INSTALLER’S MANUAL
A
【1】
A1
【2】
Recommendations
L Ensure that the oven is set to the type of gas used (see label on the gas connector).
If the gas supply is not compatible with the gas setting of your range the setting must be modied.
Refer to the “Changing the hob gas” section of the present instructions.
Butane-fuelled units : Connect unit to 2.6 kg/h pressure reducer. Use two cylinders connected to a
3-way valve ahead of the pressure regulator in case of prolonged, continuous duty.
Propane-fuelled units : Connect unit to a 3.0 kg/h pressure reducer. Use two cylinders and a 3-
way valve ahead of the pressure regulator in case of prolonged, continuous duty. The use of 37 kg
or extern cryogenic tanks is both possible and recommended.
Voor het aansluiten :
Check :
◊ That the gas-supply pressure matches the gas pressure for which the range is set.
◊ Pipework is perfectly clean in order to prevent the injectors becoming blocked and malfunctioning
of the magnetic heads.
◊ The gas for which the appliance was set up : rating plate and markings.
◊ Cross-sectional area of gas supply pipework is compatible with the appliance’s thermal output.
◊ Correct fresh air flowrate (Air supply sufcient to enable correct combustion to occur - see
appendix 0).
Gas connection :
Male coupling Ø 15/21, 1/2” gas thread on A (fig.【1】).
After connection :
Check the mains pressure at A1 (fig.【2】).
Check your connection is gastight.
GAS CONNECTION