Wiring Scheme Manual and
Instructions for Initial Operation
Control lights:
1. Voltage
2. 'OPEN' button
3. 'CLOSE' button
Control elements
11. 'OPEN' button
12. 'CLOSE' button
13. 'STOP' button
14 S3 MAINTENANCE RELEASE limit switch
Plug connections:
21. X10 Membrane keypad
22. X10a Cable slack device
23. X4 Spindle limit switch
24. X3 Motor
25. X2 Mains
26. X6 Control extensions
Connecting terminals:
31. X7H Cable safety device switch
Programming switch:
41. S7 Press and release in 'OPEN' direction
Figures to the Control 22 / 23 control unit
C
B
A
D
E
Overview of door and surrounding area
A Membrane keypad
B Control connections in the operator
C Jack bolt limit switch or cam limit switch
D Site electric socket CEE standard 16 A
E Door leaf connection
Fig. A/1: Membrane keypad and key switch
0
I
Key switch:
0 red OFF
1 blue ON
2
1
3
11
13
12
Fig. A/2: Control 22 control unit Fig. A/3: Control 23 control unit
31
14
22
21
24
25
41
26
23
3
1. Contents
Chapter Page
Figures 2
Explanation of symbols inside of back cover
1. Contents 3
2. Important! Read carefully before carrying out any work 4
3. Initial operation of the Control 22 / 23 control unit
3.1 'Press-and-release' or 'press-and-hold' in the 'OPEN' direction 5
3.2 Connections in the control unit 5
3.3 Control unit - door leaf connection 6
3.4 Initial operation of the control unit 6
3.5 Setting the travel limits 7
3.5.1 Dynamic 121 - 128 7
3.5.2 Dynamic 3-201 - 3-208 9
3.5.2.1 Setting of end position DOOR CLOSED 9
3.5.2.2 Setting of limit switch SKS-STOP 10
3.5.2.3 Setting of end position DOOR OPEN 11
4. Connection and initial operation of the extensions
4.1 External control elements (description of function) 12
4.2 Connection of external operating devices with system plug 12
5. Appendix
5.1 Wiring diagrams 14
5.1.1 Control 22 wiring diagram 14
5.1.2 Control 23 wiring diagram 16
5.2 Test instructions 18
4
2. Important! Read carefully before carrying out any work!
This control unit may only be connected and put into operation by qualified and
suitably trained specialist personnel. For the purpose of this description qualified and
suitably trained specialist personnel are persons who are adequately instructed or
supervised by qualified electricians and are thus in a position to recognize the hazards
that electricity can cause. Moreover, they must hold qualifications consistent with the
work being carried out, in particular they must
• knowledge of applicable electro-technological regulations,
• have received training in the use and maintenance of adequate safety equipment,
• as well as first aid training.
Before carrying out any cabling work, it is essential to disconnect the control unit from
the mains supply.
Observe local safety regulations!
Always lay mains cable and control cable separately!
Control voltage 24 V DC.
Before putting the control unit into operation, it is essential to ensure that there are no
persons or objects within the door's area of operation, since a number of settings set
the door in motion.
All available emergency command devices must be tested prior to
initial operation.
The door operator may only be installed with the door closed.
After installation and initial operation, those persons or their representatives
responsible for operating the door system must be shown how the door system works.
Special note for installation according to protection category IP 65:
At the very latest following initial operation, the cable with plug allowing connection
to the mains must be replaced by a direct mains connection. At the same time a mains
isolator switch must be fitted.
Non-compliance with these warning and safety instructions can
lead to bodily injury and material damage.
5
Insert the mains plug of the control unit into a site electric socket in accordance
with CEE standard 16 A.
Check that the voltage at the electric socket corresponds with that given
on the control unit's data plate and also that its protection category
complies with local requirements.
If the control unit is to be connected directly to the mains, a mains
isolator switch will have to be installed.
For the Control 22: control unit: The rotary field must be of clockwise
rotation.
Operational check of the mains connection
3.1
Selecting 'press-and-release' / 'press-and-hold' operation in the
'OPEN' direction
Via the programming switch S7 (41) the control unit's mode of operation can
be switched from 'press-and-release' to 'press-and-hold' push button operation
in the 'OPEN' direction. With the 'press-and-hold' operation mode, the operator
is started by pressing and holding the 'OPEN' button (11) and stopped by
releasing it again.
For initial operation and the basic settings of the limit switches,
switch the programming switch S7 (41) to the OFF position to programme
press-and-hold operation.
3.2 Connections in the control unit
Connecting the membrane keypad
Connect the system cable for the supplied membrane keypad to the socket X10
(28) in the control unit.
The control unit features a static current circuit. If a malfunction occurs
in any of the safety devices of the door system, the static current circuit
immobilizes power operation of the door.
Elements within this static current circuit are the cable slack switch and wicket
door switch, the cable safety device and the limit switch of the night lock.
3. Initial operation of the Control 22 / 23 control unit
6
3.3 Control unit - door leaf connection
Connecting the cable slack device
Connect the system cable to the X10a (29) socket in the control unit.
Fig. B/1: Control unit - door leaf connection
3.4 Initial operation of the control unit
With the following settings, it is important to ensure that the door is
NEVER allowed to close or open fully. Halt the door at least 50 cm before
it reaches its mechanical travel limits by pressing the 'STOP' button (13),
or if in the press-and-hold mode, by releasing the push button.
• Half open the door by hand.
• Switch on at the mains.
The VOLTAGE control light (1) on the control panel should light up.
- if this is not the case, look up section 'no voltage' in the test instructions.
• Press the 'OPEN' button (11).
The door should open.
- Door closes: press the 'STOP' button, reverse the rotary field.
- Door doesn't move: Look up section 'no function' in the test instructions.
3. Initial operation of the Control 22 / 23 control unit
Wiring diagram legend:
Switches (system plugs):
S5 Wicket door switch
S6 Cable slack switch
Switches (screw terminals):
S5a * Wicket door switch
S6a * Cable slack switch
S6b * Cable safety device
Connecting terminals:
X7H Static current circuit
(in the control unit)
X7b Coiled cable
X7h Static current circuit
Plug connections:
X10a Static current circuit
(in the control unit)
X7a Coiled cable
X7c Coiled cable
X7d Cable slack switch
X7f Connection lead
X7g Wicket door contact
* To connect, the short-circuit bridge
must be removed.
7
Operational check of the safety circuit
• Actuate each safety element separately.
Power operation of the door should now no longer be possible.
- If this is not the case, check the electrical connection of the respective safety
element.
3.5 Setting of the limit switches
3.5.1 Dynamic 121 - 128
Close the door manually.
Remove the door operator's transparent cover.
Release the switching spindle by shifting the red no-load lever (50) forward and
pressing the wheel's inner door link disc (51) towards the spindle (see fig. C/1).
Turn the knurled wheel (52) clockwise until the switching carriage (53) actuates
the 'CLOSE' limit switch. The red LED (54) lights up (see fig. C/1). Relatch the
door link disc and make secure by re-engaging the no-load lever (makes an
audible click on engaging), as shown in fig. C/2. If necessary, re-adjust the
setting via the fine adjustment facility (55) on the switching carriage; turn the
adjusting cam clockwise: the operator cuts off earlier.
3. Initial operation of the Control 22 / 23 control unit
Fig. C/1: Limit switch setting (door is closed)
55
53
51
52
50
54
8
The door must now be opened fully by hand.
Via the smaller knurled wheel (56), now turn the adjusting spindle, until the 'OPEN'
limit switch (57) is actuated by the switching carriage (see fig. C/2). The green LED
(58) lights up.
Return the transparent cover to the operator.
Fig. C/2: Limit switch setting (door is open)
3. Initial operation of the Control 22 / 23 control unit
56
57
58
9
3.5.2 Dynamic 3-201 - 3-208
Note / Advice
For setting the cams you need a socket head screwdriver with handle,
width across flats 2,5mm.
3.5.2.1 Setting of end position DOOR CLOSED
Move the door manually into the mechanical end position DOOR CLOSED.
Open the case lid of the door operator.
Loosen the locking device (grub screw (J)) of the switch cam (A).
Adjust the switch cam A so that the limit switch DOOR CLOSED (G) is operated as
shown in illustration D.1 (position H).
Fix the switch cam (A) again by tightening the grub screw (J).
If necessary, adjust the position of the door DOOR CLOSED with the screw for fine
adjustment (K) at the switch cam.
Fig. D/1: Setting of end position DOOR CLOSED
3. Initial operation of the Control 22 / 23 control unit
ABCDEF
A
H
G
J
K
10
3.5.2.2 Setting of limit switch SKS-STOP
The limit switch SKS-STOP deactivates the protection of the closing edge shortly
before reaching the end position DOOR CLOSED to avoid wrong reactions
(for example unwanted reciprocating).
Loosen the locking device (grub screw (J)) of the switch cam (E).
Adjust the switch cam (E) so that the limit switch SKS-STOP (G) is operated
approx. 5 cm before the profile of the door reaches the floor.
Fix the switch cam (E) again by tightening the grub screw (J).
3. Initial operation of the Control 22 / 23 control unit
ABCDEF
E
H
G
J
K
Fig. D/2: Setting of limit switch SKS-STOP
18
5. Appendix
5.2 Test instructions
Fault
No voltage
No function
Only operates in press-
and-hold mode in
OPEN direction
Signal/Message
Voltage control light doesn't
light up
Cause
No voltage
Emergency hand chain is not in the home
position
Thermal overload protection in motor has
been activated
Membrane keypad is locked
(key switch pointing at red mark)
Static current circuit (control elements) is open
Static current circuit (door leaf) is open
Operator is disengaged
Cable safety device switch has been activated
S7 programming switch is at OFF position
(press-and-hold mode in OPEN direction)
Remedy
Check voltage. Check main fuses in the electric distribution and the
mains plug connection.
Return the emergency hand chain to the home position (see
Operator Installation Instructions)
Allow motor to cool down
Unlock the membrane keypad (key switch points at blue mark)
Insert control element plug into X10 socket
Check cable slack, wicket door and cable safety switch
Check static current circuit connection in socket X10a
Engage maintenance release/quick release.
Check cable safety device switch.
Connection X7H socket in door operator controls
Switch S7 programming switch to ON position (press-and-release in
OPEN direction).
18

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Marantec Control 23 bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Marantec Control 23 in de taal/talen: Engels als bijlage per email.

De handleiding is 0,38 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

Andere handleiding(en) van Marantec Control 23

Marantec Control 23 Gebruiksaanwijzing - Deutsch - 20 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info