fixed wiring in accordance with the wiring rules.
3
installation manual
19. Connecting wire for display (2M)
20. Cord protection rubber ring
3. ATTACHED FITTINGS
Please check whether the following fittings are of full scope. If there are some spare fittings , please restore them carefully.
Table 3-1
QUANTITY SHAPE NAME
1. Soundproof / insulation sheath
11. Remote controller manual
7. Remote controller
(on some models)
8. Frame
10.Alkaline dry batteries (AM4)
2
1
12. Wire controller
1
1
1
1
(on some models)
2
1
1
1
Tubing & Fittings
Remote controller & Its Frame
(Match with
remote controller )
Wire controller & Its Frame
(Match with wire controller )
Others
9.Mounting screw(ST2.9×10-C-H)
15. Installation manual
16 .Transfer connector(Φ12.7-Φ15.9)/
( )
(Packed with the indoor unit )
(NOTE: Pipe size differ from appliance
to appliance.To meet different pipe size
requirement, sometimes the pipe
connections need the transfer connector
to install on the outdoor unit .)
17 .Transfer connector(Φ6.35-Φ9.52)/
( )
(Packed with the indoor unit )
(NOTE: Pipe size differ from appliance
to appliance.To meet different pipe size
requirement, sometimes the pipe
connections need the transfer connector
to install on the outdoor unit .)
18 .Transfer connector(Φ9.52-Φ12.7)/
( )
(Packed with the indoor unit,used for
multi-type models only )
(NOTE: Pipe size differ from appliance
to appliance.To meet different pipe size
requirement, sometimes the pipe
connections need the transfer connector
to install on the outdoor unit .)
1
14. Owners manual
5. Drain joint
6. Seal ring
Drainpipe Fittings
(for cooling & heating)
2. Binding tape
1
3.Seal sponge
2
EMC & Its Fitting
(for some models)
13. Magnetic ring
(twist the electirc wires L and N
around the magnetic ring to five
circles)
1
4.Orifice
1
(on some models)
Φ0.5in-Φ0.63in
Φ0.25in-Φ0.375in
Φ0.375in-Φ0.5in
1
(on some models)
1
(on some models)
1
(on some models)
1
(on some models)
1
(on some models)
4
installation manual
CAUTION
4. INSPECTING AND HANDLING THE UNIT
At delivery, the package should be checked and any damage should
be reported immediately to the service agent.
When handling the unit, take into account the following:
Fragile, handle the unit with care.
Keep the unit upright in order to avoid compressor
damage.
Choose on before hand the path along which the unit is to be
brought in.
Move this unit as originally package as possible.
When lifting the unit , always use protectors to prevent belt
damage and pay attention to the position of the units centre
of gravity.
1
2
3
4
NOTE
5. INDOOR UNIT INSTALLATION
Keep indoor unit, outdoor unit, power supply wiring and
transmission wiring at least 1 meter away from televisions
and radios. This is to prevent image interference and
noise in those electrical appliances. (Noise may be
generated depending on the conditions under which the
electric wave is generated, even if 1 meter is kept.)
There is enough room for installation and maintenance.
The ceiling is horizontal, and its structure can endure the
weight of the indoor unit.
The outlet and the inlet are not impeded, and the
influence of external air is the least.
The air flow can reach throughout the room.
The connecting pipe and drainpipe could be extracted out
easily.
There is no direct radiation from heaters.
5.1 Installation place
The indoor unit should be installed in a location that meets
the following requirements:
5.2 Install the main body
Please refer to the following figures for positioning 4 screw
bolts.
Evaluate the ceiling construction and please install with Ø10
/ Ø0.394in hanging screw bolts.
1 Installing Ø10/Ø0.394in hanging screw bolts. (4 bolts)
Consult the construction personnels for the specific procedures.
Do keep the ceiling flat. Consolidate the roof beam to avoid
possible vibration.
Carry out the pipe and line operation in the ceiling after finishing
the installation of the main body. While choosing where to start
the operation, determine the direction of the pipes to be drawn
out. Especially in case there is a ceiling, position the refrigerant
pipes, drain pipes,indoor & outdoor lines to the connection
places before hanging up the machine.
The installation of hanging screw bolts.
Cut off the roof beam.
Strengthen the place that has been cut off, and consolida-
tethe roof beam.
After the selection of installation location, position the refriger-
ant pipes, drain pipes,indoor & outdoor wires to the connection
places before hanging up the machine.
The installation of hanging screw bolts.
Fig.5-2
Fig.5-1
Confirm the minimum drain tilt is 1/100 or more
Wooden construction
Put the square timber traversely over the roof beam, then install
the hanging screw bolts. (Refer to Fig.5-2)
5.2.1
Timber over the beam
Roof beam
Hanging screw bolts
Ceiling
Maintenance roomage
checking orifice
600mmX600mm/23.622inX23.622in
300mm/11.811in or more
200mm/7.874in or more
5
installation manual
Fig.5-3
Fig.5-4
Fig.5-5
Fig.5-6
New concrete bricks
Inlaying or embedding the screw bolts. (Refer to Fig. 5-3)
For Original concrete bricks
Use embedding screw bold, crock and stick harness.
(Refer to Fig.5-4)
Steel roof beam structure
Install and use directly the supporting angle steel. (Refer to Fig.5-5)
5.2.2
5.2.3
5.2.4
(Blade shape insertion)
(Slide insertion)
Steel bar
Embedding screw bolt
(Pipe hanging and embedding screw bolt)
Hanging screw bolt
Hanging bolts
Supporting
angle steel
Overhanging the indoor unit
2
(1) Overhang the indoor unit onto the hanging screw bolts with
block.
(2) Position the indoor unit in a flat level by using the level indicator,
unless it may cause leakage.
Screw nut
Washer
Hanging
screw bolt
Overhang part
Shockproof cushion
3. Air inlet and air outlet duct should be apart far enough to avoid
air passage short-circuit.
Recommended duct connection
Canvas tie-in Canvas tie-in
Air outlet
Isolation booth
Isolation booth
checking orifice
Air inlet
Air dust filter
Do not put the connecting duct weight on the indoor unit.
1.
When connecting duct, use inflammable canvas tie-in to prevent
vibrating.
2.
Change the fan motor static pressure corresponding to external
duct static pressure.
Insulation foam should be wrapped outside the duct to avoid
condensate and internal duct underlayer shall be added to reduce
the noise for special requirement.
3.
Fig.5-7
NOTE
Table.5-1
5. Please refer to the following static pressure to install
5.3 Duct and accessories installation
Install the filter(optional) according to air inlet size.
1.
Install the canvas tie-in between the body and duct.
2.
4.
MODEL
(Btu/h)
Static Pressure
(Pa)
3012
70
18
70
24
80
30~36
100
42~60
6
installation manual
Air filter
Air filter
Electric control box
Electric control box
Dimension and air outlet size
Air inlet size
Position size of descensional ventilation opening
Size of mounted hook
Fig.5-8
Unit: mm
The positioning of ceiling hole, indoor unit and hanging screw bolts
7
installation manual installation manual
NOTE
Air return flange
Side rail
Seal sponge
Dentilation panel
1.
Take off ventilation panel and flange, cut off the staples at
side rail.
2.
Stick the attached seal sponge as per the indicating place in
the following fig, and then change the mounting positions of
air return panel and air return flange .
3. When install the filter mesh, please plug it into flange inclined
from air return opening, and then push up.
4. The installation has finish, upon filter mesh which fixing
blocks have been insert to the flange positional holes.
Fig.5-9
How to adjust the air inlet direction? (From rear side to under-side.)
Table.5-2 mm
air outlet opening size
air return opening size
Size of
mounted lug
Outline dimension
920 210 635 570 65 713 35 119 815 200 80 960 350
A B C D E F G H I J K L M
920 270 635 570 65 713 35 179 815 260
920 270 635 570 65 713 35 179 815 260
20 960 350
12~18
24
36
(small model)
All the figures in this manual are for explanation purpose only. They may be slightly different from the air
conditioner you purchased.The actual unit shall prevail.
1140 270 775 710 65 933 35 179 1035 260
20 1180 490
45 1240 500
30~36
42~60
1200
300 865 800 80 968 40 204 1094 288 45 1240 500
12
700 210 635 570 65 493 35 119 595 200 80 740 350
(in=mm/25.4)
8
installation manual
5.9
Fan performances
Static pressure curve(middle static pressure duct)
12K 18K
800
700 400 300
Low speed
10
20
30
40
50
60
70
80
90
Pa
Air volume(m /h)
3
High speed
Mid speed
500
600
900
0
Super high speed
1200
Mid speed
High speed
3
Air volume(m /h)
1100 1000 900 800 700 600
Pa
90
80
70
60
50
40
30
20
10
Low speed
200
300 400
500
Super high speed
24K 30K
700
1500
1200
Mid speed
High speed
3
Airvolume(m /h)
1100 1000 900 800
Pa
90
80
70
60
50
40
30
20
10
Low speed
1300 1400
Super high speed
2000
1800
Mid speed
High speed
3
Air volume(m /h)
1200
Pa
90
80
70
60
50
40
30
20
10
Low speed
1400 1600 2200
2400
Super high speed
9
installation manual
36K
36K(small model)
48K
60K
2400
2200
1600 1400
Low speed
10
20
30
40
50
60
70
80
90
1100
Air volume(m /h)
3
High speed
Mid speed
1200
1800
2000
Super high speed
Pa
3100
2800 1900 1600
Low speed
10
20
30
40
50
60
70
80
90
1000
Air volume(m /h)
3
High speed
Mid speed
1300
2200
2500
Pa
100
Super high speed
110
120
2500
2200
1300
Mid speed
High speed
3
Air volume(m /h)
1000
Pa
90
80
70
60
50
40
30
20
10
Low speed
1600 1900 2800
3100
100
3400
Super high speed
110
120
Pa
high speed
1500
1400
1100
Low speed
Mid speed
3
Air volume(m /h)
1000
1200 1300 1600
1700
10
20
30
40
50
60
70
80
1800
900
installation manual
Static pressure curve(high static pressure duct)
18k
Mid speed
High speed
1400 1300
1200
1100
1000
Pa
90
80
70
60
50
40
30
20
10
Low speed
700
Super high speed
800
900
1500
24K
Mid speed
High speed
1400 1300
1200
1100
1000
Pa
90
80
70
60
50
40
30
20
10
Low speed
700
Super high speed
800
900
1500
1600
3
Air volume(m /h)
3
Air volume(m /h)
30K
Mid speed
High speed
2000
1800
1600 1400 1200
Pa
90
80
70
60
50
40
30
20
10
Low speed
600
Super high speed
800
1000
2200
2400
3
Air volume(m /h)
100
36K
Mid speed
High speed
2000 1800
1600 1400 1200
Pa
180
160
140
120
100
80
60
40
20
Low speed
600
Super high speed
800
1000
2200
2400
3
Air volume(m /h)
48K
Mid speed
High speed
3200
3000
2800
2600
2400
Pa
180
160
140
120
100
80
60
40
20
Low speed
800
Super high speed
1000
2200
3400 3600
3
Air volume(m /h)
2000
1600
60K
Mid speed
High speed
3200 3000
2800
2600
2400
Pa
180
160
140
120
100
80
60
40
20
Low speed
800
Super high speed
1000
2200
3400
3600
3
Air volume(m /h)
2000
1600
installation manual
2. Place The Pipe
Drill a hole in the wall (suitable just for the size of the wall
sleeve), then set on the fittings such as the wall sleeve and its
cover.
Bind the connecting pipe and the cables together tightly with
binding tapes.
Pass the bound connecting pipe through the wall sleeve from
outside. Make sure of the pipe allocation not to damage the
copper tubes.
3
5
6
7
4
Connect the pipes.
Expel the air with a vacuum pump or refrigerant.
Open the service valves of the outdoor unit .
Check the refrigerant leakage. Check all the joints
with the leak detector or soap water.
Cover the joints of the connecting pipe with the
insulation foam, and bind them well with the tapes to
prevent potential leakage.
8.1 Length and drop height permitted of the
refrigerant piping
8. REFRIGERANT PIPE(the unit with the
twins function)
Note: Reduced length of the branching tube is the 0.5m/1.64ft
of the equivalent length of the pipe.
Table.8-1
Permitted value
Piping
Total pipe length (Actual)
Indoor unit to indoor unit drop height
(farthest from the line
pipe branch)
(farthest from the line
pipe branch)
Indoor unit-outdoor unit
drop height
30m/98.42ft
18K+18K
24K+24K/
30K+30K
50m/164.04ft
15m/49.21ft
10m/32.8ft
20m/65.8ft
0.5m/1.64ft
L+L1+L2
L1,L2
L1-L2
H1
H2
Fig.8-1
A
L
L1
L2
Outdoor unit
The line branch pipe
Drop height between indoor
unit and outdoor unit H20m/65.8ft
Indoor unit to intdoor unit
drop height H0.5m/1.64ft
Indoor unit
Note: All used branch pipe must be produced by Midea,
otherweise it causes malfunction. The indoor units should
be installed equivalently at the both side of the U type branch
pipe.
8.3 Size of joint pipes for outdoor unit
Model
Gas side Liquid side
Φ15.9/0.626in
Φ15.9/0.626in
Φ15.9/0.626in
Φ9.5/0.375in
Φ9.5/0.375in
Φ9.5/0.375in
the size of main pipe(mm)
36K
48K
60K
Size of joint pipes for 410A outdoor unit Table.8-3
Base on the following tables, select the diameters of the
outdoor unit connective pipes. In case of the main
accessory pipe large than the main pipe, take the large one
for the selection.
The 1st
branching pipe
8.2 Size of joint pipes for indoor unit
Gas side
Capacity of
indoor unit
(A)
Size of main pipe(mm)
Liquid side
Φ12.7/0.5in
Φ15.9/0.626in
Φ15.9/0.626in
Φ6.35/0.25in
Φ9.5/0.375in
Φ9.5/0.375in
18K
24K
30K
Size of joint pipes for 410A indoor unit
Table.8-2
CE-FQZHN-01C
CE-FQZHN-01C
CE-FQZHN-01C
CE-FQZHN-01C
CE-FQZHN-01C
CE-FQZHN-01C
Available
branching pipe
installation manual
Test operation
3
Set the air conditioner in cooling mode with the remote
controller, and check the following points. If there is any
malfunction, please resolve it according to the chapter
"Troubleshooting" in the "Owner's Manual".
1) The indoor unit
a. Whether the buttons on the remote controller works
well.
b. Whether the air flow louver moves normally.
c. Whether the room temperature is adjusted suitable.
d. Whether the indicator lights normally.
e. Whether the temporary switch on the unit works well.
f. Whether the drainage is normal.
g. Whether there is abnormal vibration or noise during
operation.
h. Whether the air conditioner works well in heating
mode(heat pump model).
2) The outdoor unit
a. Whether there is abnormal vibration and noise during
operation.
b. Whether the exhaust air, noise, or condensate influence
your neighborhood.
c. Whether there is any refrigerant leakage during
operation.
3 minutes delay is normal when restarting the unit for
compressor protection.
CAUTION
15. TEST OPERATION
The test operation must be carried out after the entire
installation.
Please confirm the following points before the test operation:
2
1
The indoor unit and outdoor unit are installed properly.
Tubing and wiring are correctly completed.
The refrigerant pipe system is leakage-checked.
The drainage is unimpeded.
The heating insulation works well.
The ground wiring is connected correctly.
The length of the tubing and additional charge amount
have been recorded.
The power voltage matches rated voltage of the air
conditioner.
There is no obstacle at the outlet and inlet of the outdoor
and indoor units.
The gas-side and liquid-side service valves are both
completely open.
The air conditioner is pre-heated by turning on the power.
All the figures in this manual are for explanation purpose only.
They may be slightly different from the air conditioner you
purchased(depend on model).The actual unit shall prevail.
NOTE
Fig.14-2
Protection Board
2.Centrifugal fan outdoor unit
installation manual
Table 14-1
Table 14-2
The Specification of Power(indoor power supply)
The Specification of Power(outdoor power supply)
20/16 40/25 50/30 60/45 60/50
40/30 60/40 70/55 70/60
MODEL
POWER
CIRCUIT BREAKER/FUSE(A)
PHASE
FREQUENCY AND VOLT
18
24 60 30~36 42~48
208-240V 208-240V
1Phase 1Phase
208-240V
1Phase
208-240V
1Phase
208-240V
1Phase
MODEL
POWER
CIRCUIT BREAKER/FUSE(A)
PHASE
FREQUENCY AND VOLT
30~36 30~36
42~60 42~60
380-420V
25/20 25/20 40/25 45/35
208-240V
3Phase
380-420V
3Phase 3Phase
208-240V
3Phase
Table 14-3
Table 14-4
MODEL
POWER
CIRCUIT BREAKER/FUSE(A)
PHASE
FREQUENCY AND VOLT
24 60 30~36 42~48
208-240V
1Phase
20/16
12~18
208-240V
1Phase
208-240V
1Phase
208-240V
1Phase
208-240V
1Phase
MODEL
POWER
CIRCUIT BREAKER/FUSE(A)
PHASE
FREQUENCY AND VOLT
30~36 30~36
42~60 42~60
380-420V
25/20 25/20 40/25 45/35
208-240V
3Phase
380-420V
3Phase 3Phase
208-240V
3Phase
23
installation manual
The Specification of Power(independence power supply)
The Specification of Power for the invert type air conditioner(independence power supply)
20/16 40/25 50/30 60/45 60/50
208-240V 208-240V
1Phase 1Phase
208-240V
1Phase
208-240V
1Phase
208-240V
1Phase
MODEL
POWER
(indoor)
POWER
(outdoor)
POWER
(indoor)
POWER
(outdoor)
CIRCUIT BREAKER/FUSE(A)
CIRCUIT BREAKER/FUSE(A)
PHASE
FREQUENCY AND VOLT
PHASE
FREQUENCY AND VOLT
18 24 60 30~36 42~48
208-240V 208-240V
1Phase 1Phase
208-240V
1Phase
208-240V
1Phase
208-240V
1Phase
20/16 20/16 20/16 20/16 20/16
208-240V
1Phase
208-240V
1Phase
208-240V
1Phase
208-240V
1Phase
20/16 20/16 20/16 20/16
MODEL
CIRCUIT BREAKER/FUSE(A)
CIRCUIT BREAKER/FUSE(A)
PHASE
FREQUENCY AND VOLT
30~36 30~36
42~60 42~60
380-420V
25/20 25/20 40/25 45/35
208-240V
3Phase
380-420V
3Phase 3Phase
208-240V
3Phase
Table 14-5
Table 14-6
PHASE
FREQUENCY AND VOLT
POWER
(indoor)
POWER
(outdoor)
30/20 30/20 40/30 40/35 50/40
208-240V 208-240V
1Phase 1Phase
208-240V
1Phase
208-240V
1Phase
208-240V
1Phase
MODEL
POWER
(indoor)
POWER
(outdoor)
POWER
(indoor)
POWER
(outdoor)
CIRCUIT BREAKER/FUSE(A)
CIRCUIT BREAKER/FUSE(A)
PHASE
FREQUENCY AND VOLT
PHASE
FREQUENCY AND VOLT
18 24 60 30~36 42~48
220-240V 220-240V
1Phase 1Phase
220-240V
1Phase
220-240V
1Phase
220-240V
1Phase
15/10 15/10 15/10 15/10 15/10
220-240V
1Phase
220-240V
1Phase
220-240V
1Phase
220-240V
1Phase
15/10 15/10 15/10 15/10
MODEL
CIRCUIT BREAKER/FUSE(A)
CIRCUIT BREAKER/FUSE(A)
PHASE
FREQUENCY AND VOLT
30~36 30~36
42~60 42~60
380-420V
30/20 30/25 50/40 50/40
208-240V
3Phase
380-420V
3Phase 3Phase
208-240V
3Phase
Table 14-7
Table 14-8
PHASE
FREQUENCY AND VOLT
POWER
(indoor)
POWER
(outdoor)
installation manual
24
The power supply is included in the power supply above mentioned can be applied to the table.
Before obtaining access to terminals, all supply circuits must be disconnected.
CAUTION
Wiring figure
Fig.14-3
Fig.14-4
Ground wiring
Ground wiring
Power supply
Switch/Fuse
(Available locally)
Power wiring (indoor)
Power linking wiring (Outdoor)
Strong elec-signal link wiring
Weak elec-signal link wiring
Indoor
Unit
Outdoor
Unit
Ground the air conditioner properly in case to affect its anti-interference function
Ground wiring
Ground wiring
Power supply
Switch/Fuse
(Available locally)
Power wiring (outdoor)
Power linking wiring (indoor)
Strong elec-signal link wiring
Weak elec-signal link wiring
Indoor
Unit
Outdoor
Unit
Ground the air conditioner properly in case to affect its anti-interference function
QST2I-013AEN
202000192509
20140926
The design and specifications are subject to change without prior notice for product
improvement.Consult with the sales agency or manufacturer for details
.
3

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Midea MTBD-Serie Mono bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Midea MTBD-Serie Mono in de taal/talen: Engels als bijlage per email.

De handleiding is 4,47 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

Andere handleiding(en) van Midea MTBD-Serie Mono

Midea MTBD-Serie Mono Installatiehandleiding - Deutsch - 24 pagina's

Midea MTBD-Serie Mono Gebruiksaanwijzing - Deutsch - 12 pagina's

Midea MTBD-Serie Mono Gebruiksaanwijzing - English - 12 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info