INSTALLATION MANUAL FOR ROOM
A
AIR CONDITIONER
(Split Wall-Mounted Type)
For correct installation, read this manual before starting installation.
Only trained and qualified service personnel should install, repair or service air conditioning
equipment. Users should not install the air conditioner by themselves.
All pictures are only sketches. If there is any difference between pictures in this manual and
the actual shape of the air conditioner you purchased, the actual shape shall prevail.
Installation in the following places may cause trouble. If it is unavoidable, please, consult
with the local dealer.
A place full of machine oil.
A saline place such as coast.
A place full of sulfide gas such as hot-spring resort.
Places where there are high frequency machines such as wireless equipment, welding
machine, and medical facility.
A place of special environmental conditions.
The appliance shall not be installed in the laundry.
A place, which is convenient to installation
and not exposed to a strong wind. A place
that is dry and ventilated.
A place can bear the weight of the outdoor
unit and where the outdoor unit can be held
in the horizontal position.
A place which does not allow an increase
in noise level and vibration.
A place where the operation noise and dis-
charge air do not disturb your neighbor.
A place free of a leakage of combustible
gases.
An allowable head level at the connective
piping is less than 5m and length of the
connective piping is up less than 10m.
No any obstacle which block radiat air.
Indoor Unit
Outdoor Unit
INSTALLATION PRECAUTION
A place where is no obstacle near the inlet
and outlet area.
A place which can bear the weight of the
indoor unit.
A place which allows the air filter to be
removed.
A place where the reception range is not
Exposed to direct sunlight.
A place where the connective pipe and
drain hose is easy to led out.
A place 1m or more to TV, radio instrument,
in the center of the room is perfect.
The indoor unit should be installed 2.3
meters or more above the floor.
INDOOR UNIT INSTALLATION
1
1. Run the drain hose sloping downward. Do
not install the drain hose as illustrated
below.
2. When connection extension drain hose,
insulate the connecting part of extension
drain hose with a shield pipe
Do not form a rise
Connective
pipe
Pipe holder
Pipe cover
Right piping
Left piping
Pipe cover
Drain hose
Connective
pipe
Pipe room
Ponding box
Indoor unit outline
Connective pipe
Right back piping
Left back piping
Wrapping belt
Do not put the hose
end into water
Indoor unit
1. For the left-hand and right-hand piping,
remove the rear plate bushing from the left
side of the rear plate.
Explain to clients that the pipe cover must
be kept as it may be used when relocate
the air conditioner to any other place.
2. For the left-hand and rear-left-hand piping,
install the piping as shown. Bend the conn-
ective pipe to be laid at 43mm height or
less from the wall.
3. Fix the end of the connective pipe.
(Refer to Tightening Connection in REFRI-
GRANT PIPING CONNECTION)
Connect the indoor unit first then the outdoor
unit and bend and arrange the pipe carefully.
Do not allow the piping to let out from the
back of the indoor unit.
Be careful not to let the drain hose slack.
Insulate both of the auxiliary piping.
Banding the drain hose under the auxiliary
pipe.
Do not allow the piping to let out from the
back of the indoor unit.
Wind the connective cable, drain hose and
wiring with tape securely, evenly as shown
below.
Because the condensed water from rare
of the indoor unit is gathered in ponding
box and is piped out of room. Do not put
anything else in the box.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
43
3. Piping and bandaging
1. Drainage
2. Connective pipe
CAUTION
1. Drilling A Hole and Mounting Installation Plate
2. Connective Pipe and Drainage Installation
Installation Plate and Its Dimention
Indoor unit outline
20
12cm or more
to wall 12cm or more
to wall
Left refrigerant
pipe hole 65 Right refrigerant
pipe hole 65
Installation plate
30
70
750
45
250
15cm or more to ceiling
1. Install the installation plate horizontally on stru-
ctural parts in the wall with the spaces provided
around the plate.
2. In case of brick, concrete or similar type walls,
make 6mmdia, holes in the wall. Insert clip anc-
hors for appropriate mounting screws.
3. Fix the installation plate on the wall.
1. Pass the piping through the hole in the wall.
2. Put the upper claw at the back of the indoor unit on
the upper hook of the installation plate, move the
indoor unit from side to side to see that it is securely
hooked.
3. Piping can easily be made by lifting the indoor unit
with a cushioning material between the indoor unit
and the wall. Get it out after finish piping.
4. Push the lower part of the indoor unit up on the wall,
Then move the indoor unit from side to side, up and
down to check if it is hooked securely.
1. As diagram above determine the pipe
hole position using the installation
plate, drill the pipe hole( 65mm) so it
slants slightly downward.
2. Always use a wall hole conduit when
piercing metal lath, ply wood or metal
plate.
Upper hooker
Low hooker
Cushioning
material
Installation Plate
1. Fix the installation plate.
2. Drilling a hole.
3. Indoor Unit Installation
.
.
.
...
.
.
.
.
.
.
.
.
.
.
.
.
...
.
...
.
.
.
.
.
. .
.
NOTE: At least two of A, B, C
Aspects are free from blocking.
60cm or more
Air blowing
direction
Loop the
connective
cable.
Air filter
12cm or more
12cm or more
15cm or more
10cm or more
100cm or more
3
2
1
4
C
A
B
Before installation, operate the remote
controller to determine its location in a
reception range.
Keep the remote controller at least 1m
apart from the nearest TV set or stereo
equipment.
Do not install the remote controller in a
place exposed to direct sunlight or close
to a heating source, such as a stove.
Note that the positive and negative poles
are right positions when loading batteries.
The air-conditioner can be connected only
to a supply with system impedance no
more than 0.26 ohm. In case necessary
please consult your supply authority for
system impedance information.
Part
No.
1
2
3
4
5
6
7
8
Installation plate
Mounting screw ST3.9 25-C-H
Refrigerant
pipe
Liquid side
Gas
side
Remote controller
Remote controller holder
Seal
Drain elbow
6.35
9.53
1
8
8
1
1
1
1
Name of part Qty
Parts Installation
Cautions on remote controller installation
10cm or more
60cm or more
5
6
Clip anchor
anchor bolts of out door unit installation
The outdoor unit should not be exposed to
strong wind.
Fix the outdoor unit with 10 or 8 anchor
bolts.
air outlet
air inlet
A
B
Remote controller
Mounting screw B
ST2.9x10-C-H
Remote controller
holder
12.7
10000Btu/h
9000Btu/h
Model
7000Btu/h
9000Btu/h
50Hz R22
9000Btu/h
60Hz R22
9000Btu/h
R407C
10000Btu/h
A
458
548
548
548
458
B
250
266
266
266
250
INDOOR UNIT INSTALLATION
1
OUTDOOR UNIT INSTALLATION
2
Prepare the power source for exclusive with the air conditioner.
The supply voltage must comply with the rated voltage of the air conditioner:The plug socket shall be accessible
after installation.
Power Source
Model
Plug socket and Fuse rating
Wiring
50Hz 220-240V~
or
60Hz 220-230V~
7000Btu/h
9000Btu/h
10000Btu/h
2
1mm
2
1.5mm
10A
15A
Perform the wiring with sufficient capacity. Installation places legally require a short circuit isolator to be attached
to prevent electrical shock.
Do not extend the power cable code by cutting.
Power voltage should in the range of 90% 110% of rated voltage.
The plug of the air conditioner takes a grounding leg, so clients should use a grounding socket so that the air
conditioner can be grounded efficiently.
If the power cord is damaged, replacement should be conducted by qualified technician or a serviceman.
Install the outdoor unit on a rigid base to prevent increasing noise level and vibration.
Determine the air outlet direction where the discharged air is not blocked.
In the case that the installation place is exposed to strong wind such as a seaside operation by
putting the unit lengthwise along the wall or using a dust or shield plates.
Specially in windy area, install the unit to prevent the admission of wind. The connection betw-
een bracket and wall, bracket and the air conditioner should be firm, stable and reliable.
If need suspending installation, the installation bracket should accord with technique requir-
ement in the installation bracket diagram.
Fit the seal into the drain elbow,
then insert the drain elbow into
the base pan hole of outdoor unit,
rotate 90 to securely assemble
them. Connecting the drain elbow
with an extension drain hose
(Locally purchased), in case of the
water draining off the outdoor unit
during the heating mode.
Strong
wind
NOTE: Remark per EMC Directive 89/336/EEC
For to prevent flicker impressions during the start of the compressor (technical process),
following installation conditions do apply.
1. The power connection for the air conditioner has to be done at the main power distribution.
The distribution has to be of an low impedance, normally the required impedance reaches at a 32 A fusing point.
2. No other equipment has to be connected with this power line,.
3. For detailed installation acceptance, please refer to your contract with the power supplier if
restrictions do apply for products like washing machines, air conditioner or electrical ovens.
4. For power details of the air conditioner, refer to the rating plate of the product.
5. For any question contact your local dealer.
CAUTION
1. OUTDOOR INSTALLATION PRECAUTION
2. DRAIN ELBOW INSTALLATION
4. Wiring
~
Seal
Seal
Drain elbow
Drain elbow
Base pan hole of
outdoor unit
Base pan of
outdoor unit
1. Remove the electric parts cover from the outdoor
unit.
2. Connect the connective cables to the terminals as
identified with their respective matched numbers
on the terminal block of indoor and outdoor units.
3. To prevent the ingress of water, from a loop of the
connective cable as illustrated in the installation
diagram of indoor and outdoor units.
4. Insulate unused cords (conductors) with PVC-tape.
Process them so they do not touch any electrical
or metal parts.
Wrong wiring connections may cause some electrical
parts to malfunction. A disconnection device having
an air gap contact separation in all active conductors
should be incorporated in the fixed wiring according
to the National Wiring Regulation. All wiring must
comply with local and national electrical codes and be
installed by qualified and skilled electrician.
Oblique
90 C Roughness
Burr
Cover
Screw
Cooling & heating
type
Cooling only
type
Wire connector of outdoor unit
Wire-holding
board
Connective cable
CAUTION
CAUTION
3. REFRIGERANT PIPING CONNECTION 4. WIRING CONNECTION
10mm10mm
40mm40mm
A
1. Cut a pipe with a pipe cutter. Align pipes to be connected.
Sufficiently tighten the flare nut with fingers,
and then tighten it with a spanner and torque
wrench as shown.
Excessive torque can break nut depending
on installation conditions.
2. Insert a flare nut into a pipe and flare the
pipe.
Outer diam.
(mm)
A(mm)
Max. Min.
Outer
diam. Tightening
torque(N.cm) Additional tightening
torque(N.cm)
6.35mm 1570
(160kgf.cm) 1960
(200kgf.cm)
2940
(300kgf.cm)
4410
(450kgf.cm)
12.7mm
6.35 1.3 0.7
12.7
1.8 1.0
1. Flaring 2. Tightening Connection
1
134
2(N)
AIR PURGE AND TEST OPERATION
3
When relocate the unit to another place,
perform evacuation, using vacuum pump.
Choose purge method from the table:
When Using the Vacuum Pump
(For method of using a manifold valve, refer to its operation manual.)
1. Completely tighten the flare nuts, A, B, C, D, connect the manifold
valve charge hose to a charge port of the packed valve on the gas
pipe side.
2. Connect the charge hose connection to the vacuum pump.
3. Fully open the handle Lo of the manifold valve.
4. Operate the vacuum pump to evacuate. After starting evacuation,
slightly loose the flare nut of the packed valve on the gas pipe side
and check that the air is entering.(Operation noise of the vacuum
pump changes and a compound meter indicates 0 instead of
minus)
5. After the evacuation is complete, fully close the handle Lo of the
manifold valve and stop the operation of the vacuum pump.
Make evacuation for 15 minutes and more and check that the
5
compound meter indicates -76cmHg(-1.0x10 Pa).
6. Disconnect the charge hose from the charge connection of the
packed valve at the gas pipe side.
7. Fully open the packed valve stems B and A.
8. Securely tighten the cap of the packed valve.
Make sure no gas come out from connections
with leak detector or soap water.
A: Lo packed valve B: Hi packed valve
C and D are ends of indoor unit connection.
Connective
pipe length
Less than 5m
5 10m (Pipe length-5)x30g
Air purging
method
Use vacuum
pump
Additional amount of
refrigerant to be charged
Open the valve stem until it hits against the
stopper. Do not try to open it further.
Securely tighten the valve stem cap with a
spanner or the like.
Valve stem cap tightening torque.
Gas pipe side ( 9.53): 2940N.cm (500kgf.cm)
Liquid pipe side ( 6.35): 1570N.cm (160kgf.cm)
CAUTION IN HANDING THE PACKED VALVE
CAUTION
1. AIR PURGE
2. GAS LEAK CHECK
3. TEST OPERATION
~
Perform test operation after completing gas leak check at the flare nut
connections and electrical safety check.
1. Connect the power, push the "COOL" button on the remote
controller to begin testing.
2. Check if all the functions works well while testing the air conditioner.
A protection feature prevents the air conditioner from being activated
for about 3 minutes when it is restarted immediately after operation
or when the power switch is turned on.
3. Be sure to set the tickle-type switch on OFF after finishing the test
operation.
Indoor unit
check point
D
B
C
A
Outdoor unit
check point
Cover
Manifold valve
Outdoor
unit
Indoor
unit
Refrigerant gas
Flare nut
Stopper
Compound meter
-76cmHg
Handle Lo Handle Hi
Charge hose Charge hose
Vacuum pump
Pressure gauge
Cap
Valve body
Packed valve
Half union
12.7mm
6.35mm
AC
D
B
Packed valve
Valve stem
Auto/cool o
Manual
switch
9.53mm
2940
(300kgf.cm) 3430
(350kgf.cm)
9.53
1.6 1.0
9.53mm
( 10000Btu/h)
( 9000Btu/h)
2(N)
2200019232 CS232-I
5. Connecting Cables
1. Indoor/Outdoor connection cable should be H07RN-F5G type.
2. Remove the panel and Screw Covers (3), remove Screws (4), then take
out the Frame.
3. Connect cables according to their marks to terminals.
4. Wrap those cables not connected with terminals with insulation tapes, so
that they will not touch any electrical components.
Note: Some models may be equipped with power cord, connecting cables
according to the terminal block with five terminals in the wiring diagram.
10mm
10mm
40mm
40mm
Cooling only
type.
Cooling & heating
type.
Code wire
Panel
Frame
Screw Cover
Use vacuum
pump
For the R407C refrigerant model, make sure
the refrigerant added into air conditioner is
liquid form in any cases.
Terminal block of indoor unit
To outdoor unit To outdoor unit
Power supply Power supply
Cord clamp
1 2(N) 3 4 1 2(N) 3 4
L L
N N
1

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Midea Glory Eco MSG-xxHRN2 bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Midea Glory Eco MSG-xxHRN2 in de taal/talen: Engels als bijlage per email.

De handleiding is 0,21 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

Andere handleiding(en) van Midea Glory Eco MSG-xxHRN2

Midea Glory Eco MSG-xxHRN2 Gebruiksaanwijzing - Nederlands - 13 pagina's

Midea Glory Eco MSG-xxHRN2 Gebruiksaanwijzing - English - 12 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info