IMPOSTA LA VELOCITA’
DELLA POMPA PWM AD
ALTA EFFICIENZA
IMPOSTAZIONI-POMPA PWM
AUTO
B
E
INFO
OK
C
D
B
ESCI
IMPOSTA LA TEMPERATURA
DI ATTIVAZIONE DELLA FUNZIONE
ANTIGELO
IMPOSTAZIONI-FUNZ ANTIGELO
DISATTIVA
FUNZ ANTI.
ATTIVA
FUNZ ANTI.
57
13 - SETTINGS MENU
Technical Dept. - All rights reserved - Reproduction is prohibited
PWM PUMP
This function is used to set high eciency pump speed.
To enter the function press:
from the Settings menu- press ok (E key), press the C-D key (arrow) and scroll up to PWM Pump, press OK (E key)- Modify the percentage
using the central C and D keys, press the E key to conrm.
FUNCT. ANTI-FREEZE
It consists of activating the pump (level 1) or the stove (level 2) and is automatically activated by the temperature read by the stove probe
and the temperature read by the external probe (if present and connected to the aux input).
The level 1 anti-freeze activation conditions (PUMP ON) are:
boiler temp < anti-freeze set +3°C
The level 2 anti-freeze activation conditions (PUMP and FLAME ON) are:
boiler temp = anti-freeze set
Anti-freeze activation conditions on external probe (if present) are:
ext_ltered temp < anti-freeze set -3℃
To enter the function, press and adjust anti-freeze set:
from the Settings menu- press ok (E key), press the C-D key (arrow) and scroll up to Antifreeze function and press OK (E key)- Activate and
set (from 1 to 5°C) or deactivate the function and press the E key to conrm.
PELLET SENSOR
Optional Function.