Manual for installation and operation, Comfort 870 GB (#81125) 31
6. Installation
Terminals XP54B / XP54A
Advice:
A two-wire photocell connected to
terminals X62B / XB62A will be
recognised automatically by the
controls after “Mains On”.
The photocell can be deactivated later
(Level 8 / Menu 1).
If the contacts of a closing prevention
device are open, the gate can no longer
be closed.
Label Type / function
P6 0 Volt
26
Signal , photocell,
Gate travelling direction OPEN (XP62B)
27
Signal , photocell,
Gate travelling direction CLOSE (XP62A)
R Receiver for the two-wire photocell
T Transmitter for the two-wire photocell
Label Type / function
P5 0 Volt
46
Signal, closing edge safety device,
Gate travelling direction OPEN (XP54B)
47
Signal, closing edge safety device,
Gate travelling direction CLOSE (XP54A)
Terminals XP62A / XP62B
Attention!
If an 8.2 kΩ contact strip closing edge
safety device is connected, the 8.2 kΩ
resistors installed at terminals XP54B
closing edge OPEN and XP54A closing
edge CLOSE must be removed.